IM 77J01A21-01E

3rd Edition

[%]

0

20
15

40

60

80

100

[1]

[2]

[3]

[4]

1 sec

2 sec

3 sec

4 sec

Alarm-2 hysteresis (5%)

Alarm-1 hysteresis (10%)

Alarm-1 setpoint (80%)

Alarm-2 setpoint (15%)

Elapsed time

sec

Alarm-1 ON delay

Alarm-1 OFF delay

Alarm conditions

established

Alarm conditions

established

Normal conditions

established

Normal conditions

established

Low-limit alarm ON

Low-limit alarm OFF

Alarm-2 ON delay

Alarm-2 OFF delay

[1]: Alarm status does not continue for more than 1 second after the 

alarm conditions are established at alarm 1.

[2]: Normal status does not continue for more than 2 seconds after the 

normal conditions are established at alarm 1.

[3]: Alarm status does not continue for more than 3 seconds after the 

alarm conditions are established at alarm 2.

[4]: Normal status does not continue for more than 4 seconds after the 

normal conditions are established at alarm 2.

Alarm conditions established

Alarm conditions established

High-limit alarm ON

High-limit alarm OFF

Normal conditions established

Normal conditions established

Alarm-1 action

Alarm-2 action

Alarm

Normal

Normal

Normal

Alarm

Normal

7.  LIST OF PARAMETERS

DISPLAY

ITEM

MODEL

Model

TAG NO

Tag No.

SELF CHK

Self-check result

A

DISPLAY1

Display 1

A01 INPUT1

Input value 1

A09 OUTPU1

Output value 1

A15 ALM1 STATUS

Alarm-1 status

A16 ALM2 STATUS

Alarm-2 status

A54 STATUS

Status

*1

A56 REV NO

Rev No.

A58 MENU REV

Menu Rev

A60 SELF CHK

Self-check result

B

DISPLAY2

Display 2

B01 INPUT1

Input value 1

B09 OUTPUT1

Output value 1

B15 ALM1 STATUS

Alarm-1 status

B16 ALM2 STATUS

Alarm-2 status

B60 SELF CHK

Self-check result

D

SET (I/O)

Setting (I/O)

D01 TAG NO.1

Tag no.1

D02 TAG NO.2

Tag no.2

D03 COMMENT1

Comment 1

D04 COMMENT2

Comment 2

D41 LINEARIZE

Linearize

D42 LOW CUT

Low cut

D57 S/W FILTER

Software filter

D59 NMRR

Frequency setting

*2

D60 SELF CHK

Self-check result

E

SET(ALM)

Setting (alarm output)

E03 SET POINT1

Alarm-1 setting (%)

E04 SET POINT2

Alarm-2 setting (%)

E05 ALM1 ACTION

Direction of alarm-1 action

E06 ALM2 ACTION

Direction of alarm-2 action

E09 HYSTERESIS1

Alarm-1 hysteresis

E10 HYSTERESIS2

Alarm-2 hysteresis

E11 ON DELAY1

Alarm-1 ON delay setting

E12 ON DELAY2

Alarm-2 ON delay setting

E13 OFF DELAY1

Alarm-1 OFF delay setting

E14 OFF DELAY2

Alarm-2 OFF delay setting

E15 RL1 ACTION

Direction of alarm-1 relay action

E16 RL2 ACTION

Direction of alarm-2 relay action

E60 SELF CHK

Self-check result

P

ADJUST

Adjustment

P04 IN1 ZERO ADJ

Zero adjustment of input-1

P05 IN1 SPAN ADJ

Span adjustment of input-1

P60 SELF CHK

Self-check result

Q

TEST

Test

Q10 ALM1 TEST

Forced output (alarm 1)

Q11 ALM2 TEST

Forced output (alarm 2)

Q60 SELF  CHK

Self-check result

*1

The status is displayed for service personnel to see 

history records.

*2

The parameters are the items to be set at the factory.

8.  MAINTENANCE

The product enters the operable status as soon as the power is 

turned on, but requires 10 to 15 minutes of warm-up to meet the 

performance requirements.

8.1  Calibration Apparatus

 • A voltage and current generator (YOKOGAWA GS200 or the 

equivalent): 1

 • Digital Multimeter (YOKOGAWA 7561 or equivalent): 1

•  Setting tool for adjustment (Refer to “4.2 Connecting the 

Setting Tools” in this manual.)

8.2  Calibration Procedure

1. 

Connect the instruments as shown in figure below.

 

10

11

3 2 1

4

5

6

7

8

9

11

10

8

9

7

5

2

1

3

3

4

GND

ALM2 (NO)

COM

ALM1 (NO)

COM

DMM

DMM

Input

With SINK current

Without SINK current

Alarm-2 output

Alarm-1 output

Power supply

L+

+

N–

+

voltage and 

current 

generator

voltage and 

current 

generator

2.  Produce the input signal equivalent to 0% of the input range 

from the voltage and current generator to the product.

3.  Then, read the input value of Display items, “A01: INPUT1” 

using the VJ77 and check that the input value is within the 

rated accuracy range.

4.  Take the same procedure for the input signal equivalent to 25, 

50, 75 and 100% of the input range and check that the input 

values are within the rated accuracy range.

For alarm output, check the relay action by the alarm indicator 

lamp or resistance of output terminals.

●  If it is outside the rated accuracy range, use the VJ77 PC-

based Parameters Setting Tool to make adjustments.

User’s Manual for VJ77 [Document No.: IM 77J01J77-01E]

9.  TRANSPORT AND STORAGE CONDITIONS

 • Temperature: -25 to 70°C

 • Temperature change rate: 20°C per hour or less

 • Humidity: 5 to 95%RH (no condensation)

 CAUTION

Keep this product in a conductive bag when plugged 

out, during transport or storage.