7.  LIST OF PARAMETERS

Parameter Display Item

MODEL

Model

TAG NO

Tag no.

SELF CHK

Self-check result

A

DISPLAY1

Display 1

*2

A01

INPUT1

Input value 1

A09

OUTPUT1

Output value 1

A10

OUTPUT2

Output value 2

A15

ALM1 STATUS

Alarm-1 status

A16

ALM2 STATUS

Alarm-2 status

A54

STATUS

Status

*1

A56

REV NO

Rev. no.

A58

MENU REV

MENU REV

A60

SELF CHK

Self-check result

B

DISPLAY2

Display 2

*2

B01

INPUT1

Input value 1

B09

OUTPUT1

Output value 1

B10

OUTPUT2

Output value 2

B15

ALM1 STATUS

Alarm-1 status

B16

ALM2 STATUS

Alarm-2 status

B60

SELF CHK

Self-check result

D

SET (I/O)

Setting (I/O)

*2

D01

TAG NO.1

Tag no. 1

D02

TAG NO.2

Tag no. 2

D03

COMMENT1

Comment 1

D04

COMMENT2

Comment 2

D32

OUT1 L_RNG

Output-1 low range

*3

D33

OUT1 H_RNG

Output-1 high range

*3

D34

OUT2 L_RNG

Output-2 low range

*3

D35

OUT2 H_RNG

Output-2 high range

*3

D41

LINEARIZE

Linearize

D42

LOW CUT

Low cut

D50

OUT1 DR

Direction of output-1 action

D51

OUT2 DR

Direction of output-1 action

D57

S/W FILTER

Software filter

D59

NMRR

Frequency setting

*3

D60

SELF CHK

Self-check result

E

SET(ALM)

Setting (alarm output)

*2

E03

SET POINT1

Alarm-1 setting (%)

E04

SET POINT2

Alarm-2 setting (%)

E05

ALM1 ACTION

Direction of alarm-1 action

E06

ALM2 ACTION

Direction of alarm-2 action

E09

HYSTERESIS1

Alarm-1 hysteresis (%)

E10

HYSTERESIS2

Alarm-2 hysteresis (%)

E11

ON DELAY1

Alarm-1 ON delay setting

E12

ON DELAY2

Alarm-2 ON delay setting

E13

OFF DELAY1

Alarm-1 OFF delay setting

E14

OFF DELAY2

Alarm-2 OFF delay setting

E15

RL1 ACTION

Direction of alarm-1 relay action

E16

RL2 ACTION

Direction of alarm-1 relay action

E60

SELF CHK

Self-check result

F

SET(COM)

Setting (communication)

*2

F01

PROTOCOL

Communication protocol

F02

ADDRESS

Address

F03

BAUD RATE

Baud rate

F04

PARITY

Parity

F05

DATA LEN

Data Length

F06

STOP BIT

Stop bit

F07

INPUT DEC PT

Decimal point position of input

F60

SELF CHK

Self-check result

M

X TABLE

Input breakpoint table

*2

M01

X TABLE

Input breakpoints data

M02

X TABLE

Input breakpoints data

M31

X TABLE

Input breakpoints data

M32

X TABLE

Input breakpoints data

M33 MAX POINT

Number of breakpoints

M60 SELF CHK

Self-check result

N

Y TABLE

Output breakpoint table

*2

N01

Y TABLE

Output breakpoints data

N02

Y TABLE

Output breakpoints data

N31

Y TABLE

Output breakpoints data

N32

Y TABLE

Output breakpoints data

N60

SELF CHK

Self-check result

P

ADJUST

Adjustment

*2

P04

IN1 ZERO ADJ

Zero adjustment of input-1

P05

IN1 SPAN ADJ

Span adjustment of input-1

P30

OUT1ZERO ADJ

Zero adjustment of output-1

P31

OUT1SPAN ADJ

Span adjustment of output-1

P32

OUT2ZERO ADJ

Zero adjustment of output-2

P33

OUT2SPAN ADJ

Span adjustment of output-2

P60

SELF CHK

Self-check result

Q

TEST

Test

*2

Q04 OUT1 TEST

Forced output (output 1)

Q05 OUT2 TEST

Forced output (output 2)

Q10 ALM1 TEST

Forced output (alarm 1)

Q11

ALM2 TEST

Forced output (alarm 2)

Q60 SELF  CHK

Self-check result

*1

The Status is displayed for service personnel to see history 

records.

*2

There are items not displayed depending on what output-2 

is specified.

X TABLE/Y TABLE is displayed when D41:LINEARIZE=ON.

*3

The parameters are the items to be set at the factory.

8.  MAINTENANCE 

The product starts running immediately when the power is turned 

on; however, it needs 10 to 15 minutes of warm-up before it 

meets the specified performance. 

For cleaning the instrument, use a soft and dry cloth.

8.1  Calibration Apparatus 

 •

A voltage and current generator (YOKOGAWA GS200 or the 

equivalent) 

 •

A voltmeter (YOKOGAWA 7561 or the equivalent) 

 •

A precision resistor of 250 Ω ± 0.01%, 1 W (for current output) 

 •

Setting tool for adjustment (Refer to "4.2 Connector for 

Communication" in this manual.)

8.2  Calibration Procedure 

1. 

Connect the instruments as shown in figure below. First adjust 

the output-1 signal and then the output-2 signal. 

Power Supply

Output-1 signal

R: For current output using 250 

    precision resistor

Voltage and

current

generator

Voltage and

current

generator

Output-2 signal

10

11

3 2 1

4

5

6

7

8

9

11

10

8

L

+

N

GND

3

4

+

Without SINK current

Input signal

DMM

DMM

DMM

DMM

2

5

R

+

1

3

+

With SINK current

2

5

Alarm-1 output 

Alarm-2 output 

ALM1
(NO)

COM

+

6

5

ALM2
(NO)

COM

+

7

9

R

+

2. 

Produce input signals equivalent to 0, 25, 50, 75, and 100% of 

the input span (or those equivalent to 0, 6.25, 25, 56.25, and 

100% of the input span if square root extraction is set) from 

the voltage and current generator to the distributor. 

3. 

Then, check that the distributor’s output signal shows voltages 

corresponding to 0, 25, 50, 75, and 100% of the input span 

within the rated accuracy range. 

For alarm output, check the relay action by the alarm indicator 

lamp or resistance of output terminals.

 •

When adjusting the output signal, use the VJ77 parameter 

setting tool.

For adjustment using a setting tool, refer to the User’s Manual for 

setting tool and “7. LIST OF PARAMETERS” in this manual.

User’s Manual for VJ77 [Document No.: IM 77J01J77-01E]

5

IM 77J01A07-01E