York 92% GF9 Скачать руководство пользователя страница 7

035-17737-003 Rev. A (0504)

Unitary Products Group

7

4 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition may be
caused by: dirty filter, improperly sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.

5 RED FLASHES:

 This fault is indicated if the normally closed contacts

in the rollout switch opens. The rollout control is manually reset. If it has
opened, check for proper combustion air, proper inducer operation, and
primary heat exchanger failure or burner problem. Be sure to reset the
switch after correcting the failure condition.

6 RED FLASHES:

 This indicates that after the unit was operating, the

pressure switch opened 4 times during the call for heat. If the main
blower is in a “Delay on” mode it will complete it, and any subsequent
delay off period. The furnace will lock out for one hour and then restart.

7 RED FLASHES:

 This fault code indicates that the flame could not be

established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
faulty hot surface ignitor or burner problem may cause this. The furnace
will lock out for one hour and then restart.

8 RED FLASHES:

 This fault is indicated if the flame is lost 5 times (4

recycles) during the heating cycle. This could be caused by low gas
pressure or faulty gas valve. The furnace will lock out for one hour and
then restart.

9 RED FLASHES:

 Indicates reversed line voltage polarity or grounding

problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding. Check that
flame probe is not shorted to chassis.

10 RED FLASHES:

 Gas flow with no call for heat. Check gas valve and

gas valve wiring.

11 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally-closed contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel.

STEADY ON RED: 

Control failure. Replace control board.

60-MINUTE AUTOMATIC RESET FROM LOCKOUT:

 This control

includes a “watchdog” type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists

causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the “watchdog” would restart the unit and pro-
vide heat for the house.

NOTE: 

If a flame is detected the control flashes the LED for 1/8 of a

second and then enters a flame stabilization period.

DIAGNOSTIC FAULT CODE STORAGE AND 

RETRIEVAL

The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even is power to the furnace
is lost. 

This feature should only be used by a qualified service tech-

nician. 

The control stores up to five separate error codes. If more than five
error codes have occurred since the last reset, only the five most recent
will be retained. The furnace control board has a button, labeled "LAST
ERROR" that is used to retrieve error codes. This function will only work
if there are no active thermostat signals. So any call for heating, cooling
or continuous fan must be terminated before attempting to retrieve error
codes. 

To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED will
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.

If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.

IGNITION CONTROL (P/N 031-01972-000)

Normal flame sense current is approximately

3.7 microamps DC (µa)

Low flame signal warning starts at 1.5 microamps.

Low flame signal control lockout point is

0.9 microamps DC (µa)

 FIGURE 7: 

Furnace Control Event Schedule

Thermostat Calling for Heat

Thermostat Satisfied

(Seconds)

THERMOSTAT

INDUCER

IGNITOR

MAIN VALVE

HUMIDIFIER

ELECTRONIC
AIR CLEANER

CIRCULATING
BLOWER

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

OFF

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

15 Sec.
Post
Purge

Fan on Delay
30 Seconds

0 2

17

22

52

0

60, 90, 120, 180 SEC.
Selectable Fan Off Delay

Содержание 92% GF9

Страница 1: ...wet or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other...

Страница 2: ...nace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Ex...

Страница 3: ...es to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to next step 7 Move gas control switch to the ON position Do not force See Figure...

Страница 4: ...e cabinet Some installations may have the air filter in a rack attached to the cas ing of the furnace or placed in the return air duct If the filter location or replacement process is not obvious cont...

Страница 5: ...nue until the thermostat circuit between R and W is opened which causes the ignition system and gas valve to de energize and the burner flames to be extinguished The vent motor will operate for an add...

Страница 6: ...em by setting the thermostat above the room temperature Observe the system s response Then use the troubleshooting section in this manual to check the system s operation FURNACE CONTROL DIAGNOSTICS Th...

Страница 7: ...s 6 7 8 will be reset This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction An example would be a low incoming gas supply pressure preventin...

Страница 8: ...ry Products Group SECTION III REPLACEMENT PARTS LIST 11 5 1 15 16 3 14 4 2 6 10 9 12 13 7 32 27 54 40 25 52 21 26 29 38 34 35 30 46 22 20 62 17 57 51 59 64 61 55 41 65 48 45 24 63 23 14 58 19 9 37 28...

Страница 9: ...ay 188 ID 2 ft req d 41 TUBING SILICONE Clear with insert 1 3 ft req d 42 GASKET AIR INTAKE 43 GASKET COMBUSTION BLOWER 44 GASKET CONDENSATE PAN 45 GASKET UPPER CONDENSATE PAN 46 GASKET GAS CONTROLS 4...

Страница 10: ...R0324 1NK0301 CONDENSATE NEUTRALIZER KIT 1SF0101 EXTERNAL SIDE RETURN FILTER RACK GF9 ONLY REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To request a complete parts list refer to t...

Страница 11: ...035 17737 003 Rev A 0504 Unitary Products Group 11 SECTION IV WIRING DIAGRAM FIGURE 8 Wiring Diagram...

Страница 12: ...s only to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or se...

Отзывы: