background image

036-21528-007-A-1205                                                                                                                                                                                                                               

Unitary Products Group

9

TABLE 6: COOLING CAPACITIES - 3-1/2 TON (BHP042)

TEMPERATURE AIR ON

OUTDOOR COIL

TEMPERATURE OF AIR ON INDOOR COIL

1300 CFM

1400 CFM

WB °F

WB °F

72

67

62

57

72

67

62

57

85 °F

NET CAP. MBH

48.8

44.5

40.5

40.6

49.2

44.9

40.8

41.0

POWER INPUT kW

3.37

3.32

3.21

3.20

3.43

3.38

3.27

3.26

Sen

s

ib

le Cap

a

city

MBH

1

En

te

ri

n

g

  

Dr

y

Bu

lb °F

86

31.6

39.4

40.5

40.6

33.0

41.0

40.8

41.0

83

27.8

35.6

40.1

40.5

28.9

36.9

40.8

41.0

80

24.0

31.8

38.8

40.2

24.8

32.8

40.1

41.5

77

20.2

27.9

35.0

36.4

20.7

28.8

36.0

37.4

74

16.4

24.1

31.2

32.6

16.7

24.7

31.9

33.4

71

#N/A

20.3

27.4

28.7

#N/A

20.6

27.9

29.3

68

#N/A

16.5

23.5

24.9

#N/A

16.5

23.8

25.2

95 °F

NET CAP. MBH

45.4

41.5

38.3

38.5

45.7

41.9

38.6

38.8

POWER INPUT kW

3.67

3.66

3.54

3.54

3.72

3.71

3.60

3.60

Sen

s

ib

le Cap

a

city

MBH

1

En

te

ri

n

g

  

Dr

y

Bu

lb

 °

F

86

30.7

38.2

38.3

38.5

32.0

39.8

38.6

38.8

83

26.9

34.4

38.1

38.3

27.9

35.7

38.6

38.8

80

23.0

30.6

37.5

37.9

23.9

31.6

38.8

39.2

77

19.2

26.8

33.6

34.0

19.8

27.6

34.7

35.1

74

15.4

23.0

29.8

30.2

15.7

23.5

30.6

31.0

71

#N/A

19.1

26.0

26.4

#N/A

19.4

26.5

26.9

68

#N/A

15.3

22.2

22.6

#N/A

15.3

22.4

22.8

105 °F

NET CAP. MBH

41.9

37.7

35.2

35.6

42.1

37.9

35.4

35.7

POWER INPUT kW

4.01

3.98

3.89

3.88

4.06

4.03

3.94

3.93

Sen

s

ib

le Cap

a

city

MBH

1

En

te

ri

n

g

  

Dr

y

Bu

lb

 °

F

86

28.1

34.5

35.2

35.6

29.4

35.8

35.4

35.7

83

24.5

31.6

34.8

35.1

25.6

33.0

35.2

35.5

80

21.0

28.1

33.7

33.8

21.8

29.1

34.9

35.1

77

17.4

24.6

30.1

30.3

18.0

25.3

31.1

31.2

74

13.9

21.0

26.6

26.7

14.1

21.5

27.3

27.4

71

#N/A

17.5

23.0

23.2

#N/A

17.7

23.5

23.6

68

#N/A

13.9

19.5

19.6

#N/A

13.9

19.7

19.8

115 °F

NET CAP. MBH

38.7

34.2

32.4

32.9

38.8

34.3

32.5

33.0

POWER INPUT kW

4.41

4.35

4.28

4.28

4.46

4.40

4.33

4.32

Se

nsible Cap

a

city

MBH

1

E

n

te

ri

ng

  

Dr

y

Bu

lb

 °

F

86

26.8

32.5

32.4

32.9

28.1

33.4

32.5

33.0

83

23.3

30.2

32.1

32.3

24.3

31.5

32.3

32.7

80

19.7

26.7

31.2

31.0

20.5

27.7

32.4

32.2

77

16.2

23.1

27.6

27.5

16.7

23.9

28.6

28.4

74

12.6

19.6

24.1

24.0

12.9

20.1

24.8

24.6

71

#N/A

16.1

20.6

20.4

#N/A

16.3

20.9

20.8

68

#N/A

12.5

17.0

16.9

#N/A

12.5

17.1

17.0

125 °F

NET CAP. MBH

35.6

30.7

29.6

30.3

35.5

30.6

29.6

30.2

POWER INPUT kW

4.81

4.73

4.68

4.67

4.85

4.77

4.72

4.71

Se

nsible Cap

a

city

MBH

1

E

n

te

ri

ng

  

Dr

y

Bu

lb

 °

F

86

25.5

30.4

29.6

30.3

26.8

31.0

29.6

30.2

83

22.0

28.8

29.4

29.6

23.0

30.1

29.5

29.9

80

18.5

25.3

28.7

28.3

19.2

26.3

29.8

29.4

77

14.9

21.7

25.1

24.8

15.4

22.5

26.0

25.6

74

11.4

18.2

21.6

21.2

11.6

18.6

22.2

21.8

71

#N/A

14.6

18.1

17.7

#N/A

14.8

18.4

18.0

68

#N/A

11.1

14.5

14.1

#N/A

11.0

14.6

14.2

1.

