background image

291627-YTG-B-0807

Unitary Products Group

29

MECHANICAL SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility. YORK’s 
Affinity™ package units are designed to handle applications 
ranging from residential to light commercial and any in 
between. The Affinity™ is a unit that gives you the flexibility 
and choices you need in today’s market. These packaged 
cooling/heating air conditioners are designed for outdoor 
installation. Only utility and duct connections are required at 
the point of installation. The gas fired heaters have alumi-
nized steel tubular heat exchangers and spark to pilot igni-
tion. They are available in natural gas with field conversion to 
propane.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric 
Cooling/Gas Heating units, designed for outdoor mounted 
installation. For SEER ratings, refer to technical literature. 
They shall have built in, equal size, field convertible duct 
connections for down discharge supply/return or horizontal 
discharge supply/return. The units shall be factory wired, 
piped, charged with R-22 refrigerant and factory tested prior 
to shipment. All unit wiring shall be both numbered and 
color coded. All units shall be manufactured in a facility cer-
tified to ISO 9001 standards, and the cooling performance 
shall be rated in accordance with DOE and ARI test proce-
dures. The heating performance shall be rated to DOE and 
GAMA test procedures. Units shall be CSA listed and classi-
fied to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/
CAN/CSA No. 236-M90 conditions.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, 
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 1000 hours salt spray test per ASTM-
B117 standards. The unit top shall be a single piece “Water 

Shed” design, with drip edges and no-seam corners to pro-
vide optimum water integrity. Unit shall have a rigidly 
mounted condenser coil guard to provide protection from 
objects and personnel after installation. Indoor blower section 
shall be insulated with up to 3/4” thick, aluminum, foil faced 
insulation, fastened to prevent insulation from entering the air 
stream. Cabinet panels shall be “large” size, easily remov-
able for servicing and maintenance, with built-in lift handles. 
Unit shall be built on a formed, “Super-Structure” design base 
pan, with embossments at critical points to add strength, 
rigidity and aid in minimizing sound. Full perimeter base rails 
shall be provided to assure reliable transit of equipment, 
overhead rigging, for truck access and proper sealing on roof 
curb applications. Base rails shall be removable, when 
required, to lower unit height. Filters shall be furnished and 
be accessible through a removable access door, sealed air-
tight. Units vertical discharge and return duct configuration 
shall be designed to fit between standard 24” O.C. beams 
without modification to building structure, duct work and base 
unit. Condensate pan shall be internally sloped and conform 
to ASHRAE 62-89 self-draining standards, with 3/4” NPTI 
copper, ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be direct drive, multi-speed design. Job site 
selected (BHP) brake horsepower shall not exceed the 
motors nameplate horsepower rating. Fan wheel shall be 
double-inlet type with forward-curved blades, dynamically 
balanced to operate smoothly throughout the entire range of 
operation. Airflow design shall be constant air volume. Bear-
ings shall be sealed and permanently lubricated for longer life 
and no maintenance. Fan assembly shall be “Slip Track” 
(slide-out) design for easy removal and cleaning.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to cor-
rosion resistant steel spider bracket and shall be statically 
balanced for smooth operation. The outdoor fan motor shall 

FIGURE 19 -  WIRING DIAGRAM DETAIL A (460-3-60 POWER SUPPLY)

1

1. See Figure 15.

LOW SPEED

MED SPEED

HI SPEED

(BR-LI)

(BR-LI)

(BR-LI)

ID F

AN MOT

OR

ID F

AN MOT

OR

ID F

AN MOT

OR

BLK  (HI)

BLK / WHT

BLK / WHT

BLK / WHT

BLU  (MED)

BLU  (MED)

BLU  (MED)

BLU / WHT

BLU / WHT

BLU / WHT

RED  (LOW)

RED  (LOW)

RED  (LOW)

BLK  (HI)

BLK  (HI)

Содержание AFFINITY 030N03625

Страница 1: ...ng from residential to light commercial and any in between The Affinity is a unit that gives you the flexibility and choices you need in today s market FEATURING COOLING GAS HEATING UNITS NATURAL GAS OR PROPANE LOW PROFILE QUIET OPERATION COMMON FOOTPRINT OPTIONAL SLIDE IN MOTORIZED DAMPERS OPTIONAL SLIDE IN ECONOMIZERS OPTIONAL PROPANE CONVERSION KIT OPTIONAL HIGH ALTITUDE CONVERSION KIT NATURAL ...

