background image

035-15806-004 Rev. A (1000)

6

Unitary Products Group

REFRIGERANT VALVE OPERATION

All models in this series have brass service valves. These
valves are not back seating. Opening or closing valve does
not close service port. Service ports have Schrader valves for
gauge connections. Use back-up wrench on valve body when
removing cap to open or close the valve. To open, insert hex
wrench into stem and back out counter clockwise until stem
just touches retaining ring.  

All caps must be replaced to prevent leaks.

OIL TRAPPING

When the outdoor unit is above the indoor coil oil trapping is
necessary. Please refer to APPLICATION DATA, 690.01-
AD1V (1296) and worksheet 690.01-AD1.1V (791) “General
Piping Recommendations and Refrigerant Line length".

Check the system for correct charge after all components of
the system have been installed, connected and wired cor-
rectly.

Connect service gauges to low pressure port and discharge
service ports.

Allow unit to operate until system pressures and tempera-
tures have stabilized, making sure that the pressure and tem-
perature align with unit service data. If not, check system
charge and adjust if necessary.

ELECTRICAL WIRING

POWER SUPPLY

All wiring must comply with N.E.C. and local codes. See rat-
ing plate and product data sheet for volts, frequency, phase,
maximum fuse size and minimum branch circuit ampacity. 

Refer to the wiring diagram inside the unit control box cover
before connecting to power supply.

1.

The line voltage service wiring for the outdoor unit must 
include a disconnect switch located within sight of the 
outdoor unit.

2.

Use the correct size fuse or circuit breaker as listed on 
the unit rating plate and data sheet. See Tabular Data 
Sheet for minimum recommended wire size. If using 
nonmetallic-sheathed cable (NM or NM-B) ampacities 
shall be that of 60º C conductors per N.E.C. 336-26.

3.

Wiring connections. - Two are provided in the control 
box:

a.

One for low voltage wiring.

b.

One entrance for high voltage.

The reversible High Voltage Conduit Plate is factory installed
for 1/2" conduit connections. For 3/4" conduit, remove the
screw holding the plate in place and reverse the location of
the holes. For 1" conduit, remove the conduit plate and dis-
card. Re-install screw to maintain the integrity of the unit
structure, regardless of the conduit being used. See Figure 3.

4.

Power connection to the unit is facilitated by screw termi-
nals on the outdoor unit contactor. See Figure 3.

5.

Ground the outdoor unit using the ground lug provided. 
Unless the outdoor unit is grounded through proper wir-
ing to the service entrance ground, a suitable separate 
ground should be provided at the outdoor unit.

6.

Use copper conductors only. 

If the valve stem is backed out beyond the retaining
ring, system pressure could force the stem out of the
valve body and possibly cause personal injury. In
the event that the retaining ring is missing do not
attempt to open the valve. 

To prevent electrical shock, open remote disconnect
so electrical supply to outdoor unit is shut off. Con-
tactor does not open both sides of the line volt elec-
trical circuit.

Casing or cabinet must be permanently grounded in
accordance with National Electric Code or other
applicable local codes.

Содержание 3 PH

Страница 1: ...NIT 4 INDOOR UNITS 4 REFRIGERANT LINE 4 INSULATION OF VAPOR LINE 4 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LINE LENGTH 5...

Страница 2: ...any additional external static pressure The maximum and minimum conditions for operation must be observed to assure a system that will give maximum perfor mance with minimum service Check Electrical...

Страница 3: ...ences standing off from the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches...

Страница 4: ...istance and fewest number of bends Determine the path that the refrigerant lines will follow Starting at either the indoor coil or the outdoor unit refrigerant line connections carefully measure cut d...

Страница 5: ...tamination Contaminated refrigerant must be recovered and returned to the local refrigeration supply house for proper disposition TOTAL LINE LENGTH Units should be installed only with approved system...

Страница 6: ...t include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet See Tabular Data Sheet for minim...

Страница 7: ...3 or 4 2 Using wire nuts connect the low voltage wiring as shown in Figure 5 6 or 7 3 A minimum of 18 AWG wire gauge for total lengths not exceeding 130 feet must be used in connecting the low voltage...

Страница 8: ...TACTOR 1 TERMINALS GND LUG R B Y O W R Y G AIR HANDLER TERMINAL BLOCK 4TB TYPICAL THERMOSTAT ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY X 53 G 60 66 JUNCTION BOX RED BRN YEL OR...

Страница 9: ...see that nothing was over looked Have all braze joints on refrigerant lines been leaked checked Have base valves been opened Have all refrigerant lines been secured and iso lated properly Is the indo...

Страница 10: ...035 15806 004 Rev A 1000 10 Unitary Products Group NOTES...

Страница 11: ...035 15806 004 Rev A 1000 Unitary Products Group 11...

Страница 12: ...without notice Printed in U S A 035 15806 004 Rev A 1000 Copyright by York International Corp 2000 All rights reserved Supersedes 035 15806 403 REV A 550 46 N2Y 499 Unitary 5005 Norman Product York OK...

Отзывы: