York International TCHDSERIES Скачать руководство пользователя страница 6

5320779-UIM-A-0417

6

Johnson Controls Unitary Products

SECTION VI: SYSTEM CHARGE

To ensure that your unit performs at the published levels, it is important
that the indoor airflow is determined and refrigerant charge added
accordingly.

MEASURE INDOOR AIR FLOW

To determine rated air flow for a specific match, consult the technical lit-
erature at www.upgnet.com. When attempting to match this air flow,
select the lowest possible speed tap, measure the actual flow, and
adjust as necessary. 

To measure actual air flow, it is not an acceptable method to just
check the jumper pin setting tables and is to assume 0.5” water
column total external static pressure.

To determine indoor air flow, first measure the static pressure with a
manometer between the filter and blower. On a single-piece air handler,
take a second reading after the coil. On a furnace or modular air han-
dler, take the second reading after the heat exchanger but before the
indoor coil. Add the negative return static to the positive supply static to
determine the system total static pressure. Treat the negative return
static as a positive pressure (even though it is a negative reading). If
there is static pressure on the blower (i.e. -.10) return, add it to a supply
static (.40) which equals a (.50) total system static pressure. Compare
this value to the table for the indoor unit's static pressure vs. CFM or to
a curve chart.

SYSTEM CHARGING

The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. line set, and the smallest indoor coil match-up. Some
indoor coil matches may require additional charge. See tabular data
sheet provided in unit literature packet for charge requirements.

The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.

Total system charge is determined as follows:

1.

Determine outdoor unit charge from tabular data sheet.

2.

Determine indoor coil adjustment from tabular data sheet.

3.

Calculate the line charge using the tabular data sheet if line length
is greater than 15 feet.

4.

Total system charge = item 1 + item 2 + item 3.

5.

Permanently stamp the unit data plate with the total amount of
refrigerant in the system.

Use the following charging method whenever additional refrigerant is
required for the system charge.

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly. Otherwise, model-specific charging
charts are provided on the access panel of the unit.

SUBCOOLING CHARGING METHOD - TXV INDOOR

For cooling operation, the subcooling values are shown in parentheses
on the charging charts provided with the unit.

1.

Set the system running in cooling mode by setting the thermostat
at least 6°

F below the room temperature and operate system for at

least 10 – 15 minutes.

2.

Refer to the technical guide for the recommended indoor airflow
and verify it is correct (it should be about 400 SCFM per ton).

3.

Measure and record the indoor wet bulb (WB) and the outdoor
ambient dry bulb (DB) temperature.

4.

Using the charging chart located on the unit, find the intersection
of the indoor wet bulb and the outdoor dry bulb. This is the recom-
mended liquid pressure (and subcooling value).

5.

Measure and record the pressure at the liquid valve pressure port
and compare to the value obtained in step 4.

6.

Add charge if the measured liquid pressure is lower than the rec-
ommended value. Remove / recover charge if the measured liquid
pressure is above the recommended value.

Condenser subcooling is obtained by calculating the difference of the
saturated refrigerant temperature of the pressure measured at the liquid
base valve and the liquid tube temperature as measured at the liquid
base valve.

Subcooling Temp. (TC) = Saturated Temp. (TS) – Liquid Temp. (T)

 CAUTION

R-410A refrigerant cylinders are rose colored. Always charge the 
system slowly with liquid R-410A refrigerant.

 CAUTION

Do not leave the system open to the atmosphere.

 WARNING

DO NOT attempt to pump “Total System Charge” into outdoor unit for
maintenance or service. This may cause damage to the compressor
and/or other components. Recover and weigh “System Charge” into
an appropriate recovery cylinder for any instances requiring evacua-
tion.

!

!

!

 CAUTION

Refrigerant charging should only be carried out by a qualified 
air conditioning contractor.

 CAUTION

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The liquid pressure listed at the intersection of the indoor 
WB and the outdoor DB 320 psig. Pressure at the liquid valve is 305 
psig. It would be necessary to add refrigerant to increase the liquid 
pressure to 320 psig.

 CAUTION

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR,
SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS
UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE
OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE
OWNER’S APPROVAL.

!

!

!

Содержание TCHDSERIES

Страница 1: ...it combinations elevation differences or total line lengths Refer to Appli cation Data covering General Piping Recommendations and Refriger ant Line Length Part Number 247077 SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Understand and pay particular attention to the signal words DANGER WARNING or CAUT...

Страница 2: ...d area that is seasonally hot the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is required that the outdoor unit indoor coil and metering device all be replaced The following steps sho...

Страница 3: ...utdoor unit In these applications care must be taken to address unit base pan support structural integ rity safe access and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution LIQUID LINE FILTER DRIER The air conditioning unit s filter dryer is located on the liquid line PIPING CONNECTIONS T...

Страница 4: ...allation The reusable service valves are pro vided to evacuate and charge per this instruction Serious service problems can be avoided by taking adequate precau tions to assure an internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also protect all painted s...

Страница 5: ...th fitting supplied with the liquid line Hand modify the liquid line to align with casing opening Hand tighten the liquid line and an addi tional 1 4 turn to seal 6 Install the TXV equalizer line into the vapor line as follows a Hand tighten the 1 4 SAE nut to the schrader fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb cla...

Страница 6: ...arging charts are provided on the access panel of the unit SUBCOOLING CHARGING METHOD TXV INDOOR For cooling operation the subcooling values are shown in parentheses on the charging charts provided with the unit 1 Set the system running in cooling mode by setting the thermostat at least 6 F below the room temperature and operate system for at least 10 15 minutes 2 Refer to the technical guide for ...

Страница 7: ...NEC and or local city codes 5 Mount the thermostat about 5 ft above the floor where it will be exposed to normal room air circulation Do not place it on an out side wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat T...

Страница 8: ... 48 5 21 6 67 06 7 7 287 225 5 1 0867 7 53522 86 233 5 21 8 7256 21 32 5 5 1 21752 5 1 725 5 1 5 1 72 1 25 1 7 75 2 1 1 25 2 2 6 FIGURE 7 Typical Field Wiring Air Handler Electrical Heat Three Phase 5 1 72 1 25 1 7 75 2 1 1 25 2 2 6 32 5 5 1 217 725 7 50 1 6 2 1 8 5 5 92 7 21752 5 1 0 1 080 5 1 66 851 25 5 1 5 7 50 1 2 5220 7 50267 7 21 16 1 81 7 287 225 5 1 0867 7 53522 86 233 5 21 8 7256 21 7 50...

Страница 9: ...l XFMR W Full Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary AHR ID MODELS COM 24 Volt Common R 24 Volt Hot W2 Second Stage Heat O Reversing Valve Energized in Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise PSC AIR HANDLER CONTROL G Fan PSC AIR HANDLER EAC 24 VAC out Electronic Air Cleaner HUM OUT 24 VAC out Humidifier Y1 Single Stage Compres...

Страница 10: ...r Full Stage Compressor W1 First Stage Heat Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Selection of GAS ELEC switch on thermostat is not necessary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Thermo...

Страница 11: ...Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE STAGE AIR CONDITIONER SINGLE STAGE AIR CONDITIONER ID MODELS TG 8 9 S C 24 Volt Common R 24 Volt Hot W Full Stage Heat SINGLE STAGE PSC FURNACE G Fan SINGLE STAGE PSC FURNACE Y Y2 Full Sta...

Страница 12: ...t Cool XFMR W Full Stage Heat Selection of GAS ELEC switch on thermostat is not necessary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Thermostat Installer Setup 1 System Type must be set to 0 C 24 Volt Common Thermostat Installer Setup 15 Compressor Protection must be set to 5 External Humidistat Optional ...

Страница 13: ...AINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to keep the unit clean Use a brush vacuum cleaner attachment or other suitable means 2 The outdoor fan motor is permanently lubricated and does not require periodic oiling 3 If the coil needs to be cleaned use clean water to wash dust dirt and debris from outdoor...

Страница 14: ...CTRICAL SUPPLY TO AIR CONDITIONER IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUT...

Страница 15: ... L ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE S WITH THIS UNIT MUST BE REPLA MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVA WHERE POWER SUPPLY HAS ON VOLT CONDUCTOR AND ONE 1 CONDUCTOR CONNECT L2 OF C TO NEUTRAL 1 2 3 4 LEGE CAP C COMP CC CO CCH C HPS H LPS LO OFM O HS HE WIRING DIAGRAM C Y L2 T2 VAC 60 Hz 3 PHASE SUPPLY C 60 Hz 3 PHASE SUPPLY...

Страница 16: ...5320779 UIM A 0417 16 Johnson Controls Unitary Products NOTES ...

Страница 17: ...Data Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plenum and return ducts are connected and sealed Filter Size Vent system is connected if applicable Thermostat wiring complete Heat anticipator is set to the r...

Страница 18: ...ual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting any problems Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through a cooling cycles noting and correcting any problems COOL ADJUST ECM X 13 PSC A ...

Отзывы: