![YOKOGAWA F3RS22-0N Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/yokogawa/f3rs22-0n/f3rs22-0n_user-manual_3494923042.webp)
4-11
IM 34M6H21-01E
2nd Edition : Aug, 2001-00
4.4 Using
Registers
F3RS22-0N and F3RS41-0N have many registers for handling various aspects of
transmission. This section describes the use of these registers.
List of Registers
Register
Number
Register
Type
Contents Default
Value
01
S
Input wait status
0 :
no
others : waiting for input
0
02
S
Interrupt request status
0
: receive terminated normally
1
: error during receiving
2
: break received
0
03
S
Input data status
Bit 5
: framing error
Bit 4
: overrun error
Bit 3
: parity error
Bit 2
: internal buffer overflow
Bit 1
: character-to-character receiving interval timeout
Bit 0
: break received
A bit is “1” when the corresponding error occurs.
0
04 S
Output processing data
status
Output status for OUTPUT/TRANSFER statement
=0
: sending terminated normally
z
0
: sending terminated abnormally
0
05 S
Input processing data
status
INPUT status for ENTER/TRANSFER statement
=0
: receiving terminated normally
z
0
: receiving terminated abnormally
0
06 S/C
Transmission
code
0
: internal code
1 :
ASCII
2
: JIS 8 unit
0
07 S/C
Character-to-character
receiving interval timeout .
processing
0
: receive terminated normally
1
: error during receiving
0
11 S/C
Character
length
0
: 7 bits
1
: 8 bits
Others : 8 bits
1
12
S/C
Length of stop bits
0
: 1 bit
1
: 1.5 bits
2
: 2 bits
Others : 2 bits
0
13 S/C
Parity
0 :
none
1 :
odd
2 :
even
Others :
even
2
14
S/C
Data transfer rate (bps)
0 :
75
1 :
150
2 :
300
3 :
600
4 :
1200
5 :
2400
6 :
4800
7 :
9600
8 :
19200
others :
19200
6
F3RS22-0N RS
control
0
: always ON
1
: ON only when sending
0
15 S/C
F3RS41-0N
Send/receive
control
See Section 4.6
Setting Registers
F3RS22-0N RS
control
0 :
ER=OFF
1 :
ER=ON
1
16 S/C
F3RS41-0N
Send/receive
control
See Section 4.6
Setting Registers
17* S/C
DR
check
0
: transmits regardless of the state of DR
1
: transmits only when DR is ON
0
18* S/C
CD
check
0
: transmits regardless of the state of CD
1
: transmits only when CD is OFF
0
19* S/C
Transmission enabled
monitoring time
(DR control monitoring)
0
: no time-monitoring
1 to 32760 (ms)
0
Содержание F3RS22-0N
Страница 11: ...Blank Page...
Страница 15: ...Blank Page...
Страница 28: ...3 3 IM 34M6H21 01E 2nd Edition Aug 2001 00 External Dimensions Unit mm 83 2 28 9 2 12 1 100...
Страница 31: ...Blank Page...
Страница 59: ...Blank Page...
Страница 63: ...Appx 3 2 IM 34M6H21 01E 2nd Edition Aug 2001 00 Blank Page...
Страница 65: ...Blank Page...