"DPV" SERIES VERTICAL INDOOR SYSTEM

GENERAL MECHANICAL SPECIFICATIONS

GENERAL

All models 5-15 tons ship as factory-charged unitized packages. The 20 ton model shall be shipped as

separate evaporator and condensing unit modules (nitrogen holding charge only). All units may be field

split and installed as separate modules to suit on-site requirements. All packages are designed for free-

standing mounting on the floor, or on a field fabricated structural steel stand. The 5, 8, and 10 ton models

are shipped with vertical evaporator fan discharge as standard. The 12, 15, and 20 ton models are

shipped horizontal discharge as standard.

CABINET

All cabinets are completely constructed of heavy gauge galvanized steel. The entire unit interior ( both

evaporator and condensing section ) is insulated with 1/2" thick, 2 lb. density insulation. Service panels

are equipped with lifting handles for ease of removal and handling. Duct flanges for condenser discharge,

condenser intake, and evaporator discharges, are provided with the unit for field installation. Duct flange

on evaporator return is incorporated into the filter frame.

COMPRESSORS

All models utilize "Scroll" type hermetic compressors. Compressors are mounted on rubber isolators to

minimize vibration transmission. Internal overload protection is provided. External high pressure and low

pressure cutout switches are included in each compressor control circuit.  Crankcase heaters are

standard on all models.

REFRIGERANT CIRCUITS

The 5 ton units have a single refrigeration circuit. The 8-20 ton units feature two independent refrigeration

circuits. Each refrigeration circuit includes an adjustable thermal expansion valve (with external

equalizer), liquid line filter drier, sight glass/moisture indicator, and service gauge ports.

EVAPORATOR AND CONDENSER COILS

The evaporator and condenser coils are constructed of internally enhanced copper tubes mechanically

bonded to rippled aluminum plate fins. Both coils are employed in a draw-thru configuration. Large

evaporator coil face area minimizes potential water blow-off.

INDOOR/OUTDOOR FANS

Forward curved, double inlet and double width centrifugal blowers are used for both evaporator and

condenser air movement. Blower wheels are fabricated of galvanized steel. Blowers employ solid steel

shafts, supported in permanently lubricated ball bearing. All blowers are belt driven. Variable-pitch motor

sheaves allow for field adjustment of blower rpm.

ELECTRICAL/CONTROLS

All units are completely factory wired with all necessary controls. Manual reset protection is provided on

both evaporator and condenser motors. A manual reset circuit is also provided on each compressor

control circuit in the event of high/low pressure cutout.  A 24 volt control circuit, with oversize transformer,

is provided for field connection.

FILTERS

All models are shipped with 2-inch thick medium-efficiency throwaway filters factory installed. Filter rack

is external to the cabinet (shipped loose).

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

March 2008

MECHANICAL SPECIFICATIONS

DPV180 VERTICAL UNIT

 AIR-COOLED SELF-CONTAINED

Form YK145.12-PA7 (308)

2 of 4

Page 15

Содержание D*V

Страница 1: ...D V Model Air Cooled Self Contained Indoor Packaged Units 2 25 Tons Preliminary Application Data July 28 2008 Page 1...

Страница 2: ...STANDARD MOTOR ELECTRICAL DATA OVERSIZED MOTOR MODEL SUPPLY 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3000 3200 DPV096...

Страница 3: ...le refrigeration circuit The 8 20 ton units feature two independent refrigeration circuits Each refrigeration circuit includes an adjustable thermal expansion valve with external equalizer liquid line...

Страница 4: ...0 9 92 0 108 8 76 0 96 8 96 8 97 2 90 4 104 1 74 5 Ambient Condenser Air Temperature F 5 1 1 F 5 0 1 B W E B W E 62 F 67 F 72 F 62 F 67 F 72 F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75 F 83 3 69...

Страница 5: ...March 2008 DIMENSIONAL DATA DPV096 DPV120 VERTICAL UNIT AIR COOLED SELF CONTAINED Form YK145 12 PA4 308 4 of 4 DPV096 AND DPV120 DIMENSIONAL DATA Page 5...

Страница 6: ...ECTRICAL DATA OVERSIZED MOTOR MODEL SUPPLY 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3600 DPV120 DPV120 DPV120 DPV120...

Страница 7: ...le refrigeration circuit The 8 20 ton units feature two independent refrigeration circuits Each refrigeration circuit includes an adjustable thermal expansion valve with external equalizer liquid line...

Страница 8: ...140 2 98 6 125 1 125 1 126 4 119 5 134 8 96 7 Ambient Condenser Air Temperature F 5 1 1 F 5 0 1 10 TON B W E B W E 62 F 67 F 72 F 62 F 67 F 72 F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75 F 106 3...

Страница 9: ...March 2008 DIMENSIONAL DATA DPV096 DPV120 VERTICAL UNIT AIR COOLED SELF CONTAINED Form YK145 12 PA5 308 4 of 4 DPV096 AND DPV120 DIMENSIONAL DATA Page 9...

Страница 10: ...STANDARD MOTOR ELECTRICAL DATA OVERSIZED MOTOR MODEL SUPPLY 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 4300 4800 DPV144...

Страница 11: ...le refrigeration circuit The 8 20 ton units feature two independent refrigeration circuits Each refrigeration circuit includes an adjustable thermal expansion valve with external equalizer liquid line...

Страница 12: ...72 1 119 1 152 2 152 2 153 4 141 2 164 9 116 6 Ambient Condenser Air Temperature F 5 1 1 F 5 0 1 12 TON B W E B W E 62 F 67 F 72 F 62 F 67 F 72 F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75 F 130 2...

Страница 13: ...DPV144 DPV180 March 2008 DIMENSIONAL DATA DPV144 DPV180 VERTICAL UNIT AIR COOLED SELF CONTAINED Form YK145 12 PA6 308 4 of 4 DPV0144 AND DPV180 DIMENSIONAL DATA Page 13...

Страница 14: ...drop from wet coil and clean filters 3 Shaded areas indicate oversize motors EVAPORATOR FAN PERFORMANCE CONDENSER FAN PERFORMANCE ELECTRICAL DATA STANDARD MOTOR MODEL SUPPLY 0 2 0 4 0 6 0 8 1 0 1 2 1...

Страница 15: ...le refrigeration circuit The 8 20 ton units feature two independent refrigeration circuits Each refrigeration circuit includes an adjustable thermal expansion valve with external equalizer liquid line...

Страница 16: ...11 9 150 9 189 9 189 9 192 2 180 6 202 0 147 5 Ambient Condenser Air Temperature F 5 1 1 F 5 0 1 15 TON B W E B W E 62 F 67 F 72 F 62 F 67 F 72 F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75 F 161 6...

Страница 17: ...DPV144 DPV180 March 2008 DIMENSIONAL DATA DPV144 DPV180 VERTICAL UNIT AIR COOLED SELF CONTAINED Form YK145 12 PA7 308 4 of 4 DPV144 AND DPV180 DIMENSIONAL DATA Page 17...

Страница 18: ...4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7200 8000 DPV240 DPV240 DPV240 DPV240 DPV240 DPV240 DPV240 DPV240 10200 657 1 89...

Страница 19: ...le refrigeration circuit The 8 20 ton units feature two independent refrigeration circuits Each refrigeration circuit includes an adjustable thermal expansion valve with external equalizer liquid line...

Страница 20: ...279 9 202 1 276 1 276 1 261 2 245 1 267 1 197 7 Ambient Condenser Air Temperature F 5 1 1 F 5 0 1 20 TON B W E B W E 62 F 67 F 72 F 62 F 67 F 72 F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75 F 212...

Страница 21: ...March 2008 DIMENSIONAL DATA DPV240 VERTICAL UNIT AIR COOLED SELF CONTAINED Form YK145 12 PA8 308 4 of 4 DPV240 DIMENSIONAL DATA Page 21...

Страница 22: ...D MOTOR MODEL SUPPLY 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 9000 785 3 42 836 3 80 884 4 18 930 4 56 975 4 97 1019...

Страница 23: ...ion Internal overload protection is provided External high pressure and low pressure cutout switches are included in each compressor control circuit Crankcase heaters are standard on all models REFRIG...

Страница 24: ...47 7 246 2 310 6 310 6 311 0 293 2 330 9 240 5 Ambient Condenser Air Temperature F 5 1 1 F 5 0 1 25 TON B W E B W E 62 F 67 F 72 F 62 F 67 F 72 F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75 F 263 1...

Страница 25: ...March 2008 DIMENSIONAL DATA DPV300 VERTICAL UNIT AIR COOLED SELF CONTAINED Form YK145 12 PA9 308 4 of 4 DPV300 DIMENSIONAL DATA Page 25...

Отзывы: