5. CHANGING SETTINGS
IM 2493WVP-1
16
OUT3: There is no multiplier for Out3 (Power Factor). The first digit only toggles
between ‘0’ and ‘1’. The decimal point cannot be changed.
Note that the output settings have a precision of four (4) digits only. When the
PT or CT ratio is large, this will result in rounding if you try to set a value too
precisely. For example: If a 1phase/2wire/120V/5A meter has a PT ratio of
1000:1, then the output settings for watts and VARs must be in units of 100,
because you are now dealing with a range of values from
–900,000 to 900,000. Trying to set a value to 124 or another value not divisible
by 100 will result in the value being rounded to the nearest 100’s.