13.14.- Firestat

The  unit  includes,  as  standard  equipment,  an  impulse  air 
probe that locks out at 80° C and must be reset manually to 
resume operation.
Also available, as an accessory, is a manual adjust and reset 
temperature probe to be fitted in the impulse plenum of the 
unit. If the set temperature is reached in this area, the unit is 
locked out and the probe and control must be reset manually 
to resume operation. 
The fire detecting thermostat (Firestat) is a protection device 
for the unit. It should not be used as protection system for 
the building or other installations. Use is subject to compli-
ance with local regulations that affect the unit (with regard to 
ventilation systems, fire prevention, etc.). Depending upon 
these  regulations,  this  option  could  require  the  use  of  an 
economiser or a motor-driven damper.

13.15.- Copper fin coils

Coils  with  copper  fins  achieve  the  greatest  anticorrosion 
protection for installations in seaside areas, ensuring 100% 
efficiency. Applied to both condensing (outdoor) as well as 
evaporating (outdoor) units. See section No. 4.. for weight 
increase on standard units.

13.16.- "Blue Fin" coils

Aluminium fins with a varnish type coating and a polyurethane 
base, offering anticorrosion resistance of up to 1000 H.N.S. 
(ASTM-B117).

13.17.- Mounting base, Roof Curb, fixed type

For  installing  on  flat  rooftops  without  any  pitch.  Structure 
made of galvanized steel sheeting, supplied as a kit to be 
assembled and installed on the job site.
Allows assembling the ducts directly from inside the building, 
prior to location of the rooftop unit, and provides an airtight 
bond between the unit and the roof.
The  roof  curb  assembly  comprises  two  parts.  In  the  duct 
connecting section, it forms a closed frame that fits beneath 
the base of the unit. A 40 x 25 mm. self-adhesive gasket is 
supplied for application along the entire contact perimeter of 
the frame with the base, thus achieving an airtight seal. For 
the condensing section, a support is supplied for location 
beneath the compressor compartment.
Both parts of the roof curb must be anchored to the support-
ing structure of the roof. The nuts and bolts supplied can be 
used for this purpose; or welding. To avoid water or humidity 
seeping into the interior of the building, the full external pe-
rimeter of both parts must be insulated and sealed with the 
same material used to finish the roof. See mounting details 
in Fig. 15a.

13.18.- Mounting base, Roof Curb, adjustable 
type

For installation on rooftops with pitches of up to 4° (7%) or 
6.5°  (11%),  depending  upon  the  location  of  the  unit. With 
characteristics similar to those of the fixed version, but with 
the advantage of being able to level the supporting surface of 
the unit to compensate the pitch of the rooftop. See mounting 
details in Fig. 15b.

the unit can operates correctly at minimum outdoor tempera-
tures of -18° C.

13.10.- Electric heater

Available for cool only and heat pump models. 7, 50 AND 
60 kW capacities. Delivered assembled, inside the impulse 
plenum of the unit.
Power supply to the heater must be independent of the gen-
eral power supply, and be equipped with its own automatic 
switch (not supplied). See section No. 6.2.

13.11.- Hot water coil

Located within the impulse plenum of the unit. Heating capaci-
ties of from 115 to 140 kW (with water at 80/65° C). Includes 
all necessary hydraulic and control components: -way mixing 
valve, 0-10v proportional actuator and antifreeze probe. See 
details in Fig. 14.
Location of the impulse duct should be indicated when plac-
ing the order.

Hot water coil

Model 

360

Model 

480

Air flow

m

/h 19 000 21 000 2 000 22 000 25 000 28 000

Heating 
capacity

kW

115

121

126

124

11

140

Water flow

m

/h

7

7.5

7.5

7.6

7.9

8.6

Pressure 

drop, water 

circuit

kPa

26

0

0

0

8

- Fig. 14 -

- Data with water temperature at 80/65° C and air intake at 18° C.
- Total water volume: 10 l.

13.12.- Indoor air quality control probe

This  option  operates  necessarily  with  the  economiser. The 
probe determines the degree of air pollution due to different 
causes, such as occupation level of the room, cigarette smoke, 
kitchens, carbon monoxide, etc.
When the preset limits are exceeded, this control unit acts 
upon  the  economiser,  adjusting  the  outdoor  air  damper, 
without hindering the air conditioning function. Up to three air 
quality levels can be selected on the probe. The normal level 
is selected by default.

13.13.- Smoke detector

The smoke detector is installed in the return air section of 
the unit.
If smoke particles are detected, the unit is locked out (off) 
and must be reset manually to resume operation.
The  smoke  detector  is  a  protection  device  for  the  unit.  It 
should not be used as protection system for the building or 
other installations. Use is subject to compliance with local 
regulations  that  affect  the  unit  (with  regard  to  ventilation 
systems, fire prevention, etc.). Depending upon these regula-
tions, this option could require the use of an economiser or 
a motor-driven damper.

Содержание B4IH-360

Страница 1: ...Ref Y 70107 0907 ROOFTOP Air Conditioners D4IC 360 480 Cool only B4IH 360 480 Heat pump D4IG 360 480 Cool only gas heating Technical Information...

Страница 2: ......

Страница 3: ...emperature control 26 13 10 Electric heater 27 13 11 Hot water coil 27 13 12 Indoor air quality control probe IAQ 27 13 13 Smoke detector 27 1 Description 5 2 Product nomenclature 5 3 Characteristics...

Страница 4: ...ting lockout models D4IG 34 17 3 Low gas pressure models D4IG 35 17 4 Heating lockout electric heaters 35 17 5 Motor overload protection 35 18 Start up gas heating models D4IG 35 18 1 Check list prior...

Страница 5: ...7 kW 2 Product nomenclature 3 Characteristics 3 1 Structure Designed to evacuate rainwater and condensed water easily from the unit The roofing surface of the evaporating section is slightly tilted t...

Страница 6: ...isconnects the power supply to the main board of the unit 3 11 Control circuit 24 V control circuit that can operate with the optional DPC 1 communication thermostat or a 24V thermostat with control s...

Страница 7: ...m thick The length and width should be at least 150 mm more than the base beams of the units Do not fasten the bed frame to the foundation of the build ing 4 For rooftop installation the roof structur...

Страница 8: ...2 8 Stages N 4 4 Compressors Nominal start current A 21 x3 167 21 x2 38 167 272 Type SCROLL SCROLL No of circuits 3 3 Refrigerant R 407C Circuit No 1 2 3 kg 12 7 12 7 12 7 12 7 12 7 26 Power supply V...

Страница 9: ...ype SCROLL SCROLL No of circuits 3 3 Refrigerant R 407C Circuit No 1 2 3 kg 13 7 13 7 13 7 13 7 13 7 27 9 Power supply V ph Hz 400 3 N 50 Indoor fan 3 Nominal air flow m3 h 21 000 25 000 Maximum stati...

Страница 10: ...mper kg 64 64 Extraction fan axial kg 129 129 Mounting base Roof Curb fixed adjustable kg 117 220 117 220 Electric heater kg 34 34 Hot water coil kg 54 54 High pressure drive HPD kg 0 44 Cu Cu coils e...

Страница 11: ...195 94 BEAM A2 C2 A1 ACCESS ECONOMISER FILTERS RETURN A2 ACCESS INDOOR FAN AND COIL A3 ACCESS ELECTRICAL BOX A4 ACCESS COOLING CIRCUIT A5 ACCESS HEATING IMPULSE ACCESSORIES A6 ACCESS OUTDOOR COILS C1...

Страница 12: ...Model D4IG For further dimensions and details as per Fig 4A Fig 4 B A1 A6 A6 A2 230 1095 G3 G3 G2 G1 1 BSP FEMALE G1 GAS SUPPLY LINE CONNECTION G2 AIR INTAKE FOR COMBUSTION G3 COMBUSTION GAS DISCHARG...

Страница 13: ...its with optional hot water coil or D4IG units with gas heating The lower impulse section C2 cannot be accessed through access doors A5 The unit is delivered without cover C2 ready for connecting the...

Страница 14: ...the side of the unit 3 In both cases make sure of air tightness between the duct and the panel of the unit 4 Very important Cover C5 is related to the opening for the outdoor air intake when the unit...

Страница 15: ...th electrical regulations An automatic and differential switch should be installed on job site for the unit This switch should be independent of all other circuits Should any of the cables supplied wi...

Страница 16: ...ostat should be located on an inner wall at about 1 5 m above floor level where it will not be exposed to air flows direct sunlight or heat from other elec tric devices For general installation follow...

Страница 17: ...8 85 7 71 1 15 101 8 101 8 101 8 101 8 92 3 97 3 97 3 97 3 97 3 85 0 87 2 87 2 87 2 87 2 86 0 Data in compliance with EUROVENT conditions Return air Air temperature in outdoor coil DB 27 C 35 C 46 C...

Страница 18: ...100 5 100 5 85 8 71 2 89 5 89 5 89 5 84 4 69 7 15 98 3 98 3 98 3 98 3 90 8 93 9 93 9 93 9 93 9 83 5 84 1 84 1 84 1 84 1 84 1 Return air Air temperature in outdoor coil DB 27 C 35 C 46 C Total power kW...

Страница 19: ...99 8 20 48 4 61 4 77 3 96 1 118 2 127 6 139 7 165 7 193 9 23 46 7 58 6 73 8 92 2 113 4 122 9 135 1 159 7 186 5 25 44 3 55 1 71 8 89 6 110 5 119 9 131 8 155 3 182 1 m3 h Return air DB C Outdoor air tem...

Страница 20: ...nt and tensing procedure Attention When starting the installation up and once air distribution is balanced in the conditioned space impulse air flow should be checked 11 1 Models 360 applications with...

Страница 21: ...11 8 75 12 3 4 320 8 5 280 8 9 235 9 4 190 9 9 140 10 4 85 10 9 5 270 7 8 225 8 3 175 8 7 125 9 2 70 9 8 6 210 7 2 170 7 8 120 8 2 60 8 6 Opening adjustment of motor pulley No of turns Air flow m3 h 2...

Страница 22: ...n must be indicated upon placing the order see Fig 10 If necessary the economiser can include as options the enthalpy probe control see 13 2 as well as an excess air extraction system when required by...

Страница 23: ...air intake rain hood Location of economiser return air damper Fig 9 Fig 10 2040 910 OUTDOOR AIR RETURN AIR BOTTOM RETURN DUCT DAMPER OUTDOOR AIR RETURN AIR DAMPER SIDE RETURN DUCT ATTENTION INDICATE R...

Страница 24: ...ction against birds When it opens the entering outdoor air increases and the return air flow is decreased proportionally the pressure within the building rises When this pressure is greater that the a...

Страница 25: ...duct connection is on the side of the unit it must be installed at the job site directly on the front surface of the return duct as close as possible to the unit In this case a wiring hose is include...

Страница 26: ...ncy ASHRAE 52 76 90 Fire proof classification DIN5348 F1 13 7 Dirty filter pressure switch Allows establishing a dry contact when the filters are ob structed thus indicating filters need maintenance o...

Страница 27: ...e roof See mounting details in Fig 15a 13 18 Mounting base Roof Curb adjustable type For installation on rooftops with pitches of up to 4 7 or 6 5 11 depending upon the location of the unit With chara...

Страница 28: ...URB ROOF SUPPORTING STRUCTURE COMPONENTS NOT SUPPLIED WITH THE ACCESSORY 50 50 140 2955 COMPRESSOR SIDE RETURN SIDE RETURN DUCT IMPULSE DUCT ROOF CURB ROOFTOP UNIT SECTION A A 1160 77 RETURN AIR 1790...

Страница 29: ...SECTION A A 1130 77 OUTDOOR SUPPORT A 4 MAX 4 MAX 6 5 MAX 11 MAX B C 7 MAX 7 MAX 170 170 25 725 725 1790 77 200 52 1894 222 725 25 725 222 50 500 50 1685 GASKET 50 670 50 1790 50 50 1130 130 900 900 9...

Страница 30: ...ixed hub core of the pulley 2 Belt tensing Tense with tensing screw A If no belt strain gauge is available use the following practi cal method Apply a pressure of 5 kg on the midpoint of the belt and...

Страница 31: ...HEAT are displayed Fan Only The fan only mode is accessed in the OFF mode by pressing the key which selects the fan speed In this way the air conditioning system is off and only the fan is operative...

Страница 32: ...C between the cool and heat set points this value can be increased with the DPC 1 thermostat COOL HEAT If the thermostat is set to COOL the unit oper ates in the cooling mode when the thermostat requ...

Страница 33: ...rol board A6 generates a W3 output terminals 42 43 allowing the gas system to operate at 75 of its capacity The smoke discharge motor relay M8 is activated REQUEST FOR HEAT 4 If the thermostat generat...

Страница 34: ...one minute even if there is no call Simultaneous defrost of two stages is not allowed and one of these remains in standby until the operating procedure of the other is over 17 Safety features and con...

Страница 35: ...upply line is in compliance with safety regulations and is prepared to supply adequate gas flow and pressure See technical specifications in sections 4 1 and 18 8 Gas supply pipes to the unit must be...

Страница 36: ...FLYWHEEL 2ND STAGE V2 LOCK SCREW T ADJUSTING FLYWHEEL 1ST STAGE V1 PIN FOR READING OUTPUT PRESSURE TO THE MANIFOLD Pc PIN FOR READING MAIN REGULATOR PRESSURE Pa PIN FOR READING INPUT PRESSURE IGNITION...

Страница 37: ...lated in section 18 6 and in compliance with Fig 18 1 With the 4 heat stages in operation Adjust the main regulator pressure reading in Pa Adjust the 2nd stage regulator V2 pressure reading in Pc Pay...

Страница 38: ...out by qualified technical personnel only updating the maintenance log book of each unit regularly Attention Before opening any access to the interior of the unit all power supply should be turned of...

Страница 39: ...1 Air filters Indoor coil A visual inspection is recommended during the maintenance operation of the filters The entire surface of the fins must be kept clean If cleaning is needed use a soft brush or...

Страница 40: ...ctrical connections and operation of safety controls The bearings of the outdoor as well as indoor fan motors are of the permanent lubrication type and therefore do not require maintenance If the unit...

Страница 41: ...cations appearing in section 18 5 19 3 Burner and injector inspection instruc tions Burners Visually inspect the flame of the burners see Fig 19 If the flame is not correct the burners could require c...

Страница 42: ...amaging the air tightness gasket Fig 26 3 The smoke stack interior and the end of the exchanger pipes are now accessible 4 Using a metal brush with flexible rods brush and sweep each one of the pipes...

Страница 43: ...43 20 Wiring diagrams 20 1 Cool only models D4IC 360 D4IC 360G50 400 3 50 1 of 3...

Страница 44: ...44 D4IC 360G50 400 3 50 2 of 3...

Страница 45: ...45 D4IC 360G50 400 3 50 3 of 3...

Страница 46: ...46 20 2 Cool only models D4IC 480 D4IC 480G50 400 3 50 1 of 3...

Страница 47: ...47 D4IC 480G50 400 3 50 2 of 3...

Страница 48: ...48 D4IC 480G50 400 3 50 3 of 3...

Страница 49: ...49 20 3 Heat pump models B4IH 360 400 3 50 1 of 3...

Страница 50: ...50 B4IH 360 400 3 50 2 of 3...

Страница 51: ...51 B4IH 360 400 3 50 3 of 3...

Страница 52: ...52 20 4 Heat pump models B4IH 480 400 3 50 1 of 3...

Страница 53: ...53 B4IH 480 400 3 50 2 of 3...

Страница 54: ...54 B4IH 480 400 3 50 3 of 3...

Страница 55: ...55 20 5 Cool only gas heating models D4IG 360 400 3 50 1 of 4...

Страница 56: ...56 D4IG 360 400 3 50 2 of 4...

Страница 57: ...57 D4IG 360 400 3 50 3 of 4...

Страница 58: ...58 D4IG 360 400 3 50 4 of 4...

Страница 59: ...59 20 5 Cool only gas heating models D4IG 480 400 3 50 1 of 4...

Страница 60: ...60 D4IG 480 400 3 50 2 of 4...

Страница 61: ...61 D4IG 480 400 3 50 3 of 4...

Страница 62: ...62 D4IG 480 400 3 50 4 of 4...

Страница 63: ...63 Configuration of switches Data and dimensions are subject to change without prior notice...

Страница 64: ...www johnsoncontrols com...

Отзывы: