YOKOGAWA UT130 Скачать руководство пользователя страница 4

IM 05C01E02-01E 4th Edition  Mar. 14, 2016-00

4

 Alarm Function List

Alarm type

Action

“Opn” and “Cls” indicate that the relay 

contact is opened and closed; “(on)” and 

“(off)” indicate that the lamp is on and off; 

and white triangles indicate temperature 

control setpoints.

Alarm 

type code

Alarm type

Action

“Opn” and “Cls” indicate that the relay 

contact is opened and closed; “(on)” and 

“(off)” indicate that the lamp is on and off; 

and white triangles indicate temperature 

control setpoints.

Alarm 

type code

Closed 

contact

during 

alarm

Open 

contact

during 

alarm

Closed 

contact

during 

alarm

Open 

contact

during 

alarm

No alarm

OFF

De-

energized 

on deviation 

low limit

Hysteresis

Temperature setpoint

Deviation setting

Measured value

Opn (on)

Cls (off)

6

16

(See 

note.)

PV

high limit

Hysteresis

Alarm setting

Measured value

Opn (off)

Cls (on)

1

11

(See 

note.)

PV

low limit

Hysteresis

Alarm setting

Measured value

Opn (off)

Cls (on)

2

12

(See 

note.)

Deviation 

high and 

low limit

Hysteresis

Hysteresis

Temperature setpoint

Deviation setting

Measured value

Cls 

(on)

Opn

(off)

Cls

(on)

7

17

(See 

note.)

Deviation 

high limit

Opn (off)

Hysteresis

Cls (on)

Measured value

Temperature setpoint

Deviation setting

3

13

(See 

note.)

Deviation 

within 

high- and 

-low-limit

Hysteresis

Hysteresis

Temperature setpoint

Measured value

Opn (off)

Opn (off)

Cls (on)

Deviation setting

8

18

(See 

note.)

Deviation 

low limit

Cls (on)

Hysteresis

Opn (off)

Measured value

Temperature setpoint

Deviation setting

4

14

(See 

note.)

De-

energized 

on PV

high limit

Hysteresis

Opn (on)

Cls

(off)

Alarm setting

Measured value

9

19

(See 

note.)

De-

energized 

on deviation 

high limit

Measured value

Temperature setpoint

Hysteresis

Deviation setting

Opn (on)

Cls (off)

5

15

(See 

note.)

De-

energized 

on PV

low limit

Hysteresis

Cls (off)

Opn (on)

Alarm setting

Measured value

10

20

(See 

note.)

Fault 

diagnostics 

output

The contact is closed at input 

burnout.

21

Heater

disconnection

alarm

The controller starts measuring the current from   

the heater disconnection detector when 100 

milliseconds have passed after turning on the 

output.

Cls

(on)

Heater current

Alarm setting

Opn (off)

25

FAIL

output

The output contact is opened in the 

following events:

• Program error • A/D converter error

• ROM error 

• RJC error

• RAM error 

• EEPROM error

• power failure

22

Note:   The alarms numbered 1 to 10 have 

no waiting action, while alarms 11 

to 20 have a waiting action.

 

The waiting action turns off the 

PV and deviation alarms that 

occur from the start of the control 

operation until a stable state is 

reached.

Abnormal

Alarm output = ON

Normal

Low limit alarm 

setpoint

In this area, the alarm output is turned 

off even when a measured value falls 

below the low limit alarm setpoint.

Time

Power-on

°C

Taken as 

normal.

Waiting action

The waiting action is effective in the following cases where;

• The power is turned on

• SP is changed

• The alarm type is changed

 Description of Parameters

This section describes the parameter functions specific to the UT130 temperature controllers.

(The functions described in other sections of this manual and the general functions are not 

discussed.)

Parameter

Function

Parameter

Function

Control 

mode

Select one from the following:

a. Dynamic auto tune control (SLF) (See note)

b. PID control (PID)

c. On/off control (ONF)

Note:  Dynamic auto tune control is not available 

for heating/cooling control.

Read the section below this table to find out more 

about dynamic auto tune control.

PV input 

bias

This function adds a bias value to the measured 

input value, and the result is used for display and 

control computation.

PV value inside the controller

measured input value

PV bias

+

=

This function is useful for carrying out fine 

adjustment when the PV value is within the 

required accuracy but it differs from the value 

obtained by other equipment.

CTL

BS

Manual 

reset

You can set this parameter only for control without 

an integral action (when registered as CTL=PID 

and I=OFF). The controller outputs the manual 

reset (MR) value when PV=SP. For example, if 

you set MR=50%, the controller outputs (OUT) 

50% when PV=SP.

Maximum/

minimum 

value of 

 target 

setpoint 

range

    

Using the SPH and SPL parameters, you can limit 

the setting range of the target setpoint (SP) within 

the measured input range.

This function prevents SP from being mistakenly 

set at too large or too small a value (beyond the 

setting range). 

MR

SPH,  

 SPL

Cooling-side

gain 

For heating/cooling control, you can set the ratio 

between the cooling-side output and heating-side 

output.

For example, if you set COL=2.0 and the heating-

side output is 10% at a certain deviation (SP-PV), 

then the cooling-side output will be 20% when the 

cooling-side also reaches that deviation.

COL

Hysteresis 

for 

alarm 1 

and  2   

The alarms are output as relay outputs. Since a 

relay has a limited life, excessive on/off actions will 

shorten the life of the alarm. To prevent this, you 

can set a hysteresis to prevent excessive on/off 

actions for both alarm 1 and alarm 2.

Deadband

 

You can only set a deadband for heating/cooling 

control. In a positive deadband, there are neither 

heating-side nor cooling-side outputs. In a 

negative deadband, there are both heating-side 

and cooling-side outputs, which overlap each 

other.

HYS

HYS

ON

OFF

ON

OFF

Deadband

DB (+)

Deadband

DB (+)

0

SP

PV

100%

100

0

SP

100

PV

100%

Cooling 

side

Heating 

side

100%

0%

1. When the deadband of a heating/

cooling type is positive

(Proportional band [P] control)

2. When both the heating and cooling 

sides are under on-off control

HY1,   

HY2

SUPER 

function 

 selection

The SUPER function is effective in the following 

cases:

a. An overshoot must be suppressed.

b. The rise-up time needs to be shortened.

c. The load often varies.

d. SP is changed frequently.

Note 1:  The SUPER function will not work 

when on/off control is selected, or I or D 

constants is set at OFF in PID control.

Note 2:  For some types of systems, the SUPER 

function may not be so useful.  If this is the 

case, turn off the function.

DB

 

SC

Hysteresis 

for 

on/off 

control   

For on/off control (CTL=ONF), you can set a 

hysteresis band around the on/off point (SP) to 

prevent chattering.

On/off point (SP)

Hysteresis band

ON

OFF

Priority of 

PV/SP 

display 

Since the UT130 controller has a single data 

indicator, you can give display priority to either 

PV or SP. The data which has the priority will be 

displayed on the data indicator upon power-on 

or when the operating display is resumed from a 

parameter setting display using the 

 key 

(by pressing for at least 3 seconds).

To switch the display between PV and SP, 

press the          key.

Displays SP

Displays PV

SP display lamp is on.

HYS

Control 

output 

/ cooling-

side 

control 

output

cycle time ]  

The cycle time is the period of on/off repetitions of 

a relay or voltage pulse output in time proportional 

PID control. The ratio of the ON time to the cycle 

time is proportional to the control output value.

Cycle time

t ON

t OFF

C o o l i n g - s i d e 

control output cycle 

time has the same 

functions.

*

CT  

CTC

DSP

PV input 

filter

  

This function should be used when the PV display 

value may fluctuate greatly, for example, when the 

measured input signal contains noise. The filter 

is of the first-order lag type, and FL sets the time 

constant. If a larger time constant is set, the filter 

can remove more noise.

Input

2-seconds filter

10-seconds filter

FL

 What is Dynamic Auto Tune Control?

Dynamic auto tune control is one of the features offered by the temperature controller.

When the controller is turned on or the measured input value (PV) starts “hunting”, this mode of 

control monitors the behavior of the PV and/or OUT (control output value) to automatically determine 

the optimum PID constants. This means that the PID constants may be changed automatically. If this 

is not desirable for your system, operate the controller in the normal “PID control”.

If you want to automatically determine the PID constants at the initial startup of the controller, first 

define the target setpoint (SP) and then turn the controller off once and then back on again. Do not 

use dynamic auto tune control for a system where there is interference or continual disturbances.

 Parameter Lists 

Numbers in ( ) are the parmeter setpoints that apply when the 

communication function is used. Ex. OFF(0), ON(1)

(1) Target Setpoint (SP)

Code

Name

Setting range and unit

Default

User setting

(SP value display)

Target 

setpoint

Minimum value (SPL) to maximum value (SPH) of target 

setpoint range

Unit: °C/°F

SPL

(2) Operating Parameters: Parameters changed rather frequently during operation.

Code

Name

Setting range and unit

Default

User setting

A1

Alarm 1 

setpoint

 

 PV alarm    Unit: °C/°F

   Setting range:  minimum value to maximum value of 

measured input range

 

Deviation alarm    Unit: °C/°F 

   Setting range:  –100 to 100% of the measured input range 

span

 

Heater disconnection alarm    Unit: A (ampere) 

  Setting range: OFF(0), 1 to 80 

  (can be set for the alarm 1 setpoint only)

Max. value of 

measured input 

range (PV alarm)

A2

Alarm 2

setpoint

Min. value of 

measured input 

range (PV alarm)

HC

Heater 

disconnection 

current 

measured 

value

“HC” is not a parameter to be set. The current value (0 to 80) of heater disconnection 

detector is displayed.    Unit: A (ampere)

Settings: When the display value is –––, the heater current is not being measured.

CTL

Control mode

ONF(0): On/off control

PID(1): PID control

SLF(2):  Dynamic auto tune control (cannot be set for heating/

cooling control)

SLF(2) :  standard 

type;

PID(1) :  heating/

cooling type

AT

Auto-tuning

OFF(0): Stop auto-tuning(AT)

ON(1): Start auto-tuning(AT)

OFF(0)

P

Proportional 

band

1°C /°F to the temperature that corresponds to 100% of the 

measured input range span

5% of measurd input 

range span

I

Integral time 1 to 999 seconds; 

OFF(0): no integral action

240 seconds

D

Derivative 

time

1 to 999 seconds; 

OFF(0): no derivative action

60 seconds

MR

Manual reset -19.9 to 99.9 % : Standard type

-100 to 100 % : Heating/cooling type

50.0% : standard 

type; 0.0% : heating/

cooling type

COL

Cooling-side 

gain

0.01 to 9.99 times

1.00 times

DB

Dead band

 

PID control    Unit: °C/°F

  

Setting range:  –(proportional band setting) to +(proportional 

band setting)

 

On/off control    Unit: °C/°F

  

Setting range: –50 to +50% of measured input range span

3.0% of measured 

input range span

HYS

Hysteresis for 

on/off control

0°C /°F to the temperature that corresponds to 100% of the 

measured input range span 

0.5% of measured 

input range span

CT

Control 

output cycle 

time

1 to 240 seconds

30 seconds

CTC

Cooling-side 

control output 

cycle time

1 to 240 seconds

30 seconds

FL

PV input filter OFF(0), 1 to 120 seconds

OFF(0)

BS

PV input bias –100 to 100% of measured input range span

0% of measured 

input range span

LOC

Key lock

0: No key lock

1:  Prevents operations from being changed except for the 

changing of SP in the operating display

2:  Prevents all parameter changing operations

–1:  Set “-1” to enter the setup parameter setting display. But 

if “LOC=1 or 2” is already set, the parameter value can 

not be changed by setting “LOC=-1” only. To change 

the parameter value, set “LOC=0” at first (for disabling 

keylock), then set “LOC=-1” once again.

0

(3) Setup Parameters: Parameters rarely changed in normal use after once having been set.

Code

Name

Setting range and unit

Default

User setting

IN 

Measured 

input type

1 to 7, 12, 13, 15 to 19, 31 to 37, 42, 43, 45 to 48 (See 

measured input range code list.)      OFF(0): No input

(If no input type is specified at the time of ordering, you must 

set the input type.)

OFF(0), or the input 

range code specified 

with order

SPH 

Maximum 

value of 

target 

setpoint 

range

(SPL+1°C) to the maximum value of the measured input 

range; Unit: °C/°F

Maximum value 

of measured input 

range

SPL 

Minimum 

value of 

target 

setpoint 

range

Minimum value of measured input range to (SPH–1°C)

Unit: °C/°F

Minimum value of 

measured input 

range

AL1 

Alarm 1 type OFF(0), 1 to 22 (See the alarm function list.)

25 (for the heater disconnection alarm /HBA option only)

1

(PV high limit alarm)

AL2 

Alarm 2 type

OFF(0), 1 to 22 (See the alarm function list.)

2

(PV low limit alarm)

HY1 

Alarm 1 

hysteresis

0 to 100% of measured input range span

Unit: °C/°F

0.5% of measured 

input range span

HY2 

Alarm 2 

hysteresis

SC 

SUPER 

function

ON(1): Uses the SUPER function

OFF(0): Does not use SUPER function

Note: Not displayed when on/off control

OFF(0)

DR 

Direct/

reverse 

action

0: Reverse action

1: Direct action

Note: Not displayed for heating/cooling type

0

DSP 

Priority of PV/

SP display

0: Displays PV

1: Displays target setpoint (SP)

0

PSL 

Protocol 

selection

0: PC-link communication

1: PC-link communication with sum check

2: Ladder communication

3: MODBUS in ASCII mode

4: MODBUS in RTU mode

0

ADR 

Controller 

address

1 to 99

However, the number of controllers that can be connected per 

host device is 31 at the maximum.

1

BPS 

Baud rate

2.4(0): 2400 bps

4.8(1): 4800 bps

9.6(2): 9600 bps

9.6(2)

PRI 

Parity

NON(0): Disabled

EVN(1): Even parity

ODD(2): Odd parity

EVN(1)

STP 

Stop bit

1 or 2 bits

1 bit

DLN 

Data length

7 or 8 bits

• 8 bits when ladder, MODBUS (RTU)

• 7 bits when MODBUS (ASCII)

8 bits

 IMPORTANT

To use dynamic auto tune control,

(1)  be sure to turn on the final control element, such as a heater, before starting the 

control, and 

(2)  make sure the controlled loop is a closed loop.

If you do not follow these precautions, improper PID constants may be written into the 

controller. If this occurs, carry out the following:

•  Set the parameter CTL at PID.

•   Set the PID constants at the factory-set defaults (P = (upper range-limit - lower range-

limit) × 5%; I = 240 sec.; and D = 60 sec.)

•   Set the parameter CTL at SLF.

If the control still doesn’t work properly, stop using the dynamic auto tune control 

function. Change the parameter CTL setting to PID and execute auto-tuning to obtain 

the PID constants.

Отзывы: