<B4. Power, ground, and signal cable connection>
B4-3
IM 01W02D02-01EN
To disconnect the power supply cable from the spring terminal, push down the orange areas
around the cable inlet and pull out the power supply cable from the socket.
FB0403
Figure B4-3 Disconnecting the power supply cable
l
Applicable cables
Insulated cables for industrial equipment such as;
• 600 V polyvinyl chloride insulated wires (IV); JIS C3307
• Polyvinyl chloride insulated wires for electrical apparatus (KIV); JIS C3316
• 600 V grade heat-resistant polyvinyl chloride insulated wires (HIV); JIS C3317
• Heatproof vinyl insulated wires VW-1 (UL1015/UL1007)
• Control cables (vinyl insulated vinyl sheath cable) (CVV); JIS C3401
l
Wire Size
• Without sleeve: 0.2 mm
2
to 2.5 mm
2
(AWG24 to 14)
• With sleeve: 0.2 mm
2
to 2.5 mm
2
(AWG24 to 14)