77
Service Manual
F:Inspection
● Check the quality of
flare tool
. If there is any blemish,
flare
the
port again according to the steps above.
The length is equal
Improper
flaring
leaning
damaged
surface
crack
uneven
thickness
Smooth surface
Downwards
Pipe
Shaper
Union pipe
Pipe
Expander
Hard
mold
Pipe
Pipe
Pipe cutter
Leaning
Uneven
Burr
Note:
Improper pipe
flaring
is the main cause of refrigerant leakage.
Please
flare
the pipe according to the following steps:
A:Cut the pip
e
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
B:Remove the burrs
● Remove the burrs with shaper and prevent the burrs from getting into the pipe.
C:Put on suitable insulating pipe
D:Put on the
flare
nut
● Remove the
flare
nut on the indoor connection pipe and outdoor valve; install
the
flare
nut on the pipe.
E:
Flare
the
pipe
●
Flare with 45° flaring tool
● "A" is different according to the diameter, please refer to the sheet below:
Outer diameter(inch)
A(inch)
Max
Min
Ф1/4
2/39
1/36
Ф3/8
1/16
1/51
Ф1/2
1/14
1/51
Ф5/8
5/53
2/23
Appendix 3: Pipe
Flaring
Method
Note: