![York AFFINITY DNQ Series Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/york/affinity-dnq-series/affinity-dnq-series_technical-manual_912379027.webp)
333491-YTG-D-0409
54
Johnson Controls Unitary Products
Sound Performance
Indoor Blower Specifications
Size
(Tons)
Model
Motor
HP
RPM
Eff.
SF
Frame
024
(2.0)
DNZ
DNQ
DNX
1/2
Variable
0.8
1.0
48
030
(2.5)
DNZ
DNQ
1/2
Variable
0.8
1.0
48
036
(3.0)
DNZ
DNQ
3/4
Variable
0.8
1.0
48
DNX
1
Variable
0.8
1.0
48
042
(3.5)
DNZ
DNQ
1
Variable
0.8
1.0
48
048
(4.0)
DNZ
DNQ
DNX
1
Variable
0.8
1.0
48
060
(5.0)
DNZ
DNQ
1
Variable
0.8
1.0
48
Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Nominal
Applied
240
208
0.75
230
0.92
480
460
0.92
600
575
0.92
Outdoor Sound Power Levels
Size
(Tons)
Model
Sound Rating
1
dB (A)
1. Rated in accordance with ARI 270 standard.
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
024
(2.0)
DNZ
77
64
65.5
68
72.5
64.5
60.5
48.5
DNQ
80
66
70.5
74
74.5
72.5
67.5
64.5
DNX
80
66
70.5
74
74.5
72.5
67.5
64.5
030
(2.5)
DNZ
DNQ
74
63.5
64.5
66.5
67
63
57.5
51.5
036
(3.0)
DNZ
74
66.5
66.5
69.5
68
63
59
49.5
DNQ
79.5
69
71.5
74
74
70.5
67
61
DNX
80
70.5
71
74.5
74
71
67.5
64
042
(3.5)
DNZ
DNQ
79
70
70.5
73.5
73
69.5
67
66
048
(4.0)
DNZ
79
70.5
71
73.5
73
70
66
66
DNQ
80
71.5
71.5
73.5
74
69.5
65
63.5
DNX
81
72.5
73
76
75.5
71
67.5
65
060
(5.0)
DNZ
80
73
71.5
74.5
75
70.5
67
62.5
DNQ
81
73.5
73
76
75.5
71
66.5
61.5