YPP6830 Pulse Input Rate/Totalizer
Instruction Manual
92
Resetting the Total (
RESET
TOTAL?
)
If manual
Total Reset
is enabled in the
Program
menu, the total may be reset by
pressing the
Reset
button and using the
Enter
button to confirm the reset.
Additionally if programmed for manual reset, the total may be reset using a normally
open pushbutton connected across the terminals RST and COM.
Note:
The total is cleared immediately when Enter button is pressed. Totalization will
then continue, even if the Enter button or external reset button continues to be held
down/triggered.
Resetting the Grand Total (
RESET
GrTOT?
)
If manual
Grand Total Reset
is enabled in the
Program
menu, the grand total may be
reset using the
Reset
button.
To reset the grand total, display the grand total by pressing the
Up/Display
button.
While grand total is being displayed, press the
Reset
button. Confirm the reset with
the
Enter
button.
Resetting Max/Min Readings (
RESET
MAXIMUM
,
MINIMUM
)
The maximum and minimum readings may be reset by pressing the Reset button
while displaying either the maximum or minimum. The display will show
RESET
to
verify the reset of maximum or minimum value.
The maximum and minimum must be reset individually.
Reset Meter to Factory Defaults
Reset to factory defaults will restore most meter parameters to their factory default
setting.
When the parameters have been changed in a way that is difficult to determine
what’s happening, it might be better to start the setup process from the factory
defaults.
Factory default reset does not change the saved backup restore settings, override
passwords, or edit parameters locked by a permanent non-resettable grand total.
See Non-Resettable Grand Total, as described on page 75.
Instructions to load factory defaults can be found in the Backup & Restore (
BACKUP
)