<5.  Parameter Summary>

5-3

IM 01C25T03-01E

No. Parameter name

Item

*1

R/W

Content

Default value

Applicable 

model

Upload data

F

P

L

G

ALARM SET

Alarm setting

G10 P AL MODE

Alert mode 

W INHIBIT, HI. AL DETECT, LO. 

AL DETECT, or HI/LO. AL 

DETECT

INHIBIT

G11 P HI. AL VAL

High side alert value

W -32000 to 32000, unit 

specified in C20

100.000 kPa

G12 P LO. AL VAL

Low side alert value

W -32000 to 32000, unit 

specified in C20

-100.000 kPa

G20 SP AL MODE

Static pressure alert mode

W INHIBIT, HI. AL DETECT, LO. 

AL DETECT, or HI/LO. AL 

DETECT

INHIBIT

G21 SP HI. AL VAL

High side alert value of SP*

2

W -32000 to 32000, unit 

specified in D30

G22 SP LO. AL VAL

Low side alert value of SP

W -32000 to 32000, unit 

specified in D30

0.00000 MPa

G30 T AL MODE

Temperature alert mode

W INHIBIT, HI. AL DETECT, LO. 

AL DETECT, or HI/LO. AL 

DETECT

INHIBIT

G31 T HI. AL VAL

High side alert value of 

temperature

W -50 to 130

120 degC

G32 T LO. AL VAL

Low side alert value of 

temperature

W -50 to 130

-40 degC

G50 AUTO RECOVER Auto-recover from sensor error

W OFF or ON

ON

G60 SELF CHECK

Self-diagnostics

R

See A60

H

AUTO SET

Automatic setup

H10 AUTO P LRV

Lower range value auto setup

W -32000 to 32000, unit 

specified in C20

As specified

H11 AUTO P URV

Upper range value auto setup

W -32000 to 32000, unit 

specified in C20

As specified

H20 AUTO SP LRV

SP lower range value auto 

setup

W -32000 to 32000, unit 

specified in D30

0.00000 MPa

H21 AUTO SP URV

SP upper range value auto 

setup*

2

W -32000 to 32000, unit 

specified in D30

H60 SELF CHECK

Self-diagnostics

R

See A60

I

DISP SET

Display setting

I10

DISP OUT1

LCD output 1

W PRES, PRES %, ENGR. 

PRES, SP, or SP %

PRES %

I11

DISP OUT2

LCD output 2

W PRES, PRES %, ENGR. 

PRES, SP, SP %, or ---

---

I12

DISP OUT3

LCD output 3

W See I11

---

I13

DISP OUT4

LCD output 4

W See I11

---

I20

P DISP MODE

% display mode

W LINEAR or SQUARE ROOT

LINEAR

I21

PRES % RESO

% display resolution

W NORMAL or HIGH 

RESOLUTION

NORMAL

I30

ENGR. UNIT

User set engineering unit

W 8 alphanumeric characters

I31

EASY EU SET

Engineering unit select

W

I32

ENGR. EXP

Exponents

W ---, ×10, ×100, ×1000

---

I33

ENGR. LRV

User set lower range limit

W -32000 to 32000, unit 

specified in I30

0.00

I34

ENGR. URV

User set upper range limit

W -32000 to 32000, unit 

specified in I30

100.00

I35

ENGR. POINT

Decimal place of user set

W 0 to 4

1

I40

BAR INDICATR

Bar indicator

W OFF or ON

ON

I41

POWER ON INF

Display when powering on

W OFF or ON

ON

I60

SELF CHECK

Self-diagnostics

R

See A60

*1:   R/W: R = Read only, W = Read & Write

*2: 

The default value shows MWP (Maximum working pressure) of the capsule. 

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.

*3: 

This function cannot be used for V capsule.

*4: 

This parameter may contain the adjustment value at factory upon shipment. If executing J56 “CLEAR ADJ”, the value of J15, J16, 

J40 and J41 will become 0, and value of J11 and J12 will become the value of PRES LRV and PRES URV respectively.

Содержание DPharp Series

Страница 1: ...User s Manual DPharp BRAIN Communication Type EJX A EJA E IM 01C25T03 01E IM 01C25T03 01E 8th Edition...

Страница 2: ...unctions 3 1 1 Alphanumeric Keys and Shift Keys 3 1 2 Function Keys 3 2 3 1 3 Calling Up Menu Addresses Using the Operating Keys 3 3 3 1 4 Printout for BT200 printer option 3 3 1 Printout of All Param...

Страница 3: ...n code AL 3 20 20 Capillary Fill Fluid Density Compensation 3 21 21 Adjustment Information and User Memo Fields 3 22 3 3 Displaying Data Using the BT200 3 22 3 3 1 Displaying Measured Data 3 22 3 3 2...

Страница 4: ...be done after completing the range setting Regarding This Manual This manual should be provided on to the end user The contents of this manual are subject to change without prior notice All rights res...

Страница 5: ...revent the inhalation of harmful vapors and the contact of toxic process fluids with the skin or eyes When removing the instrument from a hazardous process avoid contact with the process fluid and the...

Страница 6: ...cost of fixing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa The purchaser shall bear the responsibility for repair costs even during the warranty period...

Страница 7: ...nded to install a low pass filter approximately 0 1s Connection to the transmitter with the BT200 can be made by either connecting to the BT200 connection hooks in the transmitter terminal box or by c...

Страница 8: ...splay When Powering On For models with the integral indicator code D the display shows all segments in the LCD and then changes to the displays shown below sequentially All segments display Model name...

Страница 9: ...on the upper system 3 1 BT200 Operating Procedures 3 1 1 Key Layout and Screen Display Figure 3 1 shows the arrangement of the operating keys on the BT200 keypad and figure 3 2 shows the BT200 screen...

Страница 10: ...e cursor Entry l m Key in Sequence F0307 ai m I symbol command 2 Function Keys The function command carried out by each function key is displayed directly above the key MENU A DISPLAY B SENSOR TYPE C...

Страница 11: ...SET HOME SET ADJ ESC MENU C BASIC SETUP D AUX SET 1 E AUX SET 2 G ALARM SET H AUTO SET I DISP SET HOME SET ADJ ESC MENU J ADJUST K TEST M DEVICE INFO P RECORD T CHARACTERIZR DATA DIAG PRNT ESC DATA D...

Страница 12: ...t Reverse mode is used for applications in which safety requires that output be driven toward 20 mA if input is lost Impulse line connection orientation higher pressure on right left side setup P 3 11...

Страница 13: ...35 ENGR POINT I40 BAR INDICATR I41 POWER ON INF 3 I60 SELF CHECK J09 ADJ UNIT J10 ADJ PRES J11 P ZERO ADJ J12 P SPAN ADJ J15 P ZERO DEV J16 P SPAN DEV J20 ADJ SP 1 J21 SP ZERO ADJ 1 J22 SP SPAN ADJ 1...

Страница 14: ...FICOGAWA FIC GAWA FIC 1AWA FIC 1aWA FIC 1a Set TAG NO and press the key SET C10 TAG NO YOKOGAWA FIC 1a _ CODE caps CLR ESC Example Set a Tag No to FIC 1a SET C10 TAG NO FIC 1a FEED NO OK DATA DIAG PR...

Страница 15: ...s the upper range value keeping the span constant Example 1 With present settings of 0 to 30 kPa set the lower range value to 0 5 kPa Span Upper range value Lower range value FEED NO OK SET C21 PRES L...

Страница 16: ...ified in the order when the instrument is shipped Follow the procedure below to change the mode If the instrument is equipped with an integral indicator and the display mode is SQUARE ROOT is displaye...

Страница 17: ...oint 7 2mA 20 6 Integral Indicator Scale Setup The following five displays are available for integral indicators input pressure 1 of range user set scale input static pressure and of static pressure r...

Страница 18: ...d a slash can be input on keypad at I30 ENGR UNIT only first six are displayed on the integral indicator Select the unit from the list of I31 EASY EU SET kPa MPa mbar bar psi psia mmH2O mmHg mmHgA mmA...

Страница 19: ...temperature Example Change the unit for the temperature display degC to degF ESC SET D40 TEMP UNIT degC degC degF K Use the or key to select degF Press the key twice to enter the setting F0324 ai Then...

Страница 20: ...RT ENABLE D57 NEW PASSWORD Transmitter configured data can be saved by the write protect function Write protect status D55 WRT PROTECT is set from NO to YES when eight alphanumerics are entered in the...

