718419-YTG-D-0613
18
Johnson Controls Unitary Products
115°F
125°F
1050
77
36.6
4.1
21.7
16.7
11.7
-
-
-
33.6
4.3
21.1
16.1
11.2
-
-
-
72
32.6
4.0
28.7
23.7
18.7
13.7
-
-
29.0
4.3
27.5
22.6
17.6
12.6
-
-
67
28.7
3.9
28.7
28.7
25.7
20.7
15.7
-
24.4
4.2
24.4
26.0
24.0
19.0
14.0
-
62
27.4
3.9
27.4
27.4
27.4
22.4
17.5
12.5
24.3
4.1
24.3
24.3
24.3
19.3
14.3
9.3
57
28.5
4.0
28.5
28.5
28.5
23.5
18.6
13.6
25.2
4.2
25.2
25.2
25.2
20.2
15.2
10.2
1225
77
37.9
4.3
29.2
19.9
12.2
-
-
-
34.7
4.6
30.0
20.1
11.5
-
-
-
72
33.8
4.2
31.2
25.3
19.4
13.5
-
-
29.9
4.5
30.0
24.1
18.2
12.3
-
-
67
29.7
4.1
29.7
29.7
26.6
20.7
14.8
-
25.1
4.4
25.1
26.5
24.8
18.9
13.0
-
62
28.4
4.1
28.4
28.4
29.3
23.4
17.5
11.6
25.0
4.4
25.0
25.0
25.8
19.9
14.0
8.1
57
29.6
4.1
29.6
29.6
29.9
24.0
18.1
12.2
26.0
4.5
26.0
26.0
26.5
20.6
14.7
8.8
1400
77
39.3
4.5
36.6
23.0
12.6
-
-
-
35.8
4.9
38.9
24.1
11.9
-
-
-
72
35.0
4.4
33.7
26.9
20.1
13.3
-
-
30.8
4.8
32.4
25.6
18.8
12.0
-
-
67
30.8
4.3
30.8
30.8
27.5
20.7
13.9
-
25.9
4.7
25.9
27.0
25.6
18.8
12.0
-
62
29.4
4.3
29.4
29.4
31.2
24.4
17.6
10.8
25.8
4.7
25.8
25.8
27.3
20.5
13.7
6.9
57
30.6
4.3
30.6
30.6
31.3
24.5
17.7
10.9
26.7
4.8
26.7
26.7
27.9
21.1
14.3
7.5
1575
72
36.2
4.4
35.5
28.5
20.7
13.0
-
-
31.7
4.8
33.8
27.1
19.4
11.6
-
-
67
31.8
4.3
31.8
31.8
28.5
20.7
13.0
-
26.6
4.7
26.6
27.5
26.4
18.7
10.9
-
62
30.4
4.3
30.4
30.4
31.3
23.5
15.8
8.0
26.5
4.6
26.5
26.5
27.3
19.6
11.8
4.1
57
31.6
4.3
31.6
31.6
32.0
24.2
16.5
8.7
27.5
4.7
27.5
27.5
28.2
20.5
12.7
5.0
1750
72
37.4
4.4
37.4
30.1
21.4
12.7
-
-
32.6
4.7
35.2
28.7
20.0
11.3
-
-
67
32.8
4.3
32.8
32.8
29.4
20.7
12.0
-
27.4
4.6
27.4
28.1
27.3
18.6
9.9
-
62
31.4
4.2
31.4
31.4
31.4
22.7
14.0
5.3
27.3
4.6
27.3
27.3
27.3
18.6
9.9
1.2
57
32.7
4.3
32.7
32.7
32.7
24.0
15.3
6.6
28.3
4.7
28.3
28.3
28.6
19.9
11.2
2.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
BHZ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65