Страница 2: ...ATA 7 2 RATINGS COOLING GAS HEATING 8 3 DNH030 COOLING CAPACITIES 2 1 2 TON 9 4 DNH036 COOLING CAPACITIES 3 TON 10 5 DNH042 COOLING CAPACITIES 3 1 2 TON 11 6 DNH048 COOLING CAPACITIES 4 TON 12 7 DNH060 COOLING CAPACITIES 5 TON 13 8 SIDE SUPPLY AIR BLOWER PERFORMANCE 208 VOLT 14 9 SIDE SUPPLY AIR BLOWER PERFORMANCE 230 460 VOLT 15 10 BOTTOM SUPPLY AIR BLOWER PERFORMANCE 208 VOLT 16 11 BOTTOM SUPPLY...

Страница 3: ...DENSATE PAN A non corrosive long lasting water tight pan is positioned below the evaporator coil to collect and drain all condensate Less collection of stagnate condensate will build up The condensate pan conforms to ASHRAE 62 89 standards Ventilation for Acceptable Indoor Air Quality CONDENSATE DRAIN The heavy duty 3 4 inch NPTI cop per connection is more tolerable during installation and is more...

Страница 4: ...ng the system No final field mounting required EASY SERVICE ACCESS A large single panel covers the electrical and gas controls makes servicing easy The blower compartment has an additional large panel with a built in handle tab Removing this panel will allow the blower assem bly to slide out for easy removal for maintenance and ease of trouble shooting REPLACEMENT PARTS The installer has no need t...

Страница 5: ...d screen assembly WALL THERMOSTAT The units are designed to operate with 24 volt electronic and electro mechanical thermostats All units can operate with single stage heat single stage cool thermostats with or without the economizer LOW AMBIENT KIT Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0 F Standard unit operation 45 F TRANSFORMER KIT Kit provides neces...

Страница 6: ... 1 4 1 4 1 4 1 3 1 3 NOM CFM TOTAL 2 400 2 400 2 400 3 000 3 000 CONDENSER COIL ROWS DEEP 1 2 1 2 2 FINS PER INCH 20 20 20 20 20 FACE AREA Sq Ft 11 7 11 7 14 7 14 7 14 7 CHARGE REFRIGERANT 22 lbs oz 4 9 6 12 5 14 8 0 8 12 FILTER FACE AREA Sq Ft Size Nominal 2 6 20x20 2 6 20x20 3 3 20x12 2 Reqd 3 3 20x12 2 Reqd 3 3 20x12 2 Reqd FURNACE SECTION NATURAL GAS BURNER ORIFICE NO Drill Size 43 43 40 40 40...

Страница 7: ...80 6 3 25 55 042N09025 42 0 12 0 80 108 87 80 8 4 45 75 042N09046 42 0 12 0 80 108 87 80 8 4 45 75 048N06525 48 0 12 0 84 80 64 80 8 3 25 55 048N06546 48 0 12 0 84 80 64 80 8 3 25 55 048N09025 48 0 12 0 84 108 86 80 6 4 35 65 048N09046 48 0 12 0 84 108 86 80 6 4 35 65 048N11025 48 0 12 0 84 135 107 80 5 5 45 75 048N11046 48 0 12 0 84 135 107 80 5 5 45 75 060N06525 59 0 12 0 84 80 64 80 7 3 25 55 0...

Страница 8: ...y MBH 1 Entering Dry Bulb F 86 16 0 19 6 19 4 19 0 18 4 22 3 21 4 20 9 20 8 24 9 23 3 22 8 22 3 25 0 23 4 22 9 23 7 25 2 23 5 23 0 83 13 9 18 0 19 4 19 0 15 9 20 6 21 4 20 9 17 9 23 2 23 3 22 8 18 9 23 8 23 4 22 9 20 0 24 5 23 5 23 0 80 11 8 15 8 18 2 17 5 13 4 18 0 20 8 20 0 15 0 20 2 23 3 22 4 15 6 21 0 23 4 22 7 16 2 21 8 23 5 23 0 77 9 6 13 7 16 1 15 4 10 9 15 5 18 2 17 4 12 1 17 3 20 4 19 5 1...

Страница 9: ... 20 6 25 9 28 3 28 3 23 0 28 9 30 5 30 6 25 3 31 8 32 6 32 9 25 2 32 0 33 2 33 4 25 1 32 2 33 7 33 9 83 18 9 24 2 27 9 27 8 21 0 26 9 30 3 30 4 23 2 29 7 32 6 32 9 23 6 30 4 33 2 33 4 24 0 31 1 33 7 33 9 80 17 1 22 4 26 3 26 0 19 1 25 0 29 4 29 1 21 1 27 6 32 4 32 1 22 0 28 8 33 1 33 0 23 0 30 1 33 7 33 9 77 15 4 20 7 24 6 24 3 17 2 23 1 27 5 27 1 19 0 25 5 30 4 30 0 20 5 27 3 31 5 31 4 21 9 29 0 ...

Страница 10: ... F 86 24 8 31 0 29 9 29 5 28 2 34 9 32 7 32 2 31 6 38 7 35 5 35 0 34 0 39 1 36 2 34 8 36 3 39 4 35 0 34 5 83 21 8 28 0 29 9 29 5 24 7 31 6 32 7 32 2 27 5 35 3 35 5 35 0 29 3 36 8 35 2 34 8 31 1 38 4 35 0 34 5 80 18 8 25 0 28 4 28 1 21 1 28 1 31 9 31 6 23 5 31 2 35 4 35 0 24 7 32 8 35 2 34 8 25 9 34 4 35 0 34 5 77 15 8 22 0 25 4 25 1 17 6 24 6 28 3 28 0 19 4 27 1 31 3 30 9 20 0 28 2 30 5 30 1 20 7 ...

Страница 11: ...86 31 8 39 0 39 9 39 9 34 3 41 4 40 8 40 7 36 9 43 8 41 6 41 5 40 3 45 7 42 8 42 8 43 8 47 6 44 1 44 0 83 28 4 35 7 38 9 39 0 30 3 38 0 40 2 40 3 32 2 40 3 41 6 41 5 35 0 43 3 42 8 42 8 37 9 46 2 44 1 44 0 80 24 9 32 3 37 2 37 3 26 2 34 0 39 2 39 4 27 5 35 7 41 2 41 5 29 7 38 5 42 6 42 7 31 9 41 4 44 1 44 0 77 21 5 28 9 33 8 33 9 22 2 29 9 35 1 35 3 22 9 31 0 36 5 36 8 24 4 33 2 37 3 37 4 26 0 35 ...

Страница 12: ...86 41 8 51 8 53 0 51 7 43 6 54 0 53 8 52 6 45 5 56 2 54 6 53 4 47 1 56 7 54 3 56 1 48 7 57 3 54 0 52 8 83 36 9 47 0 52 2 51 7 38 4 48 9 53 4 52 6 39 9 50 7 54 6 53 4 41 2 52 3 54 3 53 1 42 5 53 8 54 0 52 8 80 32 1 42 2 48 5 48 2 33 2 43 7 50 2 49 9 34 4 45 2 52 0 51 6 35 3 46 4 52 4 52 2 36 2 47 6 52 8 52 8 77 27 3 37 3 43 6 43 3 28 1 38 5 45 0 44 7 28 9 39 6 46 4 46 1 29 4 40 5 46 5 46 3 29 9 41 ...

