![YOKOGAWA FA Link H2 Скачать руководство пользователя страница 97](http://html1.mh-extra.com/html/yokogawa/fa-link-h2/fa-link-h2_user-manual_3498012097.webp)
Appx.-5
IM 34M06H43-02E 2nd Edition : Sep.30, 2019-00
(5) Strip off a sufficient length of the
insulation of each wire to allow good
electrical contact with a ferrule terminal.
Then put and crimp a ferrule terminal
onto each wire using a crimping tool.
Check that the ferrule terminal size is
compatible with the wire size. Check that
each ferrule terminal is securely crimped
to a wire.
Ferrule terminal
(for 1-wire)
Ferrule terminal
(for 2-wire)
(6) Apply an insulation tube to the cable
such that it partially covers both the cable
insulation and the exposed wires. Then
shrink the tube with a heat gun.
Insulation tube
(7) Fully insert each ferrule terminal into the
connector.
Ensure that each ferrule terminal is
securely inserted in the connector.
Pin
Signal Name
Wire Color (KM8
)
5
SG
Green / Yellow
4
A
Blue
3
SHIELD
Drain
2
B
White
1
NC
-
T branch connector
Pin 5
Pin 1
(8) A connector-cable set is completed.
Note: Check the completed connector-
cable set for any wrong connection,
shorted circuit or open circuit using an
ohmmeter or other appropriate
instrument.
Содержание FA Link H2
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 18: ...Blank Page ...
Страница 24: ...Blank Page ...
Страница 36: ...Blank Page ...
Страница 82: ...Blank Page ...
Страница 92: ...Blank Page ...
Страница 100: ...Blank Page ...
Страница 102: ...Blank Page ...
Страница 104: ...Blank Page ...