Page 22 of 51
IM 60A02S01-01E-A
2.6.3 Canadian Standards Association (CSA) Certification
1) Technical Data
a. CSA Intrinsically Safe/CSA Explosionproof/ CSA Non-Incendive Type.
Caution for CSA Intrinsically Safe/CSA Explosionproof/CSA Non-Incendive type.
Note 1. Model MLX Loop Process Indicator with optional code /CU1 are applicable for use
in potentially hazardous locations.
•
Certificate No. 4000798
•
Certified to: CSA C22.2 No.25, CSA C22.2 No.30, CSA C22.2 No.157, CSA
C22.2 No.213, CSA C22.2 No.60079-0, CAN/CSA E60079-11
• Explosionproof/Dust-Ignition-Proof for:
- Class I, II, III; Groups A - G; Divisions 1 & 2.
- Class I, Zone 1, Group IIC T4.
- Tamb. –40°C to 80°C
• Intrinsically Safe for:
- Class I, Division 1, II, III; Groups A - G; Divisions 1 & 2.
- Zone 20, Class I, Zone 0
- AEx ia IIC T4
- Tamb. –40°C to 80°C
• Non-Incendive for:
- Class I, II, III; Groups A - D, F, G; Divisions 2.
- Class I, Zone 2, Group IIC T4.
- Tamb. –40°C to 80°CEnclosure: Type 4X
•
Temp. Code: T4
•
Amb. Temp.: –40°C to 80°C
•
Enclosure: “Type 4X”
Note 2. Electrical Data
•
Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 28 V
Maximum Input Current (Imax/Ii) = 115 mA
Maximum Input Power (Pmax/Pi) = 0.65 W
•
Non-Incendive ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Input Current (Imax/Ii) = 150 mA
Maximum Input Power (Pmax/Pi) = 0.85 W
•
Installation Requirements
Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
Voc ≤ Vmax, Isc ≤ Imax,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are parameters of barrier.