036-21502-002-A-0303
Unitary Products Group
11
TABLE 1: SOUND POWER RATING
1
UNIT
SIZE
CFM
ESP
BLOWER
SOUND POWER (db 10
-12
Watts)
Octave Band Centerline Frequency (Hz)
SWL
dB(A)
dB(A)
@
10Ft.
2
IWG
SPEED
KW
63
125
250
500
1,000
2,000
4,000
8,000
036
1,200
0.6
LOW
0.60
84
84
74
67
69
62
57
52
74
41
048
1,600
0.55
HIGH
0.80
85
85
75
68
70
63
58
53
75
42
060
2,000
0.45
HIGH
1.00
86
86
76
69
71
64
59
54
76
43
072
2,200
0.3
HIGH
1.35
87
87
77
70
72
65
60
55
77
44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
1
1. 80/67°F Indoor and 95°F outdoor.
MODEL
MBH
EER
2
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
SEER
3
3. SEER = Seasonal Energy Efficiency Ratio.
DM036
36.0
9.1
10.0
DM048
47.4
9.0
10.0
DM060
59.0
9.1
10.0
DM072
72.0
9.0
-
TABLE 3: GAS HEAT RATINGS
1
1. All units are single-stage heating.
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DM036N04
DM036N08
50
100
40
79
80.9
80.5
15 - 45
40 - 70
DM048N06
DM048N10
75
125
59
99
80.9
80.3
25 - 55
45 - 75
DM060N08
DM060N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65
DM072N08
DM072N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65