343615-YTG-A-0807
12
Unitary Products Group
TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63
77
84
77
84
81
85
79
84
125
71
71
72
73
74
75
71
72
250
57
58
55
56
66
66
60
61
500
53
53
51
51
60
60
55
55
1000
50
50
45
46
60 60 53 53
2000
49
49
43
44
58
58
50 50
4000
49
49
42
43
59
59
47
47
8000
49
49
48
48
54
54
47 47
DY060 / 5 Ton
Horizontal Ducted Inlet
840
845
1166
1188
0.2
0.6
0.3
1.3
1.51
0.80
1695
1100
2618
1323
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
0.67
0.50
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Octave Center Freq.
ID Blower
Only (dB)
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63
82
87
79
88
88
89
82
87
125
75
76
72
74
82
83
78
78
250
69
69
66
66
79
79
73
73
500
64
64
60
60
72
72
66
66
1000
59
60
55
56
68
68
61
61
2000
55
55
50
50
65
65
57
57
4000
58
58
52
52
68
68
60
60
8000
55
55
49
49
66
67
56
56
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
0.6
1100
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
DY060 / 5 Ton
Horizontal Ducted Discharge
840
845
1166
1188
0.80
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Eq uipment .
0.50
0.3
2618
1.51
Cooling
Operation
2
(dB)
0.2
1695
0.67
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
1.3
1323