MODEL AND SUFFIX CODES

Model

Suffix codes

Description

VJH1

-0

x x -x x x

0

/x

Isolator

Fixed code

-0

Always -0

Output

1

1 output

2

2 outputs

Power supply

6

100-240 V AC/DC 

(*1)

7

15-30 V DC 

(*2)

Input signal

-A

4 to 20 mA DC

-B

2 to 10 mA DC

-C

1 to 5 mA DC

-D

0 to 20 mA DC

-E

0 to 16 mA DC

-F

0 to 10 mA DC

-G

0 to 1 mA DC

-H

10 to 50 mA DC

-1

0 to 10 mV DC

-2

0 to 100 mV DC

-3

0 to 1 V DC

-4

0 to 10 V DC

-5

0 to 5 V DC

-6

1 to 5 V DC

-7

−10 to +10 V DC

-Z

Custom order (DC voltage/DC current)

Output-1 signal

A

4 to 20 mA DC

B

2 to 10 mA DC

C

1 to 5 mA DC

D

0 to 20 mA DC

E

0 to 16 mA DC

F

0 to 10 mA DC

G

0 to 1 mA DC

1

0 to 10 mV DC

2

0 to 100 mV DC

3

0 to 1 V DC

4

0 to 10 V DC

5

0 to 5 V DC

6

1 to 5 V DC

7

−10 to +10 V DC

Z

Custom order (DC voltage/DC current)

Output-2 signal

A

4 to 20 mA DC

6

1 to 5 V DC

N

No output-2

Z

Custom order (DC voltage/DC current)

Fixed code

0

Always 0

Option

/SN

No socket (with socket if not specified)

/C0

Coating 

(*3)

/FB

Fuse bypass 

(*3)

/C

With OOP 

(*4) (*5)

/HC

With OOP (HART communication) 

(*4) (*5)

*1: Operating range: 85 to 264V

*2: Operating range: 12 to 36V

*3:  When option code /C0 or /FB is specified, the conformity to the safety 

and EMC standards is excluded. CE marking is not applicable.

*4: When the option code /C or /HC is specified, only the input signal code 

“A” (4 to 20 mA DC) can be specified, and the output-1 signal code can 

be specified only “A” (4 to 20 mA DC).

*5: Only output-1 is supported.

1.  MOUNTING METHOD

 CAUTION

 

Plug/disconnect the main unit into/from the 

socket vertically to the socket face.  Otherwise the 

terminals may bend and it may cause bad contact.

 

The converter shall not tilt 5 degrees or more in 

either direction when installed.

 

When the converter is not connected to the socket,  

it is necessary to protect the socket against ingress 

of dust to the connector part.

 

Keep this product in a conductive bag when 

plugged out, during transport or storage.

1.1  Wall Mounting

Loosen the main unit-fixing screw of the product and pull out the 

main unit from the socket. Fix the socket on the wall with screws. 

Next, insert the main unit into the socket and fasten the main unit 

with the main unit-fixing screw.

 

29.5 or more

22±0.2

2-M4 or

2-ø4.5 or more

Mounting Dimensions

Unit: mm

59±0.3

Main unit-fixing screw

Socket

Main unit

Threaded hole for

fixing the main unit

Mounting screws

1.2  DIN Rail Mounting

Insert a DIN rail into the upper part of the DIN rail groove on the 

rear of the socket, and then slide the slide lock at the lower part of 

the socket upwards until the socket is fixed into position as shown 

below.

 

DIN rail

DIN rail

(Rear of socket)

Slide lock

DIN rail

Fit into here

Push

1.3  Mounting Using a Multi-mounting Base

When using a multi-mounting base, see the User’s Manual for 

VJCE-01A (VJ Mounting Base for communication) (IM 77J01C51-

11E).

1.4  Using a Duct

When using a wiring duct, install the duct at leaset 30 mm away 

from the top and bottom faces of the main unit.

2.  INSTALLATION AND ENVIRONMENTAL 

CONDITIONS

 •

Avoid the following environments for installation locations: 

 

Areas with vibrations, corrosive gases, dust, water, oil, 

solvents, direct sunlight, radiation, a strong electric field, 

and/or a strong magnetic field, direct radiant heat

wind, 

temperature fluctuation.

 •

If there is any risk of a surge being induced into the power line 

and/or signal lines due to lightning or other factors, a dedicated 

lightning arrester should be used as protection for both the 

product and a field-installed device.

 • Use indoors at an altitude of 2000 m or less.

 •

Operating temperature/humidity range: −10 to 55°C (−10 

to 45°C for side-by-side mounting*)/5 to 90%RH (no 

condensation)

*  If the previous model (style S3.xx earlier) is installed 

together, the ambient temperature is 0 to 40°C.

 •

Continuous vibration: (at 5 to 9 Hz) Half amplitude of 3 mm or 

less (at 9 to 150 Hz) 9.8m/s

2

 or less, 1 oct/min for 90 minutes 

each in the three axis directions

 •

Impact: 98 m/s

2

 or less, 11 ms, 3 axes, 6 directions, 3 times 

each

2

IM 77J01H01-01E

7th Edition

Содержание JUXTA VJH1

Страница 1: ...ause injury to the user or damage to the instrument or property and indicates precautions that should be taken to prevent such occurrences CHECKING PRODUCT SPECIFICATIONS AND PACKAGE 1 Checking the Model and Product Specifications Check that the model and specifications indicated on the nameplate attached to the main unit are as ordered 2 Packaged Items Check that the package contains the followin...

Страница 2: ...1 Wall Mounting Loosen the main unit fixing screw of the product and pull out the main unit from the socket Fix the socket on the wall with screws Next insert the main unit into the socket and fasten the main unit with the main unit fixing screw 29 5 or more 22 0 2 2 M4 or 2 ø4 5 or more Mounting Dimensions Unit mm 59 0 3 Main unit fixing screw Socket Main unit Threaded hole for fixing the main un...

Страница 3: ...ground the ground terminal through minimum resistance The length and thickness of the grounding cable should be as short and thick as possible Directly connect the lead from the ground terminal terminal no 8 of the product to the ground Do not carry out daisy chained inter ground terminal wiring The product is sensitive to static electricity exercise care in operating it Before you operate the pro...

Страница 4: ...CAT III For measurements performed in the building installation Distribution board circuit breaker etc IV CAT IV For measurements performed at the source of the low voltage installation Overhead wire cable systems etc EMC standards CE EN 61326 1 Class A Table 2 EN 61326 2 3 The instrument continues to operate at a measurement accuracy of within 20 of the range during testing EN 55011 Class A Group...

Отзывы: