background image

Store this manual in an easily accessible place  
for quick reference.

User's
Manual

2nd Edition: October 2017 (YMI)
All Rights Reserved. Copyright © 
2015, Yokogawa Meters & Instruments Corporation, 
2017, Yokogawa Test & Measurement Corporation

A3

Printed in China

9.  Display Functions

Lit when the measured insulation 

resistance is being held.

Flashes when the battery voltage is low.

Lit when the rating setting is 

1000 V/2000 MΩ.

Lit when the rating setting is 

500 V/2000 MΩ

Lit when the rating setting is 

250 V/200 MΩ.

Lit when the rating setting is 

125 V/200 MΩ.

Indicates overrange (OL).

Indicates the extension bar graph.

Change toward smaller values

Change toward larger values
Stable

Sub-display

Indicates:

• Comparator setting value or 

the storage number; or

• The storage number for memory.

Indicates the unit for 

insulation resistance for comparator.

Lit when:

• Pressing the MEAS key in 

insulation resistance measurement; and

• Residual electrical charges are present 

during discharging.

Lit when the comparator is activated.
Lit when the measured 

insulation resistance is lower than

the comparator setting value.

Lit when the memory feature is in use.
Indicates the unit for 

AC voltage measurement.

Indicates the unit for insulation resistances.
Indicates the unit for 

conductor resistance measurement.

Indicates the continuity mark, 

which is lit when the measured 

insulation resistance is lower than 40 Ω.

The extension bar graph shows how 

the measured value is changing 

(trend) as follows:

Note that the number of      marks means 

the degree of change.

■ Overrange Display Functions

  OL Display

The tester displays the OL mark when the measured resistance exceeds  

the following values.

 

Insulation resistance measurement:

 

 

For 1000 V and 500 V ratings: 2000 MΩ

 

 

For 250 V and 125 V ratings: 200 MΩ

 

Conductor resistance measurement: 400 Ω

 

 Display

The tester displays the   mark when the internal calculation exceeds  

the following values.

 

Insulation resistance measurement:

 

 

For 1000 V and 500 V ratings: approx. 4000 MΩ

 

 

For 250 V and 125 V ratings: approx. 400 MΩ

  Change to Upper/Lower Ranges

• To upper range

 

When the digital reading exceeds 4000,  

 

the measuring range changes to the next upper range.

• To lower range

 

When the digital reading falls below 360,  

 

the measuring range changes to the next lower range.

  Lower Resolution Display

If the digits below the decimal point are not stable,  

they can be automatically omitted to limit the resolution.

10.  Before Measurement

1. Safety

• Read the handling precautions in this manual carefully.

• Make sure it is safe before starting measurement.

2. Battery Voltage Verification

• Make sure that the battery voltages are within the valid ratings 

 

(i.e. the 

 mark is not flashing).

• If the batteries are low, replace them as specified in the battery replacement 

 

section of this manual.

NOTE

 

As the 

 mark indication depends on the load (current consumption), 

 

check that the 

 mark does not appear for the largest load  

when short-circuiting the earth probe and the line probe (0 MΩ).

3. Connecting the Probes

WARNING

 

• Remove the probes from the measured object before attaching/detaching 

 

the probes to/from the tester.

• Make sure the MEAS key is off when attaching/detaching the probes to/from the tester.

• Plug the earth probe into the earth terminal.

• Plug the line probe into the line terminal.

4. Function Switch Verification

Be sure to confirm that the function switch is set to the desired rating.

5. 1000-V Rating

When measuring with the 1000-V rating,  

see section 14.1, “Double-action1000-V Function”.

11.  Measuring the Insulation Resistance

11.1  Before Connecting the Probes

WARNING

 

• Turn off the power to the measured object before connecting or 

 

measuring insulation resistance.

• Electrical charges may be present in the cables attached to or metal of 

 

the electrical equipment being tested. Verify that the equipment is free from  

electrical charges before connecting the testing terminals.

• Be sure to confirm that the function switch is set to the desired rating.

ON

OFF

125 V/200 MΩ
250 V/200 MΩ
500 V/2000 MΩ
1000 V/2000 MΩ

Measurement wiring

Insulation resistance ratings:

Power supply side

 (primary)

Load side 

(secondary)

Set the switch to OFF

Line probe

Earth probe

11.2. Setting the Function Switch

Turn the function switch to the desired measurement rating position.

The initial display is “---- MΩ”.

11.3  Connecting the Earth Probe

• If the measured object is grounded, connect the earth probe clip to 

 

the measured object’s ground line.

• If the measured object is not grounded, this process may be omitted.

11.4  Connecting the Line Probe

Bring the line probe into contact with the measured object, and then 

 

press the 

 key. The display indicates the insulation resistance of  

the measured object.

NOTE

 

During measurement, exercise care to prevent the leadwire of the line probe from  

coming into contact with the ground, floor or any other object. 

Not observing this precaution may result in a failure to measure the correct  
insulation resistance.

11.5  After Measurement

WARNING

 

• Immediately after measurement, electrical charges resulting from the applied testing 

 

voltage may remain present in the probes or measured object.

• The tester, therefore, is designed to automatically begin discharging electricity upon 

 

completion of measurement.  

Verify that the ALARM LED turns off when discharging is complete.

12.  Measuring AC Voltages

WARNING

 

• Do not press the MEAS key while measuring AC voltages.

• Voltage that exceeds the specified limit (600 V) must not be applied to terminals. 

 

Doing so causes all digits of the measuredvoltage to flash and the buzzer to beep.

12.1  Setting the Function Switch

Turn the function switch to an AC voltage

measurement ( 

 V) position.

12.2  Connecting the Earth Probe

• If the measured object is grounded, connect the earth 

 

probe clip to the measuredobject’s ground line.

• If the measured object is not grounded, 

 

this process may be omitted.

12.3  Connecting the Line Probe

Bring the line probe into contact with the measured object.

The display indicates the AC voltage of measured object.

Model MY40

Insulation Resistance Tester

[ Operation Manual ]

This manual describes the specifications and handling precautions of 

 

the insulation resistans tester. 

Before using this product, thoroughly read this manual to understand how to use it properly.

  IM MY40-E: 

Safety precautions, components and specifications etc.

  IM MY40-02EN:  Operation manual (this manual)
Contact information of Yokogawa offices worldwide is provided on the following sheet.

  PIM 113-01Z2:  Inquiries  List of worldwide contacts

IM MY40-02EN

2nd Edition: Oct. 2017 (YMI)

Отзывы: