Johnson Controls Unitary Products

operation. Independent blade design insures proper control and 
less than 1% leak rate. Includes hood and mesh bird screen 
filter integrated into the hood, dry bulb sensor and relief 
damper. Separate field accessories of single enthalpy and dual 
enthalpy are also available.

SINGLE ENTHALPY SENSOR -

 Sensor replaces dry bulb 

sensor standard in economizer kit. Provides improved 
economizer operation by sensing the dry bulb temperature from 
outdoors plus the enthalpy content of the outdoor air.

DUAL ENTHALPY SENSOR -

 Additional sensor to single 

enthalpy sensor. Sensor senses both the return air temperature 
dry bulb and humidity in conjunction with the single enthalpy to 
determine the most economical mix. 

Single Enthalpy sensor 

also required.

UPGRADE SAFETY PACKAGE -

 Contains screw-in type High 

pressure, Low Pressure/Loss of Charge switch, freeze protection 
switch and lockout relay. Switches are placed onto existing 
schrader ports located in the unit by furnished adapters. When 
abnormal conditions are sensed through the pressure switches, 
the unit will lock out preventing any further operation until reset or 
problem is corrected. Package agency approved.

HAIL GUARD KIT -

 Kit contains protected grilles made of 

expanded aluminum grilles with full perimeter  inch frame. 
Sloped hoods are also included to assure maximum protection..

ANTI SHORT CYCLE TIMER -

 Automatically prevents the 

compressor from restarting for 5 minutes after cycled off. Not 
required if Thermostat 2ET07700224 and 2ET04700224 are 
used.

FILTER / FRAME KIT (Single Phase only) -

 Kit contains the 

necessary hardware to field install return air filters into the base 
unit. Pre-cut filter racks and appropriate cleanable standard 
size filters are shipped in one kit. (1" filter is supplied)  This kit is 
available for single phase horizontal or vertical duct application  
only. Standard in all 3 Phase models.

MOTORIZED FRESH AIR DAMPER -

 Designed for duct 

mounted side return and unit mounted down shot return 
applications. Damper capable of providing 0% thru 50% of 
outdoor air (field supplied). Closes on power loss, includes 
hood and screen assembly.

RECTANGLE TO ROUND ADAPTERS -

 Kit includes one 

supply and one return air rectangle to round duct adapter. 
Adapters are preformed and designed to fit over current duct 
openings on the base unit. Transition is from 15” square to 14” 
round.

ROOF CURBS -

 NRCA approved curbs provide proper fit to 

base unit for rooftop installations. Curbs are designed to be 
assembled through hinge pins in each corner. Kit also provides 
seal strip to assure a water tight seal. Eight and 14 inch high 
roof curbs are available.

MANUAL OUTDOOR DAMPER -

 Provides 0% thru 50% 

outdoor air capability (field adjustable). Designed for duct 
mounted side return and unit mounted down shot return  
applications. Includes hood and screen assembly.

WALL THERMOSTAT -

 The units are designed to operate with 

24-volt electronic and electro-mechanical thermostats. All units 
can operate with single stage heat / single stage cool 
thermostats - with or without the economizer.

LOW AMBIENT KIT -

 Kit provides necessary hardware to 

convert unit to operate in cooling cycle down to 0 °F. Standard 
unit operation 45 °F.

TRANSFORMER KIT -

 Kit provides necessary hardware to 

provide single phase models from factory furnished 40 VA 
transformer capability to 75 VA transformer capability.

ELECTRIC HEATERS -

 Each heater package provides easy 

installation of electric heat strips. Slide in design with plug in 
harness and agency approved. Heaters are available from 5.0 
KW sizes and are designed for single point connection.

FIGURE 1 - UNIT CUTAWAY

DIRECT DRIVE 

CONDENSER 

FAN MOTOR 

HIGHLY EFFICIENT 

ENHANCED COPPER 
TUBE/ALUMINUM FIN 

CONDENSER COIL 

LOW VOLTAGE 

TERMINAL BLOCK 

HIGH EFFICIENCY 

COMPRESSOR 

RIGIDLY 

MOUNTED 

BACK AND BOTTOM 

RETURN AIR 

AND SUPPLY AIR 

DUCT OPENING 

3-SPEED DIRECT DRIVE

BLOWER MOTOR WITH 

SLIDE-OUT BLOWER ASSEMBLY 

HIGH VOLTAGE 

TERMINAL BLOCK 

HIGHLY EFFICIENT ENHANCED 

COPPER TUBE/ALUMINUM FIN 

EVAPORATOR COIL 

HEAVY GAUGE 

REMOVABLE 

BASE RAILS 

LONG LASTING 

POWDER PAINT 

FINISH EARTH 

TONE COLOR 

DECORATIVE 

PROTECTIVE 

COIL GUARD 

Содержание CHAMPION D2EB036

Страница 1: ...ds to carry less inventory LOWER INSTALLATION COST Installation time and costs are reduced by easy power and control wiring connections The small base dimension means less space is required on the gro...

Страница 2: ...3 60 POWER SUPPLY DEB MODELS 20 LIST OF TABLES Tbl Pg 1 PHYSICAL DATA 5 2 RATINGS ARI 5 3 COOLING CAPACITIES 2 1 2 TON DEB030 6 4 COOLING CAPACITIES 3 TON DEB036 7 5 COOLING CAPACITIES 3 1 2 TON DEB04...

Страница 3: ...e condenser fan does not disrupt neighboring areas and does not dry out vegetation surrounding the unit The warm air from the top mounted fan is blown up away from the structure and any landscaping Th...

Страница 4: ...ed side return and unit mounted down shot return applications Damper capable of providing 0 thru 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly RECTANGLE TO RO...

Страница 5: ...IL ROWS DEEP 1 1 1 1 1 FINS PER INCH 20 18 16 13 20 FACE AREA Sq Ft 8 3 8 3 11 7 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 3 13 3 10 4 8 5 15 5 15 FILTER FACE AREA Sq Ft Qty Size 2 14 2 14 x 22 COMPRESSO...

Страница 6: ...Power Input kW 3 38 3 28 3 22 3 22 3 45 3 35 3 29 3 28 3 52 3 42 3 36 3 35 3 66 3 55 3 49 3 48 3 79 3 68 3 62 3 61 Sensible Capacity MBH 1 Entering Dry Bulb F 86 16 5 21 3 22 2 22 3 18 5 23 4 23 1 23...

Страница 7: ...ut kW 4 05 3 92 3 93 3 85 4 07 3 94 3 95 3 87 4 09 3 96 3 97 3 89 4 15 4 02 4 02 3 95 4 21 4 08 4 08 4 00 Sensible Capacity MBH 1 Entering Dry Bulb F 86 17 5 23 3 25 0 24 4 19 9 26 3 26 6 26 0 22 3 29...

Страница 8: ...20 4 22 4 47 4 35 4 27 4 29 4 54 4 42 4 34 4 35 4 69 4 57 4 48 4 50 4 84 4 71 4 63 4 64 Sensible Capacity MBH 1 Entering Dry Bulb F 86 22 4 29 3 30 8 31 2 24 8 32 1 32 0 32 4 27 3 34 9 33 1 33 6 29 3...

Страница 9: ...21 5 21 5 49 5 43 5 34 5 33 5 62 5 55 5 46 5 45 5 72 5 66 5 56 5 55 5 83 5 76 5 66 5 65 Sensible Capacity MBH 1 Entering Dry Bulb F 86 27 0 33 2 37 8 37 4 29 6 36 1 38 3 37 9 32 3 39 1 38 8 38 3 34 3...

Страница 10: ...58 7 07 6 90 6 79 6 75 7 25 7 06 6 96 6 91 7 47 7 28 7 17 7 12 7 69 7 50 7 38 7 33 Sensible Capacity MBH 1 Entering Dry Bulb F 86 33 5 42 4 45 0 45 3 37 5 47 1 46 9 47 2 41 4 51 8 48 8 49 1 44 9 53 7...

Страница 11: ...657 1597 640 1542 623 1486 607 1431 590 1336 563 1240 537 Low 1385 520 1349 510 1312 500 1276 490 1235 480 060 5 0 High 2450 1213 2366 1165 2282 1117 2198 1068 2114 1020 1989 993 1864 967 1739 940 Me...

Страница 12: ...E KW CAP MULTIPLIER 240 208 230 75 92 480 460 92 600 575 92 TABLE 11 ELECTRICAL DATA COOLING ELECTRIC HEAT MODEL DEB POWER SUPPLY COMPRESSOR COND FAN MOTORS SUPPLY AIR BLOWER MOTOR ELECTRIC HEAT ACCES...

Страница 13: ...501546 1 15 0 18 24 8 25 25 048 460 3 60 7 1 55 0 0 8 2 0 2NP04501046 1 10 0 12 17 5 20 20 2NH04501546 1 15 0 18 25 1 30 30 2NH04502046 2 20 0 24 1 32 6 35 35 2NH04502546 2 25 0 30 1 40 1 45 45 060 46...

Страница 14: ...RALL 4 1 2 UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN DIA KNOCKOUT HIGH VOLTAGE...

Страница 15: ...2 UNIT WEIGHTS Unit Size Shipping Weight Operating Weight Corner Weights Economizer lbs Roof Curb lbs A B C D 030 333 328 85 81 82 86 40 8 70 14 75 036 338 333 91 80 78 88 042 347 342 94 83 80 91 048...

Страница 16: ...OWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT...

Страница 17: ...ED PANELS 22 14 OPENING FOR RETURN AIR DUCT OPENING FOR SUPPLY AIR DUCT RECOMMENDED DUCT SIZE SUPPLY AIR DUCT x RETURN AIR DUCT x UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FR...

Страница 18: ...Controls Unitary Products FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DEB MODELS 15695BASH0301 SEE DETAIL A T2 M1 2 DETAIL A BLK BLK CCH L1 T1 OPTIONAL CCH S P CONFIGURATION BLK BLK CCH...

Страница 19: ...0508 Johnson Controls Unitary Products 19 TYPICAL WIRING DIAGRAM NOTES TYPICAL WIRING DIAGRAM LEGEND FIGURE 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DEB MODELS 6 F 9 N O T U S E D 2 M 3 2...

Страница 20: ...360101 XTG B 0508 20 Johnson Controls Unitary Products FIGURE 11 TYPICAL WIRING DIAGRAM 460 3 60 AND 575 3 60 POWER SUPPLY DEB MODELS 2...

Страница 21: ...and base unit 10 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPTI copper ridged mount connection INDOOR EVAPORATOR FAN ASSEMBLY 1 Fan shall b...

Страница 22: ...eset to prevent the heating element system from operating at an excessive temperature 3 The heating section assembly shall slide out of the unit for easy maintenance and service 4 Units with electric...

Страница 23: ...360101 XTG B 0508 Johnson Controls Unitary Products 23...

Страница 24: ...change without notice Printed in U S A 360101 XTG B 0508 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 360101 XTG A 0108 Johnson Controls Unitary Products 5005 York Drive Norma...

Отзывы: