036-21103-003 Rev. A (0403)
Unitary Products Group
3
1.
TXV = Thermal Expansion Valve kit required. Use 1TV700 series kit.
2.
Single phase units require single phase 2HK heaters — Three phase units require three phase 2HK heaters. (29) indicates 460 volt use only.
3.
G2FD coils available with a factory installed horizontal drain pan. Replace “S” with “H” in the model number.
— = Not Applicable.
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 & 3 Phase
Additional R-22 Charge / Orifice Size for Various Matched Systems
Outdoor Unit (H1RA)
018S78
024S78
030S78
036S78
036S50
048S50
060S50
Unit Orifice(s)
1
51
57
69
71
71
84
Factory R-22 Charge, lbs-oz
3 - 13
3 - 14
3 - 14
4 - 11
4 - 11
7 - 10
9 - 12
Indoor Coil
Coil Orifice
2
System O Additional Charge, Oz
G2FD024S14,17
61
51
+
0
G2FD030S17
65
57
+
0
69
+
0
G2FD036S17
75
69 + 3
71 + 0
71 + 0
G2FD036S21
75
71
+
2
71
+
2
G2FD042S21
78
71
+
4
G2FD048S21,24
78
84
+
0
G2FD060S24
90
90
+
0
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
AIR HANDLER
COIL
3
MODEL
COOLING
MODEL
ELECTRIC
2
HEAT KW
W
RATED
CFM
NET MBH
KW
SEER SEER/TXV
1
EER
TOTAL SENS.
1 PHASE HRA / NAH
H1RA018S78
N1AHB1293
5,8,10,15,18
17
G2FD024S17
650
18.1
12.9
1.86
--
--
--
H1RA024S78
N1AHB1293
5,8,10,15,18
17
G2FD030S17
850
23.4
16.8
2.87
--
--
--
H1RA030S78
N1AHB1293
5,8,10,15,18
17
G2FD030S17
1000
28.9
20.0
3.45
--
--
--
N1AHB1293
5,8,10,15,18
17
G2FD036S17
1000
29.6
20.6
3.57
--
--
--
H1RA036S78
N1AHB1293
5,8,10,15,18
17
G2FD036S17
1250
33.5
25.2
3.83
--
--
--
3 PHASE HRA / NAH
H1RA036S50
N1AHB1293
5,8,10,15,18
17
G2FD036S17
1200
33.6
24.9
3.81
--
--
--
N1AHB1293
5,8,10,15,18
17
G2FD036S21
1200
34.4
25.5
3.87
N1AHC1693
5,8,10,15,20
21
G2FD042S21
1250
35.1
25.9
3.93
H1RA048S50
N1AHC1693
5,8,10,15,18
21
G2FD048S21
1600
48.8
35.9
4.82
--
--
--
H1RA060S50
N1AHD2093
5,8,10,15,18
24
G2FD060S24
1900
60.5
43.0
6.29
--
--
--
1 PHASE HRA / FRP (SINGLE PHASE)
H1RA018S78
F2RP024N93
5,7.5,10
18
--
650
18.1
12.9
1.86
--
--
--
H1RA024S78
F2RP024N93
5,7.5,10
18
--
850
23.4
16.8
2.87
--
--
--
H1RA030S78
F2RP036N93
5,7.5,10,15
21
--
1000
29.6
20.6
3.57
--
--
--
H1RA036S78
F2RP036N93
5,7.5,10,15
21
--
1250
34.3
25.6
3.86
--
--
--
3 PHASE HRA / FRP (SINGLE PHASE)
H1RA036S50
F2RP036N93
10,15
21
--
1200
34.4
25.5
3.87
--
--
--
H1RA048S50
F2RP048N93
10,15
24
--
1600
48.8
35.9
4.82
--
--
--
H1RA060S50
F2RP060N93
10,15
24
--
1900
60.5
43.0
6.29
--
--
--
Cooling MBH based on 8
0
°F entering air temperature, 50% RH, and rated air flow.
KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at
those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the
total electric power
input in watt-hours during the same period.