C2-1
IM 34M06C11-01E
C2.
Specifications and Configuration
C2.1
Specifications
Common Specifications
Item Specifications
Supply voltage range
100 to 240V AC, single phase 50/60Hz
Range of supply voltage change
85 to 264V AC, 50/60Hz ± 3Hz
Power consumption
35VA
Insulation resistance
5M
Ω
min. when tested between a group of external AC terminals and the FG terminal using a
500V DC insulation resistance tester
5M
Ω
min. when tested between a group of FAIL-signal contact output and internal circuit using a
500V DC insulation resistance tester.
Withstanding voltage
1500V AC for one minute between a group of external AC terminals and the FG terminal
1000V AC for one minute between a group of FAIL-signal contact output and internal circuit.
FAIL-signal contact output
Located on the front terminal block of power supply module;
contact ratings: 24V DC, 0.3A
(Equipped with both normally-open and normally-closed terminals)
Leakage current
3.5mA max.
Allowable momentary power failure time
20ms
Noise immunity
Tested using a noise simulator with a noise voltage of 1500Vp-p, pulse width of 1 µs, rise time of 1
ns, and repetition frequency of 25 to 60Hz.
For CE Marking-compliant modules, compliant to EN61326-1, EN61326-2-3
*5
and EN61000-6-2
Vibration resistance
Tested in compliance with JIS C60068-2-6 under the following conditions:
- Frequency ranges:
10 to 57Hz with an amplitude of 0.075mm
57 to 150Hz with an acceleration of 9.8m/s
2
(1G)
- Direction and sweep cycles: 10 times each in the X, Y, and Z directions
Shock resistance
Tested in compliance with JIS C60068-2-27 under the following conditions:
- Direction and sweep cycles: 3 times each in the X, Y, and Z directions with an acceleration of
147m/s
2
(98m/s
2
with DIN-rail mounting)
Surrounding air temperature range
Operating
:
0 to 55°C
Storage
:
-20°C to 75°C
Surrounding humidity range
Operating
:
10 to 90% RH (non-condensing)
Storage
:
10 to 90% RH (non-condensing)
Surrounding atmosphere
Must be free of corrosive gases, flammable gases or heavy dust.
Grounding Protective
earth
(Comply with the regulation of each country.)
Cooling method
Natural-air cooled
Mounting
Direct mounting with 4 M4-size set screws
*1
or 35-mm wide DIN-rail mounting
Structure
Designed for mounting inside a panel enclosure
Altitude of installation
Max. of 2000m above sea level
Compliance
with safety
and EMC
standards
*2
UL
UL508 approved File No.E188707
(Overvoltage Category
*3
:
II, Pollution Degree
*4
:
2)
CE
EMC
Directive
EN 61326-1 Class A, Table 2
EN 61326-2-3
*5
EN 55011 Class A, Group 1
EN 61000-6-2, EN 61000-3-2, EN 61000-3-3 compliance
Low Voltage
Directive
EN 61010-1, EN 61010-2-201 compliance (only for F3SC23-
□□
)
(Overvoltage Category
*3
II, Pollution Degree
*4
2)
RoHS
Directive
EN 50581 compliance
RCM
EN 55011 Class A, Group 1 compliance
EN 61326-1 Class A, Table 2 compliance
KC
Korea Electromagnetic Conformity Standard compliance
Finish color
Light cobalt blue, equivalent to Munsell 6.2PB 4.6/8.8;
lampblack, equivalent to Munsell 0.8Y 2.5/0.4
External dimensions
147 (W)× 100 (H)× 88.5 (D)(mm)
For more information, see the dimensional figures in Section A2.11, “External Dimensions,” for the
case where an F3BU04-0N module is used
*1:
For details on the number of mounting screws, see subsection A3.2.2, “Mounting Dimensions.”
*2:
For details on conforming modules, see Appendix A2, “Standard compliant products”.
*3:
The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has
four categories. Overvoltage Category II applies to systems with a rated voltage of 220/230/240V and applies to electrical
appliances, portable devices, etc.
*4:
The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a
reduction of dielectric strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to
an environment where normally only non-conductive pollution occurs but occasionally temporary conductivity caused by
condensation is to be expected.
*5:
EN61326-2-3 is applicable only to F3CU04-
□□
.
Содержание FA-M3V e-RT3 Plus
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 20: ...Blank Page ...
Страница 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Страница 22: ...Blank Page ...
Страница 34: ...Blank Page ...
Страница 159: ...A2 125 IM 34M06C11 01E Unit mm F3YD32 F3YD64 1M F3YD64 1A F3YD64 1F F3YD64 1P F3YD64 1R F3WD64 FA021106 VSD ...
Страница 160: ...Blank Page ...
Страница 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Страница 220: ...Blank Page ...
Страница 232: ...Blank Page ...
Страница 241: ...TOC B 1 IM 34M06C11 01E Hardware Manual Part B FA M3 Value F3SC21 1N IM 34M06C11 01E 40th Edition ...
Страница 242: ...Blank Page ...
Страница 252: ...Blank Page ...
Страница 253: ...TOC C 1 IM 34M06C11 01E Hardware Manual Part C FA M3 Value II F3SC22 F3SC23 IM 34M06C11 01E 40th Edition ...
Страница 254: ...Blank Page ...
Страница 268: ...Blank Page ...
Страница 274: ...Blank Page ...