2. Transportation, Storage and Installation
2-26
TI 33Q01J10-01E
Isolation from Rack
Isolate the rack mountable devices from the rack by attaching isolation bushings. Fasten a
pair of isolation bushings together to each of the screw holes on the plate or the bracket on the
devices to prevent the devices from touching the rack, and then screw the devices to the rack.
After screwing the devices to the rack, confirm that the devices are electrically isolated. Isolation
bushings are supplied with the rack mountable devices.
CAUTION
When you install the ‘devices with isolation bushings attached’ on a rack or an instrument panel,
do not keep the devices hung on loose screws in an unstable status. Too much force may apply
to the isolation bushings and cause damaged or broken isolation bushings.
Installation Procedure
1. Fasten a pair of isolation bushings together to each of the screw holes on the plate or the
bracket on the device. The tapering end of the isolation bushings must come to the front
side where a screw enters.
2. Using eight M5 screws to fix the device onto the rack or the panel.
F020413.ai
Input/output module slots
Power supply
module
Processor
module
Cable tray
Using grounding terminal to
connect the base unit to earth
(less than 100 ohm). Make the
grounding cable to pass through
the tray and pull it down along
the right side of the racks.
M5 screws (8 pieces)
M5 screws
Attach isolation to both
sides of the plate.
How to install isolation bushings
Rack
Rack
Isolation
bushing
(with a tapering)
Isolation
bushing
Plate
(front)
Isolation bushings (8 pieces)
Plate
Base unit
Figure Example of Mounting FFCS on a Rack
Sep. 30, 2008-00