284720-BIM-D-0909
10
Johnson Controls Unitary Products
FIGURE 7 - ROTARY COMPRESSOR MOUNTING
MOUNTING STUD
NUT
COMPRESSOR BASE
GROMMET
UNIT CHASSIS
(There must be clearance between Grommet & Nut)
0.02 – 0.08 in. (0.5 – 2mm)
TABLE 3: NATURAL GAS APPLICATION DATA - SINGLE STAGE
AVAILABLE ON
MODELS
INPUT
(MBH)
1
OUTPUT
(MBH)
GAS RATE
2
FT.
3
/HR.
NUMBER OF
BURNERS
TEMP. RISE ºF AT
FULL INPUT
3
MIN.
MAX.
2, 2-1/2, 3 TON
45
36
42
2
25
55
2, 2-1/2 TON
70
56
65
3
30
60
3 TON
70
56
65
3
25
55
3-1/2, 4, 5 TON
80
64
74
3
25
55
3 TON
90
72
84
4
30
60
3-1/2 TON
108
87
100
4
45
75
4, 5 TON
108
87
100
4
35
65
4, 5 TON
135
108
126
5
45
75
1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be
reduced by 4% for each 1,000 feet above sea level.
2. Based on 1075 BTU/Ft.
3
.
3. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not
be below 55°F.
TABLE 4: NATURAL GAS APPLICATION DATA - TWO STAGE
AVAILABLE ON
MODELS
INPUT (MBH)
1
HIGH FIRE / LOW FIRE
OUTPUT (MBH)
HIGH FIRE/LOW FIRE
GAS RATE
2
FT.
3
/HR.
HIGH FIRE/LOW FIRE
NUMBER OF
BURNERS
TEMP. RISE ºF AT
FULL INPUT
3
MIN.
MAX.
2, 2-1/2 TON
70 / 45.5
56 / 36.4
65 / 42
3
30
60
3 TON
70 / 45.5
56 / 36.4
65 / 42
3
25
55
3 TON
90 / 58.5
72 / 46.8
84 / 54
4
30
60
4, 5 TON
108 / 70.2
87 / 56.2
100 / 65
4
35
65
4, 5 TON
135 / 87.75
108 / 70.2
126 / 82
5
45
75
1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be
reduced by 4% for each 1,000 feet above sea level.
2. Based on 1075 BTU/Ft.
3
.
3. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not
be below 55°F.