1.4.3 Unit sound pressure data
Octave band sound spectrum dB(A), outdoor
Models
100
125
150
175
125 Hz
87,3
90,1
250 Hz
85,4
86,6
500 Hz
84,5
84,2
1000 Hz
84,9
84
2000 Hz
79,7
79
4000 Hz
73,4
75,5
8000 Hz
68,4
73,2
Sound power level dB (A)
88,4
88,5
Sound pressure level at 5 m dB (A)
63,7
63,8
Sound pressure level at 10 m dB (A)
57,6
57,7
Octave band sound spectrum dB(A), indoor
Models
100
125
150
175
125 Hz
89,8
94,4
250 Hz
77,5
83,2
500 Hz
75,7
76,9
1000 Hz
75,6
76,4
2000 Hz
75
75,7
4000 Hz
73,8
76,4
8000 Hz
70,3
74,5
Sound power level dB (A)
83,3
84,2
1.4.4 Weight options and accessories
Models
100
125
150
175
Economiser
kg
88
88
100
100
Exhaust fan (axial)
kg
75
75
106
106
Roofcurb mounting base (fixed/adjustable)
kg
152 / 248
186 / 302
Heating element
kg
Hot water coil
kg
Fixed outdoor air intake
kg
39
39
43
43
Barometric damper
kg
28
28
36
36
Copper fin coil
indoor
105
160
outdoor
144
204
Side air supply
11
13
1
Installation manual
1.4
Technical data
8
Содержание ACTIVA 100
Страница 1: ...ACTIVA SERIES ROOF TOP Air Conditioners 100 175 Installation manual Ref N 40428_EN 0413...
Страница 4: ...1 Installation manual...
Страница 40: ...2 Options and accessories...
Страница 53: ...3 Unit installation data...
Страница 57: ...4 Wiring diagrams...