5. CHANGING SETTINGS

IM 2493VVV-1

10

Changing the Baud Rate setting

When you reach the setting, press Set and the whole value will begin blinking.

To change it to the next choice, press Inc.  You can scroll through all the choices
with the Inc key.  Those choices are 9600 (default), 4800, 2400 and 1200.  When
you have reached the desired choice, press Set.  The new setting will be saved
and the unit will proceed to the next mode.

Analog Output Scaling (If equipped)

The POWER SERIES 

Plus 

has the option of analog output, which can provide an

analog signal relative to the input of the meter.  The relationship between the
input and the output can be scaled by the user using the front panel.  Analog
Output 1 is always proportional to the value shown on the first (top) display.
Output 2 is always proportional to the middle display, and Output 3 will always be
proportional to the bottom display.  With 4-wire units, switching the display
between line-to-line and line-to-neutral will result in a corresponding change in
the analog output.

A 150V voltmeter with 0 to 1 milliamp output,
for example, has the following default settings:

PT ratio:  1 to 1
Analog Output LO:  0 Volts
Analog Output HI:  150 Volts

The LO is the input value at which the output
will be 0 mA.  The HI is the input value at
which the output will be 1 mA.  The charts at
right show the relationship of input and output.

0

30

60

90

120

150

0

0.25

0.5

0.75

1

DC Current Out (mA)

Содержание Power Series Plus IM 2493VVV-1

Страница 1: ...Users Power Series Plus Manual Power Series Plus 3 in 1 AC Voltage Digital Switchboard Meter IM 2493VVV 1 IM 2493VVV 1 Revision 1 October 1999...

Страница 2: ...3 Configuration 4 Configuring the 2493 POWER SERIES Plus Meter 4 Keymap 6 Changing Settings 8 Changing the potential transformer pt ratio setting 8 Changing the rolling average setting 9 Changing the...

Страница 3: ...any reason both Auxiliary Power and input voltages and currents must be de energized Limited Warranty This meter has been delivered to you after strict quality control and inspection Yokogawa Corpora...

Страница 4: ...rized modification or servicing of the Equipment The foregoing warranty is exclusive and in lieu of any other warranties of quality whether expressed or implied including any warranty of merchantabili...

Страница 5: ...PERATURE RANGE 40 to 85 Celsius INPUT RANGES 0 150 VAC or 0 300 VAC 3P4W 0 150 VAC or 0 240 VAC 3P3W POTENTIAL TRANSFORMER RATIO RANGE 1 1 through 1250 1 ANALOG OUTPUTS Optional 0 1 mADC 10 VDC compli...

Страница 6: ...ing or changing settings it moves between settings or between digits This button will increment the value being changed It is also used to display Max readings This button when viewing or changing set...

Страница 7: ...s press Next You can scroll through all the settings by pressing Next To go back to normal operations press Mode To change the setting being shown press Set See the specific sections on the following...

Страница 8: ...e front panel key options when operating in normal reading mode The options are Mode Mode Invokes change setting menu see flow chart page 6 Mode Next Toggle from Line Line to Line Neutral display Mode...

Страница 9: ...ERIES Plus meter using the push keys on the front panel Note This flowchart gives information pertaining to units equipped with YCA communications option or no communications option The setup flow is...

Страница 10: ...will jump to the first position on the next Inc Pressing Set again will bring you to the Multiplier Kilo setting In the leftmost digit you will see a blinking and if the multiplier light is on it wil...

Страница 11: ...sponse time The analog output response time is not affected by this setting When you reach the Average setting press Set and the first digit will begin blinking To increment the value of the digit pre...

Страница 12: ...input and the output can be scaled by the user using the front panel Analog Output 1 is always proportional to the value shown on the first top display Output 2 is always proportional to the middle di...

Страница 13: ...ip is shown at right Changing the Analog Output Settings When you reach the out1 or out2 or out3 display press Set and the value of HI will be displayed Pressing Set again will cause the first digit t...

Страница 14: ...Even if you do not want to change the LO setting you still must go through the steps in LO to save changes that were made to the HI value Nothing is stored in memory until you are in the LO setting C...

Страница 15: ...aller than the minimum span So with a 150V Voltmeter you could set the LO to 0 and the HI to 45 Or you could set the LO to 115 and the HI to 160 But you could not set the LO to 50 and the high to 90 9...

Страница 16: ...6 CONNECTION DIAGRAMS 6 CONNECTION DIAGRAMS IM 2493VVV 1 14 Connection Diagrams WARNING All circuits should be de energized when making connections to the rear terminal block...

Страница 17: ...6 CONNECTION DIAGRAMS IM 2493VVV 1 15 Mounting and Outline...

Отзывы: