CAUTION
Avoid damage to internal components if drilling holes
for disconnect mounting.
Note:
Since not all local codes allow the
mounting of a disconnect on the unit, please
confirm compliance with local code before
mounting a disconnect on the unit.
Electrical line must be sized properly to carry the
load. USE COPPER CONDUCTORS ONLY. Each unit
must be wired with a separate branch circuit fed
directly from the meter panel and properly fused.
CAUTION
When connecting electrical power and control wiring
to the unit, water-proof connectors must be used so
that water or moisture cannot be drawn into the unit
during normal operation. The above water-proofing
conditions will also apply when installing a field
supplied disconnect switch.
CAUTION
When installing equipment in a facility with a 3 phase
high-leg delta power supply, care must be taken to
ensure that the high-leg conductor is not attached to
either of the two legs of the (single phase, direct drive)
X13 or ECM motors. Failure to do so can result in the
motor acting erratically or not running at all.
Check for the high leg conductor by checking voltage
of each phase to ground.
Example: A or L1 phase to ground, voltage reading is
120V. B or L2 phase to ground, voltage reading is 195
to 208V. C or L3 phase to ground, voltage reading is
120V. Therefore B or L2 phase is the high Leg. The
high should always be wired to the center or B or L2
tap.
Note:
Check all three phase motors and compressors
for proper rotation after making a change. If it is
necessary to change 3 phase motor rotation, swap A
or L1 and C or L3 only.
Thermostat Wiring
A two stage thermostat must be used and should
be located on an inside wall approximately 56 inch
above the floor where it will not be subject to drafts,
sun exposure or heat from electrical fixtures or
appliances. Follow the manufacturer's instructions
enclosed with thermostat for general installation
procedure. Seven (7) color-coded, insulated wires
should be used to connect the thermostat to the
unit. Refer to Table 5 for control wire sizing and
maximum length.
Table 5: Control Wire Sizes
Wire size
Maximum length (ft)
1
20 AWG
< 150
18 AWG
150 to 250
16 AWG
250 to 500
Note:
1. From the unit to the thermostat and back
to the unit.
INSTALLATION MANUAL ZX SERIES 6 - 12.5 Ton 60 Hertz R-410A
23
Johnson Controls Ducted Systems
Содержание ZX Series
Страница 2: ...2 INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 104: ...Start Up Sheet INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 104 Johnson Controls Ducted Systems ...
Страница 105: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 105 Johnson Controls Ducted Systems ...
Страница 106: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 106 Johnson Controls Ducted Systems ...
Страница 107: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 107 Johnson Controls Ducted Systems ...
Страница 108: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 108 Johnson Controls Ducted Systems ...
Страница 109: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 109 Johnson Controls Ducted Systems ...