Страница 21: ...lue held before the error occurred Note A hardware error means CAP ERR of AL 01 or AMP ERR of AL 02 which are shown in table 4 1 Alarm Message Summary Example Set the output status to HOLD when a hard...

Страница 22: ...e present setting of 0 to 30 kPa take the following action with an input pressure of 10 kPa applied FEED NO OK SET H11 AUTO URV 10 000 kPa DATA DIAG PRNT ESC PARAM H10 AUTO P LRV 0 kPa H11 AUTO P URV...

Страница 23: ...re by using the pressure unit a 1 Zeroing Setting the parameter J11 P ZERO ADJ carries out the zero adjustment and automatically sets the applied 0 input values to the transmitter s output value of ze...

Страница 24: ...ustment should always be performed before the upper point adjustment in order to maintain the pitch between the zero and 100 points within the calibration range In the manual method the reference pres...

Страница 25: ...ss the OK key Applied Pres Value Measured Pres Value Applied Pres Value Slope Error URV LRV 30 00 30 15 30 00 30 00 10 00 0 1 c Sensor Trim for Static Pressure J21 SP ZERO ADJ J22 SP SPAN ADJ J25 SP Z...

Страница 26: ...hour by the parameter K45 TEST TIME Default value Press the OK key to release test output immediately 17 Signal Characterizer This function is used to compensate the output for non linear applications...

Страница 27: ...exceeds the specified value within the calibration range The same is available for the input static pressure and the capsule temperature on the pressure sensor Refer to table 4 1 Alarm Message Summar...

Страница 28: ...as been defined for a CPU failure or hardware error Use a 4 20 mA signal to indicate a transmitter s failure Example Set the status output to output an off signal when the input pressure exceeds 75 kP...

Страница 29: ...m diaphragm seal high side to position of transmitter low side Transmitter L h 0 H EJX118A EJA118E F0353 ai h h L L H Transmitter Transmitter 0 EJX438A EJA438E Note When the transmitter is positioned...

Страница 30: ...matically every seven seconds In addition the display can be updated to the present data value at any time by pressing the DATA key For parameters associated with the display of measured data see chap...

Страница 31: ...rors can be stored When the 5th error has occurred it is stored in P10 The error stored in P16 will be deleted and then the error in P14 will be copied to P16 In this sequence the history of the most...

Страница 32: ...problem AL 10 PRESS 10 P OVER SPEC Input is outside measurement range limit of capsule Outputs upper range limit URL or lower range limit LRL Check input or replace capsule when necessary AL 11 ST PR...

Страница 33: ...settings and change them as needed 53 P ZERO ADJ AL 54 SP RNG 54 SP ILLEG LRV Continues to operate and output holding static pressure in Check settings and change them as needed 54 SP ILLEG URV 54 SP...

Страница 34: ...specified in C20 B30 SP LRL Lower range limit for static pressure R Unit specified in D30 B31 SP URL Upper range limit for static pressure R Unit specified in D30 B32 SP MIN SPAN Minimum span for stat...

Страница 35: ...LOW HIGH D40 TEMP UNIT Temperature setting unit W degC degF or K degC D50 QUICK RESP Quick response W OFF or ON enable 0 00 to 0 50 seconds at C30 OFF D55 WRT PROTECT Write protect indicator R NO or...

Страница 36: ...nit specified in D30 0 00000 MPa H21 AUTO SP URV SP upper range value auto setup 2 W 32000 to 32000 unit specified in D30 H60 SELF CHECK Self diagnostics R See A60 I DISP SET Display setting I10 DISP...

Страница 37: ...tment information W 8 alphanumeric characters J53 ADJ DESC Adjustment information W 16 alphanumeric characters J55 EXT ZERO ADJ External zeroing permission W INHIBIT or ENABLE ENABLE J56 CLEAR ADJ Cle...

Страница 38: ...f Y R 0 00 T22 X1 Coordinate 1 of X W 0 00 to 100 00 10 00 T23 Y1 Coordinate 1 of Y W 0 00 to 100 00 10 00 T24 X2 Coordinate 2 of X W 0 00 to 100 00 20 00 T25 Y2 Coordinate 2 of Y W 0 00 to 100 00 20...