5121817-TIM-A-0515
Johnson Controls Unitary Products
19
T05
(5.0)
208-3-60
16
110
24.9
2.3
6.8
0
NONE
-
-
-
29.1
35
E05
4
1
11.1
29.1
35
E07
5.6
1
15.5
29.1
35
E10
8
1
22.2
36.3
45
E15
11.9
2
33
49.8
50
E20
15.9
2
44.1
63.7
70
E30
22.2
2
61.6
85.5
90
230-3-60
16
110
24.9
2.3
6.8
0
NONE
-
-
-
29.1
35
E05
5.3
1
12.7
29.1
35
E07
7.5
1
18
31.1
40
E10
10.6
1
25.5
40.4
45
E15
15.9
2
38.2
56.3
60
E20
21.2
2
51
72.2
80
E30
29.6
2
71.2
97.5
100
460-3-60 7.8
52
12.1
1.3
3.4
0
NONE
-
-
-
14.5
20
E07
6.8
1
8.2
14.5
20
E10
10.1
1
12.1
19.4
20
E15
13.6
2
16.4
24.7
25
E20
19.5
2
23.5
33.6
35
E30
28.8
2
34.6
47.6
50
575-3-60 5.7
38.9
8.9
1.3
2.4
0
NONE
-
-
-
10.6
15
E10
10.6
1
10.2
15.7
20
E15
15.9
2
15.3
22.1
25
E20
21.2
2
20.4
28.5
30
E30
30.4
2
29.3
39.6
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZKT03 Thru T05 Without Powered Convenience Outlet (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps