Power Supply T
erminal Connections (Options /TB, /A2TB, and /REK)
8.2 Power Supply And Ground Wiring
(1) All cable ends must be furnished with crimp-on type solderless lugs (for 4 mm screw).
(2) Examples of applicable cables:
Cross-sectional area of the cable conductor:
2.0 mm
2
. *
Applicable cable:
600 V vinyle insulated cable (IV) stranded wires, conforming to JIS
C3307.
Vinyle sheathed cables for electric appliances (KIV) stranded
wires, conforming to JIS C3316.
Note *: Power supply cables should be determined from the instrument power
consumption-they must have conductors with cross-sectional area of at least
1.25 mm
2
.
(3) Wirings to power supply and ground terminals should be made after completion of signal
terminal wirings. (To facilitate connecting input signal, pull the internal unit approximately
half way out of the housing. Do not remove the power terminal block.)
(4) After completing the power supply and ground wiring, mount the power terminal cover.