11-1
IM 05P02D41-01EN
Alarm Functions
11
11.1 Setting Alarm Type
Description
These alarms work irrespective of the operation mode.
The alarm-related parameters consist of the alarm type (type, stand-by action, energized/
de-energized, and latch function), PV velocity alarm time setpoint, alarm hysteresis,
alarm (On-/Off-) delay timer, and alarm setpoint.
Alarm-related parameter
Number of settings
Alarm type
2 (number of settings)
PV velocity alarm time setpoint 2 (number of settings)
Alarm hysteresis
2 (number of settings)
Alarm (on-/off-) delay timer
2 (number of settings)
Alarm setpoint
2 (number of settings)
► Alarm hysteresis: 11.3 Setting Hysteresis to Alarm Operation
► Alarm delay timer: 11.4 Delaying Alarm Output (Alarm Delay Timer)
► Alarm setpoint: 6.4 Setting Alarm Setpoint
Factory default: Only four groups of alarm-related parameters are displayed.
► Terminal function: 17.4.7 Contact Output Wiring
Alarm output can be assigned to the unused control relay output or contact output.
► Control relay output: 11.5 Setting Alarm Output to Control Relay Terminal
► Contact output: 12.2.1 Setting Function of Contact Output
Energized/de-energized of alarm output can be changed.
► Energized/de-energized: 12.2.2 Changing Contact Type of Contact Output
To read the conditions of alarms, outputs, or latches via communication, see
Communication Interface User's Manual.
Chapter 11 Alarm Functions
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...