IM 01C25T03-01E
3-12
3. OPERATION
a. Setting Password
(D57: NEW PASSWORD)
Enter
1234ABCD
.
Then status of parameter D55:
WRT PROTECT becomes YES.
F0340.EPS
• Example: Set the password to 1234ABCD.
SET
D57:NEW PASSWORD
1234ABCD
CODE
CAPS
CLR
ESC
SET
D57:NEW PASSWORD
1234ABCD
FEED
NO
OK
Press the key twice
to enter the setting.
Press the (OK) key.
b. Entering Password to Enable Parameter
Change (D56: WRT ENABLE)
Enter the password.
Parameter changes are available
for 10 minutes.
F0341.EPS
• Example: Enter the password of 1234ABCD.
SET
D56:WRT ENABLE
1234ABCD
CODE
CAPS
CLR
ESC
SET
D56:WRT ENABLE
PASS
FEED
NO
OK
Press the key twice
to enter the setting.
Press the (OK) key.
c. Releasing Password
(D57: NEW PASSWORD)
To release the password, enter eight spaces at D57:
NEW PASSWORD during the period that the param-
eter change is possible.
d. Software Seal
(D58: SOFTWR SEAL)
When you lose the password that has been registered, it
is possible to release the write protect function by
using general password, “YOKOGAWA.” When the
password is used, the status shown in the parameter of
D58: SOFTWR SEAL is changed from
KEEP
to
BREAK
. The status returns to
KEEP
by entering a
newly set password at D56: WRT ENABLE.
(12) Output Status Setup when a Hardware
Error Occurs (D26: ERROR OUT)
This parameter allows the setting of the output status
when a hardware error occurs. The following selections
are available.
(a) BURNOUT DIR; Outputs the corresponding values
of 110% or –5% of output signals according to the
setting by burnout direction switch (BO) on the
CPU board.
(b) HOLD; Outputs the last value held before the error
occurred.
Note: A hardware error means CAP.ERR of AL.01 or AMP.ERR of
AL.02 which are shown in table 4.2 Alarm Message
Summary.
• Example: Set the output status to
HOLD
when
a hardware error occurs.
ESC
SET
D26:ERROR OUT
BURNOUT DIR
< BURNOUT DIR >
< HOLD >
Use the or key
to select
HOLD
.
Press the key twice to
enter the setting.
F0326.EPS
Then press the (OK) key.
(13) Bi-directional Flow Measurement Setup
(E30: BI DIRE MODE)
(a) This parameter enables selection of 50% output at
an input of 0 kPa.
Procedure is shown in the figure below.
(b) Combining this with
C40: OUTPUT MODE
provides a square root output computed indepen-
dently for 0% to 50% output and for 50% to 100%
output.
• Example: If measurement range is 0 to 10 kPa
(LRV=0 kPa, URV=10 kPa)
The measurement range changes to –10 to 0 to 10 kPa
(output 0% to 50% to 100).
Note that
C21: PRES LRV
and
C22: PRES URV
are not changed.
ESC
SET
E30:BI DIRE MODE
OFF
< OFF >
< ON >
Use the or key
to select
ON
.
Press the key twice to
enter the setting.
F0327.EPS
Then press the (OK) key.