55
IM 04P02B01-02E
Setup Item
Pen/Dot
Selectable Range or Selections
Default Value
*Batch > Detail > End > Action > POC output
Pen Model On/Off
Off
*Batch > Detail > End > Action > POC speed
Pen Model C.Speed/450 mm h
C.Speed
*Batch > Detail > Start2 ... Same as Start
*Batch > Detail > End2 ... Same as End
*Batch > MSG format > Message No.
-
1/2/3/4/5
1
*Batch > MSG format > Message No. > (MSG format) -
69 characters or less
H:M L16
Setup Items in Basic Setting Mode and Their Default Values
(Firmware version: 1.31)
Setup Item
Pen/Dot
Selectable Range or Selections
Default Value
Alarm > Diagnosis
-
On/Off
Off
Alarm > Reflash
-
On/Off
Off
Alarm > AND
-
None/I01/I01-I02/I01-I03/I01-I04/I01-I05/
None
I01-I06/I01-I11/I01-I12/I01-I13/I01-I14/
I01-I15/I01-I16/I01-I21/I01-I22/I01-I23/
I01-I24/I01-I25/I01-I26/I01-I31/I01-I32/
I01-I33/I01-I34/I01-I35/I01-I36
Alarm > Act
-
Energize/De_energize
Energize
Alarm > Behavior
-
Nonhold/Hold
Nonhold
Alarm > Indicator
-
Nonhold/Hold
Nonhold
Alarm > Increase
-
01 to 15
01
Alarm > Decrease
-
01 to 15
01
Alarm > Hysteresis
-
Off/0.1% to 1.0%
0.5%
Alarm > Math hysteresis
-
Off/0.1% to 1.0%
Off
A/D > Integrate
Dot Model
Auto/50Hz/60Hz/100ms
Auto
Pen Model Auto/50Hz/60Hz
Auto
Burnout > CH
-
01 to 24
01
Burnout > Burnout
-
Off/Up/Down
Off
RJC > CH
-
01 to 24
01
RJC > RJC
-
Internal/External
Internal
RJC > RJC > Volt
-
–20000 to 20000
µ
V
0
µ
V
Color > Channel
Dot Model
01 to 24
01, 07, 13, 19: Purple
Color > Color
Dot Model
Purple/Red/Green/Blue/Brown/Black
02, 08, 14, 20: Red
03, 09, 15, 21: Green
04, 10, 16, 22: Blue
05, 11, 17, 23: Brown
06, 12, 18, 24: Black
POC > POC
Pen Model On/Off
Off
Print > CH/Tag
-
CH/Tag
CH
Print > Channel
Dot Model
On/Off
On
Print > Alarm
-
On1/On2/Off
On1
Print > Record On
-
On/Off
Off
Print > Chart speed
-
On/Off
On
Print > Scale
-
On/Off
On
Print > Pen color
Pen Model On/Off
On
Print1 > Periodic
-
Auto/Manual
Auto
Print1 > Ref. Time
-
Hour 0 to 23 (1 hour steps)
00:00
Print1 > Interval
-
10min/15min/20min/30min/1h/2h/3h/4h
1h
/6h/8h/12h/24h
Print1 > Mode
-
Inst/Report/Off
Inst
Print2 > CH
-
01 to 24
01
Print2 > Mode
-
AVE/MIX/SUM/MIN/MAX/INST
AVE
Print2 > SUM scale
-
Off, /s, /min, /h, /day
Off
Bar graph > CH
-
01 to 24
01
Bar graph > Graph
-
Normal/Center
Normal
Keylock > Keylock
-
Not/Use
Not
Keylock > Password
-
Numbers and spaces within 4 digits
Blank
Keylock > RCD
-
Free/Lock
Free
Keylock > Feed
-
Free/Lock
Free
Keylock > Menu
-
Free/Lock
Free
Keylock > Disp Menu
-
Free/Lock
Free
Keylock > Alarm ACK
-
Free/Lock
Free
Keylock > Math
-
Free/Lock
Free
Keylock > Print out
-
Free/Lock
Free
Keylock > Message
-
Free/Lock
Free
Keylock > Buffer clear
-
Free/Lock
Free
Setup Items and Default Values