Страница 13: ... 1315 657 1204 623 1093 588 MED 1432 650 1381 628 1330 605 1279 583 1210 556 1140 529 LOW 1191 527 1149 510 1107 494 1065 477 048 HI 1742 898 1695 869 1648 841 1601 811 1555 781 1501 747 1446 714 1317 667 MED 1523 750 1498 730 1473 710 1447 692 1421 673 1371 647 1320 620 1211 580 LOW 1343 620 1327 606 1310 593 1280 573 1250 553 060 3 tube HEAT 1500 245 1500 297 1500 348 1500 400 1500 470 1500 540 ...

Страница 14: ... 913 1706 888 1648 861 1590 834 1445 783 1301 731 MED 1734 848 1693 821 1651 794 1595 764 1539 734 1461 693 1382 653 1266 613 LOW 1532 700 1508 683 1458 667 1444 643 1404 620 1348 593 1291 566 060 only 575 volts HI 2444 1433 2380 1400 2313 1363 2245 1325 2169 1285 2092 1245 1902 1168 1711 1092 1521 1015 MED 2281 1265 2227 1225 2172 1185 2099 1140 2025 1095 1922 1035 1819 975 1665 915 1512 855 LOW ...

Страница 15: ... 1295 639 1147 600 MED 1482 628 1428 613 1374 599 1320 584 1242 556 1163 528 1085 500 LOW 1239 510 1184 496 1130 481 1075 467 048 HI 1655 771 1609 749 1563 727 1504 698 1444 670 1381 648 1319 626 MED 1499 687 1474 670 1449 653 1400 630 1351 606 1297 583 1242 559 LOW 1418 610 1388 593 1357 576 1327 561 1298 546 1241 523 060 3 tube HEAT 1500 245 1500 297 1500 348 1500 400 1500 470 1500 540 1500 610 ...

Страница 16: ...1814 945 1731 905 1578 582 LOW 1937 990 1892 983 1846 935 1785 908 1723 880 1655 843 1587 805 060 3 tube only 230 460 volts HEAT 1500 245 1500 297 1500 348 1500 400 1500 470 1500 540 1500 610 1500 680 1500 750 1500 820 1500 890 060 4 5 tube only 230 460 volts HEAT 1700 390 1700 443 1700 497 1700 550 1700 620 1700 690 1700 760 1700 830 1700 900 1700 970 060 factory setting only 230 460 volts COOL 1...

Страница 17: ...om the available external static pressure shown in Table 8 9 10 and 11 2 The pressure through the economizer is greater for 100 outdoor air then for 100 return air If the resistance of the return air duct system is less then 0 25 IWG the unit will deliver less CFM during full economizer operation R G W R G C Y Y W C PROGRAMMABLE THERMOSTAT ONLY Minimum wire size of 18 AWG wire should be used for a...

Страница 18: ... 504 4 3 27 0 6 1 4 7 4 15 15 96 75 036 208 230 3 60 187 253 11 4 77 1 1 3 5 18 9 25 25 96 75 036 460 3 60 414 504 5 7 39 0 6 1 8 9 5 15 15 96 75 042 208 230 3 60 187 253 13 9 88 1 3 3 5 22 2 30 30 96 75 042 460 3 60 414 504 6 4 44 0 7 1 8 10 5 15 15 96 75 048 208 230 3 60 187 253 13 0 93 1 9 4 2 22 4 30 30 96 75 048 460 3 60 414 504 6 4 46 5 1 0 2 1 11 1 15 15 96 75 060 208 230 3 60 187 253 19 3 ...

Страница 19: ...A I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They are subject to change with out notice Certified dimensions will be provided upon request TABLE 15 UNIT DIMENSIONS FRONT UNIT SIZE DIMENSION A B 030 036 33 1 2 18 1 4 042 060 41 1 2 23 1 8 TABLE 16 UNIT MI...

Страница 20: ... D R A I N 3 4 N P T I G A S S U P P L Y 1 5 8 D I A K N O C K O U T 1 2 N P T I C O N N E C T I O N L O W V O L T A G E C O N N 1 8 D I A K N O C K O U T 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2 C O N D E N S E R C O I L B O T T O M S U P P L Y A I R O P E N I N G B O T T O M R E T U R N A I R O P E N I N G S I D E R E T U R N A I R O P E N I N G...

Страница 21: ... L G A S S H U T O F F V A L V E R E T U R N A I R D U C T S U P P L Y A I R D U C T C O N T R O L W I R I N G T O I N D O O R T H E R M O S T A T T O P O W E R S U P P Y M A N U A L G A S S H U T O F F V A L V E F I E L D S U P P L I E D D I S C O N N E C T S W I T C H M O U N T E D O N U N I T T O P O W E R S U P P L Y T O G A S S U P P L Y L I N E C O N T R O L W I R I N G T O I N D O O R T H E...

Страница 22: ...D U C T S L A B O N G R O U N D I N S T A L L A T I O N TABLE 17 UNIT WEIGHTS AND CENTER OF GRAVITY UNIT SIZE SHIPPING WEIGHT lbs OPERATING WEIGHT lbs CORNER WEIGHTS location lbs ECONOMIZER lbs ROOF CURB lbs A B C D 030 395 390 98 95 96 99 40 8 70 14 75 036 400 395 100 96 98 101 042 470 465 131 129 101 103 048 475 470 133 130 102 104 060 485 480 136 133 105 107 A B C D 49 1 8 25 25 47 1 4 FRONT OF...

Страница 23: ... 1 8 X 2 1 1 2 R E C O M M E N D E D D U C T S I Z E 1 7 1 2 X 1 6 3 4 1 8 Roof curb also available 3 4 X 1 W I D E G A S K E T I N G F O R C U R B F R A M E A N D A L L D U C T S U P P O R T S U R F A C E S U N I T B A S E W O O D N A I L E R 8 M I N A B O V E F I N I S H E D R O O F C U R B F R A M E I N S U L A T I O N U N I T B A S E R A I L C O U N T E R F L A S H I N G C A N T S T R I P I N ...

Страница 24: ...291627 YTG B 0807 24 Unitary Products Group FIGURE 14 TYPICAL WIRING DIAGRAM DNH 030 036 042 048 208 230 3 60 POWER SUPPLY ...

Страница 25: ...291627 YTG B 0807 Unitary Products Group 25 FIGURE 15 TYPICAL WIRING DIAGRAM DNH 030 036 042 048 460 3 60 POWER SUPPLY ...

Страница 26: ...291627 YTG B 0807 26 Unitary Products Group FIGURE 16 TYPICAL WIRING DIAGRAM DNH 060 208 230 3 60 POWER SUPPLY ...

Страница 27: ...291627 YTG B 0807 Unitary Products Group 27 FIGURE 17 TYPICAL WIRING DIAGRAM DNH 060 460 3 60 POWER SUPPLY ...

Страница 28: ... If neither LR or ASCT are present wire 202 Y is connected to M1 coil as shown 7 Shunt contact also used with crankcase heater optional 8 Unit factory wired for low or medium speed indoor blower operation To change motor speed connect speed tap wires from indoor blower motor per Detail A Figure 19 Tape unused speed tap wires to prevent shorting and secure 9 Select indoor blower speed to remain wit...

Страница 29: ...rotection from objects and personnel after installation Indoor blower section shall be insulated with up to 3 4 thick aluminum foil faced insulation fastened to prevent insulation from entering the air stream Cabinet panels shall be large size easily remov able for servicing and maintenance with built in lift handles Unit shall be built on a formed Super Structure design base pan with embossments ...

Страница 30: ...nts brazed b Evaporator coil shall be of the direct expansion blow through design while condenser coil shall be draw through design Refrigerant Circuit and Refrigerant Safety Components a Shall include independent fixed orifice expansion devices b Shall include filter strainer to eliminate any foreign matter UNIT OPERATING CHARACTERISTICS Unit shall be capable of starting and running at 125º F out...

Страница 31: ...291627 YTG B 0807 Unitary Products Group 31 ...

Страница 32: ...ct to change without notice Printed in U S A 291627 YTG B 0807 Copyright 2007 by Unitary Products Group All rights reserved Supersedes 291627 YTG A 0207 Unitary 5005 Norman Products York OK Group Drive 73069 ...

Отзывы: