036-21137-004 Rev. C (0505)
20
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H2RC048S06
INDOOR COIL MODEL NO.
G1FA048S21
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1375
1575
1775
ID DB (°F)
85
80
75
85
80
75
85
80
75
ID WB (°F)
72
67
63
72
67
63
72
67
63
75
T.C.
52.8
49.9
45.4
53.5
50.6
46.8
54.2
51.3
48.2
S.C.
33.3
32.7
31.5
34.9
34.5
33.6
36.5
36.2
35.7
KW
3.14
3.09
3.03
3.15
3.10
3.04
3.17
3.12
3.06
85
T.C.
50.9
47.1
42.4
51.6
48.1
43.5
52.3
49.1
44.7
S.C.
33.3
32.0
30.4
35.3
34.2
32.6
37.4
36.3
34.7
KW
3.44
3.35
3.30
3.46
3.38
3.31
3.47
3.40
3.32
95
T.C.
49.0
44.3
39.4
49.7
45.5
40.3
50.3
46.8
41.2
S.C.
33.2
31.2
29.3
35.8
34.1
31.5
38.4
36.5
33.7
KW
3.74
3.62
3.57
3.76
3.56
3.57
3.78
3.69
3.58
105
T.C.
44.7
40.0
35.8
45.4
41.0
36.5
46.1
42.0
37.1
S.C.
31.9
29.8
27.8
34.5
32.2
29.9
37.0
34.7
32.1
KW
4.01
3.89
3.80
4.04
3.91
3.81
4.07
3.94
3.83
115
T.C.
40.5
35.7
32.1
41.2
36.5
32.6
41.9
37.2
33.1
S.C.
30.5
28.3
26.3
33.1
30.5
28.4
35.7
32.8
30.5
KW
4.28
4.15
4.02
4.32
4.17
4.05
4.35
4.19
4.08
125
T.C.
36.3
31.3
28.5
36.9
31.9
28.8
37.6
32.5
29.1
S.C.
29.2
26.8
24.8
31.8
28.9
26.8
34.4
31.0
28.8
KW
4.55
4.42
4.25
4.60
4.43
4.29
4.64
4.44
4.33
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
F2FP048
1.00
1.00
1.02
F2FP060
1.03
1.03
1.06
F2FV060
1.06
1.10
0.95
N1AHC1606
G2FD048(S,H)21,24
1.00
1.00
1.01
N1AHD2006
G2FD060(S,H)24
1.03
1.03
1.02
N1AHD2006
G2FD061H24
1.04
1.04
1.02
N1VSC16
G2FD048(S,H)21
1.01
1.02
0.97
N1VSD20
G2FD060(S,H)24
1.04
1.06
0.99
N1VSD20
G2FD061H24
1.05
1.07
0.99
G1FA048S17
0.98
0.98
0.98
G1FA060S21,24
1.03
1.03
1.02
G1HD048
0.99
0.99
1.01
G1HD060
1.02
1.02
1.02
G1NA048S21D
0.99
0.99
1.02
G1UA048S17
0.98
0.98
0.98
G1UA048S21
1.00
1.00
1.00
G1UA060S21,24
1.03
1.03
1.02
G2FD046(S,H)17
0.98
0.98
1.00
G2FD048(S,H)21,24
1.00
1.00
1.01
G2FD060(S,H)24
1.03
1.03
1.02
G2FD061H24
1.04
1.04
1.02
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P1DUC20V
G1FA048S21
1.00
1.00
0.99
P1DUC20V
G2FD048(S,H)21
1.00
1.00
1.00
P1XDD20V
G2FD048(S,H)24
1.01
1.01
1.01
P1XUC16V
G1FA048S21
0.99
0.99
1.00
P1XUC16V
G2FD048(S,H)21
0.99
0.98
1.01
P1XUC20V
G1FA048S21
1.00
1.00
0.99
P1XUC20V
G2FD048(S,H)21
1.00
1.00
1.00
P1XUD20V
G1FA060S24
1.04
1.05
1.00
P1XUD20V
G2FD048(S,H)24
1.01
1.01
0.99
P1XUD20V
G2FD060(S,H)24
1.04
1.05
1.00