Cmd 09
= DEVICE VARIABLES WITH
STATUS
•
Cmd 48
= ADDITIONAL
TRANSMITTER STATUS
Choose the preferable burst mode, and push
menu button to confirm.
7.
Select
Period
, and push the menu button to
confirm.
Two choices appear on the screen:
Max Time
and
Min Time
•
Select
Max Time
to set the maximum
amount of time when the message will
be sen
t
. This value can be set from 0.5
to 3600 seconds.
•
Select
Min Time
to set the minimum
amount of time when the message will
be send. This value can be set from 0.5
to 3600 seconds.
Enter the preferred value, and push the menu
button to confirm.
8.
Select
Trigger
, and push the menu button to
confirm.
9.
Five choices appear on the screen:
Continuous
= The Burst message is send
continuously.
Windowed
= The Burst message is triggered
when the measured value deviates more than
the specified trigger value.
Rising
= The Burst message is triggered when
the measured value rises above the triggered
value.
Falling
= The Burst message is triggered
when the measured value falls below the
triggered value.
On-Change
= The Burst message is triggered
when any value in the measuring changing.
Choose the desired burst mode, and set the
preferred parameters.
6.11 Information
This menu summarizes information
about the configuration of the
transmitter.
Below the contents of the information screen.
V No:
Software Version number
No:
Serial number of the transmitter
Z:
Zero adjustment
S:
Span adjustment
Da:
Out delay on display
O:
Output (4-20 mA or 20-4 mA)
Lpro:
Local protection (on/off)
Tunit:
Temperature unit (°C or °F)
Tph:
Highest measured process temperature
Tpl:
Lowest measured process temperature
Tah:
Highest measured ambient temperature
Tal:
Lowest measured ambient temperature
Tc no:
Tag number
<6. Explanation Programming Points>