11
COIL CLEANING
If the coil needs to be cleaned, it should be cleaned with water.
As an alternative to water, EVAP-Green by Nu-Calgon is the only pH
neutral coil cleaner approved to be used when it is properly diluted.
ENSURE THE CLEANED COILS ARE THOROUGHLY RINSED
AFTER USE OF EVAP-GREEN.
SECTION IX: INSTRUCTING THE OWNER
Assist the owner with registering the unit warranty using the warranty
card included with the unit, or preferably online at
www.upgproductregistration.com
. It is strongly recommended to
complete a startup sheet showing the critical readings of the unit at the
time of commissioning, which can be uploaded as part of the online
registration process.
SECTION X: AIR SYSTEM ADJUSTMENT
Refer to furnace or modular air handler instructions.
FIGURE 23:
Wiring Diagram - EEV
USE COPPER CONDUCTORS ONLY.
IF ALUMINUM CONDUCTORS ARE PRESENT,
ALL APPLICABLE LOCAL AND NATIONAL
CODES MUST BE FOLLOWED.
IPT - INDOOR COIL PRESSURE TRANSDUCER
ITS - INDOOR COIL
7(03(5$785(
SENSOR
EEV - ELECTRONIC EXPANSION VALVE
5292155-UWD-B-0117
EEV MOTOR
PR1
1
T1
GRN
RED
BLK
WHT
BLU
BLU
IPT
YEL
WHT
BLK
EEV
RED
BLU
ORG
WHT
YEL
ITS
LED
INDICATORS
EEV CONTROL BOARD
A
C
R
B
LEGEND
EEV CONTROL
LED DIAGNOSTIC CODES
Control failure OR No power to the control
Normal operation, No active faults
Invalid pressure transducer
Invalid suction temperature
EEV fully open while in superheat mode
Suction pressure out of range
No RS-485 communication
EEV Opening
EEV Closing
LAMP
COLOR
LAMP
CONDITION
DESCRIPTION
NO LAMP
RED
RED
RED
RED
RED
RED
GREEN
YELLOW
N/A
ON
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
ON
ON
INDOOR EQUIPMENT
CONTROL
COMM PORT
CAUTION
Ensure adequate precautions are taken to protect electrical compo-
nents from liquid.
!
NOTICE
Tables 4 and 5 have DRY coil data. Run system indoor fan only for
approximately 15 minutes prior to taking measurements to assure a
dry coil.