Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 13: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW
2
STAGES
AMPS
BP180
208
21.8
184
4.5
15.4
0.0
-
0.0
-
-
73.5
90
E18
13.5
1
37.5
120.3
125
E36
27.0
2
75.1
120.3
125
E54
40.6
2
112.6
160.1
175
E72
54.1
2
150.1
169.4
200
230
21.8
184
4.3
14.4
0.0
-
0.0
-
-
72.1
90
E18
18.0
1
43.3
126.1
150
E36
36.0
2
86.6
126.3
150
E54
54.0
2
129.9
147.9
175
E72
72.0
2
173.2
191.2
225
460
11.0
90
2.2
7.2
0.0
-
0.0
-
-
36.4
45
E18
18.0
1
21.7
63.4
70
E36
36.0
2
43.3
63.4
70
E54
54.0
2
65.0
74.0
90
E72
72.0
2
86.6
95.6
110
575
9.3
73
1.7
5.9
0.0
-
0.0
-
-
30.2
35
E18
18.0
1
17.3
51.9
60
E36
36.0
2
34.6
51.9
60
E54
54.0
2
52.0
59.3
70
E72
72.0
2
69.3
76.7
90
BP240
208
33.6
225
3.7
20.0
0.0
-
0.0
-
0.0
110.4
125
E18
13.5
1.0
37.5
157.2
175
E36
27.0
2.0
74.9
157.2
175
E54
40.6
2.0
112.7
165.9
175
E72
54.1
2.0
150.2
204.1
225
230
33.6
225
3.7
20.0
0.0
-
0.0
-
0.0
110.4
125
E18
18.0
1.0
43.3
164.5
175
E36
36.0
2.0
86.6
164.5
175
E54
54.0
2.0
129.9
164.5
175
E72
72.0
2.0
173.2
218.7
225
460
17.3
114
1.9
10.0
0.0
-
0.0
0
0.0
56.5
70
E18
18.0
1.0
21.7
83.6
90
E36
36.0
2.0
43.3
83.6
90
E54
54.0
2.0
65.0
83.6
90
E72
72.0
2.0
86.6
110.7
125
575
13.5
80
1.5
8.2
0.0
-
0.0
-
0.0
44.6
50
E18
18.0
1.0
17.3
66.2
70
E36
36.0
2.0
34.6
66.2
70
E54
54.0
2.0
52.0
66.2
70
E72
72.0
2.0
69.3
87.9
90