9.7
Unit Electrical Data
(09/03)
035B09012-100 Rev. 4
9
-
11
60
75
L90
L105
120
150
170
190
210
Current
Nominal
(1)
28
33
46
50
57
67
88
100
107
Input (A)
Maximum
(2)
35
45
73
73
76
91
127
147
147
Power
Nominal
(1)
19.6
22.9
25.4
30
37.7
46.3
49
56.5
59
Input (KW)
Maximum
(2)
23
29
27.5
33.5
49
59
58
62
68
Max. instantaneous current (A)
(3)
98
149
213
213
229
262
267
285
287
(1) Nominal conditions taken at 7°C leaving chilled water temperature and 35°C ambient temperature
(2) Maximum conditions for the compressor are taken at 14°C leaving chilled water temperature and 45°C ambient temperature
(3) Maximimum instantaneous current is the largest compressor LRA starting current, plus the nominal current of the other compressor and fan
Unit power input includes: the power input of the compressors, fans, control circuit and the power input of the pump against the unit pressure drops
YCAA-B
YCAA-B Models
Operating Condition
LRA
Power
Power
Current
Current
DOL
YCAA-B System
Input at
Input at
per Comp.
per Comp.
Starting
Nominal
(1)
Maximum
(2)
Nominal
(1)
Maximum
(2)
Current (A)
per Comp. (kW)
per Comp. (kW)
(A)
(A)
per Comp. LRA
60
Sys. 1+2
9.3
11
13.0
16.5
80
75
Sys. 1+2
11.0
14
15.7
21.6
126
L90
Sys. 1+2
12.0
13
21.7
35.0
175
L105
Sys. 1+2
14.0
16
24.0
35.0
175
120
Sys. 1+2
18.1
24
27.3
36.5
190
150
Sys. 1+2
22.4
29
32.0
44.0
215
170
Sys. 1+2
9.6/13.4
11.3/15.7
16.6/23.2
25/35
120/175
190
Sys. 1+2
13.0/13.0
14.5/14.5
22.8/22.8
35/35
175/175
210
Sys. 1+2
14.0/14.0
16.0/16.0
24.0/24.0
35/35
175/175
(1) Nominal conditions taken at 7°C leaving chilled water temperature and 35°C ambient temperature
(2) Maximum conditions for the compressor are taken at 14°C leaving chilled water temperature and 45°C ambient temperature
(2)
Models 170, 190 and 210 have two compressors per system
Fan Data
60
75
L90
L105
120
150
170
190
210
2
2
2
2
3
3
3
3
3
0.48
0.48
0.48
0.48
0.48
0.48
0.98
0.98
0.98
0.93
0.93
0.93
0.93
0.93
0.93
1.75
1.75
1.75
3.2
3.2
3.2
3.2
3.2
3.2
5.9
5.9
5.9
60
75
L90
L105
120
150
170
190
210
2
2
2
2
3
3
3
3
3
0.7
0.7
0.7
0.7
0.7
0.7
0.81
0.81
0.81
1.15
1.15
1.15
1.15
1.15
1.15
1.7
1.7
1.7
6
6
6
6
6
6
2.9
2.9
2.9
60
75
L90
L105
120
150
170
190
210
2
2
2
2
3
3
3
3
3
0.48
0.48
0.98
0.98
0.98
0.98
1.4
1.4
1.4
0.93
0.93
1.75
1.75
1.75
1.75
2.9
2.9
2.9
3.2
3.2
5.9
5.9
5.9
5.9
8.8
8.8
8.8
Full load Amps per fan (A)
Locked Rotor Amps per fan (A)
YCAA-B
Number of fan
Power input per fan (kW)
YCAA-B LN
Number of fan
Power input per fan (kW)
Full load Amps per fan (A)
Locked Rotor Amps per fan (A)
YCAA-B HT
Number of fan
Power input per fan (kW)
Full load Amps per fan (A)
Locked Rotor Amps per fan (A)
Содержание YCAA-B
Страница 2: ......
Страница 16: ...This Page Left Intentionally Blank 09 03 2 6 035B09012 100 Rev 4...
Страница 28: ...This Page Left Intentionally Blank 09 03 4 10 035B09012 100 Rev 4...
Страница 36: ...Page Left Intentionally Blank 09 03 6 6 035B09012 100 Rev 4...
Страница 40: ...Page Left Intentionally Blank 09 03 7 4 035B09012 100 Rev 4...
Страница 68: ...Notes 09 03 11 2 035B09012 100 Rev 4...
Страница 69: ...Notes 09 03 035B09012 100 Rev 4 11 3...
Страница 70: ...Notes 09 03 11 4 035B09012 100 Rev 4...