These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Содержание AFFINITY BHP024

Страница 1: ...the installer can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique...

Страница 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Страница 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Страница 4: ...e designed for single point and dual con nection TABLE OF CONTENTS Description 1 Standard Features Benefits 1 Field installed Accessories 3 Unit Cut Away 5 Ratings 5 Physical Data 5 Cooling Capacities...

Страница 5: ...E PHASE THREE PHASE 024 24 4 13 0 11 3 7 7 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 7 77 28 2 3 40 16 5 2 20 5 0 7 5 10 0 15 0 10 0 15 0 036 35 0 13 0 11 3 7 7 77 32 0 3 30 18 9 2...

Страница 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Страница 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Страница 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Страница 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Страница 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Страница 11: ...WER INPUT kW 5 64 5 52 5 37 5 28 6 17 6 04 5 88 5 77 Sensible Capacity MBH 1 Entering Dry Bulb F 86 36 7 45 7 46 8 47 2 41 9 49 9 46 3 46 7 83 32 0 41 1 46 8 47 2 35 9 45 9 46 3 46 7 80 27 3 36 4 46 7...

Страница 12: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 10 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TE...

Страница 13: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 12 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Страница 14: ...66 3 793 4 020 4 247 4 474 80 MBH 13 394 16 579 20 504 25 342 31 304 38 653 47 709 58 871 KW 3 227 3 453 3 680 3 907 4 134 4 361 4 588 4 815 1 These capacities are net capacities the indoor motor heat...

Страница 15: ...1 412 494 577 B1HP042 Cooling TB2 A Heating TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B Heating TB2 B 1400 CFM 393 466 544 642 734 B1HP048 Heating TB2 A 1400 CFM 377 427 504 597 683 B1HP0...

Страница 16: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Страница 17: ...7 31 0 6 6 8 12 7 20 20 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 7 3 33 4 40 40 0 96 40 208 230 3 60 187 253 13 9 88 0 1 1 7 3 25 8 30 30 0 96 75 460 3 60 414 504 6 4 44 0 0 6 7 3 16 1 20 20 0...

Страница 18: ...48 7 45 50 45 50 2NH04501525 11 3 15 0 31 3 36 1 47 7 63 7 60 70 60 70 036 208 230 3 60 11 4 78 0 1 1 7 3 2NH04501025 7 5 10 0 20 8 24 1 48 7 52 7 60 60 60 60 2NH04501525 11 3 15 0 31 3 36 1 76 7 67 8...

Страница 19: ...T OF UNIT CENTER OF GRAVITY B1HP UNIT SIZE SHIPPING WEIGHT OPERATING WEIGHT CORNER WEIGHTS A B C D 024 356 351 97 93 81 84 030 353 348 96 93 81 84 036 388 383 106 102 89 92 042 440 435 120 115 101 104...

Страница 20: ...7 A 1205 20 Unitary Products Group FIGURE 5 UNIT DIMENSIONS 5217 5217 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 29 5 81 7 6...

Страница 21: ...036 21528 007 A 1205 Unitary Products Group 21 FIGURE 6 TYPICAL APPLICATIONS...

Страница 22: ...036 21528 007 A 1205 22 Unitary Products Group FIGURE 7 ROOF CURB DIMENSIONS...

Страница 23: ...036 21528 007 A 1205 Unitary Products Group 23 FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Страница 24: ...036 21528 007 A 1205 24 Unitary Products Group FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Страница 25: ...036 21528 007 A 1205 Unitary Products Group 25 FIGURE 10 TYPICAL WIRING DIAGRAM 460 575 3 60 POWER SUPPLY...

Страница 26: ...be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height 8...

Страница 27: ...ing the normal system operation pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for r...

Страница 28: ...Printed in U S A 036 21528 007 A 1205 Copyright by Unitary Products Group 2005 All rights reserved Supersedes 036 21528 006 A 1005 Unitary 5005 Norman Products York OK Group Drive 73069 ISO 9001 Cert...

Отзывы: