IM 01C25H01-01E
7-2
7. MAINTENANCE
Table 7.1
Instruments Required for Calibration
Name
Remarks
Yokogawa-recommended Instrument
Power
supply
Model SDBT or SDBS distributor
Load
resistor
Model 2792 standard resistor [250
Ω
±
0.005%, 3 W]
Load adjustment resistor [100
Ω
±
1%, 1 W]
Voltmeter
Model 2501 A digital multimeter
Accuracy (10V DC range):
±
(0.002% of rdg + 1 dgt)
Digital
manometer
Model MT220 precision digital manometer
1) For 10 kPa class
Accuracy:
±
(0.015% of rdg + 0.015% of F.S.)
±
(0.2% of rdg + 0.1% of F.S.)
2) For 130 kPa class
Accuracy:
±
0.02% of rdg
±
5digits
±
(0.2% of rdg + 0.1% of F.S.)
3) For 700 kPa class
Accuracy:
±
(0.02% of rdg + 3digits)
±
5 digits
±
(0.2% of rdg + 0.1% of F.S.)
4) For 3000 kPa class
Accuracy:
±
(0.02% of rdg + 10 digits)
±
(0.2% of rdg + 0.1% of F.S.)
5) For 130 kPa abs class
Accuracy:
±
(0.03% of rdg + 6 digits)
4 to 20 mA DC signal
Select a manometer having
a pressure range close to
that of the transmitter.
Pressure
generator
Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm
2
}, 25 kPa {2500 mmH
2
O}
Accuracy:
±
0.05% of F.S.
Requires air pressure
supply.
Pressure
source
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Prepare the vacuum pump
for negative pressure
ranges.
Dead weight gauge tester 25 kPa {2500mmH
2
O}
Accuracy:
±
0.03% of setting
Select the one having a
pressure range close to
that of the transmitter.
T0701.EPS
for 0 to 10 kPa
for -10 to 0 kPa
for 25 to 130 kPa
for 0 to 25 kPa
for -80 to 0 kPa
for 100 to 700 kPa
for 0 to 100 kPa
for -80 to 0 kPa
for 0 to 3000 kPa
for -80 to 0 kPa
for 0 to 130 kPa abs
. . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . .
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management
procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% or higher level, there
may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa representatives from which the
instrument was purchased or the nearest Yokogawa office.
Содержание vigilantplant DPharp EJX Series
Страница 2: ......
Страница 5: ......
Страница 16: ......
Страница 21: ...IM 01C25H01 01E 4 2 4 INSTALLATION...
Страница 34: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 44: ...IM 01C25H01 01E 8 6 8 GENERAL SPECIFICATIONS EJX438A I Transmitter body section F0806 EPS EJX438A...
Страница 51: ......
Страница 52: ...IM 01C25H01 01E 8 14 8 GENERAL SPECIFICATIONS 8 4 DIMENSIONS Transmitter body section EJX118A F0811 EPS...