<2. INTRODUCTION TO BT200>

IM 01C00A11-01E

2.1 WHAT THE BT200 CAN DO

The BT200 offers the following exclusive features:

Feature

Description

Turns on the BATTERY indicator when 
the battery voltage falls.
Switches off the BT200 automatically 
when no key access is made for five 
minutes or longer.
Sets a security code to protect setup 
parameters.
Entering the correct security code 
permits alterations to the setup 
parameters.
The BT200 is shipped without a 
security code set so, you can alter the 
setup parameters without having to 
enter a security code.
(Upload to the BT200)

Records the setup data on the 
BRAIN instrument connected to the 
BT200 into the BT200 s memory in a 
batch.

Low-voltage alarm

Autopower-off

Security code-based 
setup protection

Upload/download

T0201.EPS

(Download to the instrument)

Writes uploaded data to another 
BRAIN instruments, but not to one 
having a different model name.

Supports seven modes of printout, 
including listing of all parameters and 
listing of downloaded data.
Sets an identification code for the 
BT200.
Supports both English and Japanese 
versions of operational messages. 
The BT200 is shipped with the 
message mode set to English.
Permits controlling the LCD contrast 
through startup and utility panels.
Permits controlling the printout density 
through a utility panel. the print density 
level can be visually verified from test 
printout.

Printout

ID (identification 
code) setup
Language selection 
(between English and 
Japanese)

LCD contrast control

Print density control

Содержание BT200

Страница 1: ...User s Manual Y okogawa Electric Corporation BRAIN TERMINAL Model BT200 BRAIN TERMINAL IM 01C00A11 01E 5th Edition Advanced Test Equipment Rentals www atecorp com 800 404 ATEC 2832 Established 1981...

Страница 2: ...tion Dec 2005 KP All Rights Reserved Copyright 1994 Yokogawa Electric Corporation INTRODUCTION 1 1 PRECAUTIONS 1 1 1 1 CHECK THE CONTENTS OF THE PACKAGE 1 1 1 2 PRECAUTIONS IN HANDLING 1 2 2 INTRODUCT...

Страница 3: ...s manual at the time the changes are made provided that postponement of revisions will adversely affect functional or performance Please keep the above in mind when using this manual If a problem aris...

Страница 4: ...are thoroughly tested at the factory before shipment When the BT200 units are delivered visually check to make sure that no damage occurred during shipment Also check that the specifications are as sp...

Страница 5: ...m condensation Do not leave the unit exposed to direct sunlight for an extended period of time The LCD liquid crystal display may appear dark or the unit may be disabled due to loss of the battery cap...

Страница 6: ...the model with printer printed characters may become faint when batteries except alkali type are used b Duration of continuous operation When running the unit from alkali batteries 50 hours least if...

Страница 7: ...1 4 Toc Ind 1 PRECAUTIONS IM 01C00A11 01E 5 EMC CONFORMITY STANDARDS EN61326 AS NZS CISPR11...

Страница 8: ...ay communica tion Working as a master the BT200 Permits 1 Setting and changing parameters for the BRAIN instrument 2 Monitoring PV and MV values and self check information on the BRAIN instrument and...

Страница 9: ...the BT200 s memory in a batch Low voltage alarm Autopower off Security code based setup protection Upload download T0201 EPS Download to the instrument Writes uploaded data to another BRAIN instrumen...

Страница 10: ...rallel wiring Display LCD dot matrix 21 characters 8 lines Controls Membrane switches four function keys 20 general operation keys and one power switch Printer BT200 P00 Thermal paper type Power Suppl...

Страница 11: ...nal With no printer With printer Always 00 BT200 Printer Options Suffix codes N P 00 OPTIONS Item Description T0203 EPS for SC Signal conditioner Applicable only for model BT200 N00 See Appendix B Cod...

Страница 12: ...Toc Ind 2 INTRODUCTIONTO BT200 2 5 IM 01C00A11 01E 2 3 COMPONENT NAME Fuigure 2 3 Component Name...

Страница 13: ...2 6 Toc Ind 2 INTRODUCTIONTO BT200 IM 01C00A11 01E 2 4 DIMENSIONS Fuigure 2 4 Dimensions...

Страница 14: ...he dedicated communication cable into the BT200 adjust the up arrow mark on the cable to the mark on the BT200 connector and push the cable into position until a click sounds Note You cannot plug the...

Страница 15: ...connect as shown in Figure 3 2 a using the BRAIN TERMINAL cable with IC clips Polarities are marked on the terminal box pins and on the BRAIN TERMINAL cable however no damage will occur if they are c...

Страница 16: ...r communication card or EXT extension card is provided with a BRAIN TERMINAL connector see Figure 3 2 b A 5 pin connector cable for the BRAIN TERMI NAL is supplied when the BRAIN TERMINAL comes with C...

Страница 17: ...selected items Sets up input data on the connected instrument Runs BT200 functions Function keys Use to execute the commands displayed at the bottom of the screen PARAM A10 OUTPUT 100 0 A11 ENGR OUTP...

Страница 18: ...keys a Entering Digits Symbols and Spaces 0 to 9 Simply press the alphanumeric keys 4 0 3 F0403 EPS Entry Key in Sequence b Entering letters A through Z Press an alphanumeric key following a shift key...

Страница 19: ...2 CAPS Entry Boy Key in Sequence F0406 EPS CODE CAPS CLR ESC Entering uppercase CODE caps CLR ESC Entering lowercase B y o to lower case Use the function key F1 CODE to enter symbols The following sym...

Страница 20: ...Quits setup and returns to the previous display Proceeds to the next panel Enters the parameter number setup mode Displays the SET menu Returns to the slot selection panel Calls the utility panel CAPS...

Страница 21: ...1 TABC 101 F0409 EPS DATA DIAG PRNT ESC DATA DIAG PRNT ESC PARAM C60 SELF CHECK GOOD PARAM C12 HIGH RANGE 1000 mmH2O C30 AMP DAMPING DATA DIAG PRNT ESC PARAM C10 TAG NO TABC 101 C20 PRESS UNIT mmH2O C...

Страница 22: ...eference to online communica tion with DPharp for example For the BT200 N00 the function commands marked by a corrugated line and the messages marked by an asterisk are not displayed 1 TURN THE POWER...

Страница 23: ...NO TABC 101 03 SELF CHECK GOOD OK POWER SWITCH ON STARTUP PANEL Plug the cable into the instrument and press ENT F1 UTIL Call a utility panel See Section 5 3 F2 FEED Paper feed BT200 P00 If connected...

Страница 24: ...splays the menu panel F2 SET Displays the SET menu panel F3 ADJ Displays the ADJ menu panel F4 ESC Returns the command panel ENT Enters selected menu choice DPharp If the menu choices are blocked as w...

Страница 25: ...E 1000 mmH2O C30 AMP DAMPING 2 0 SEC C40 OUTPUT MODE OUT LIN DSP LIN DATA DIAG PRNT ESC PARAM C10 TAG NO TABC 101 C20 PRESS UNIT mmH2O C21 LOW RANGE 0 mmH2O DATA DIAG PRNT ESC MENU J ADJUST K TEST M M...

Страница 26: ...NTER ADJUST esc UTILITY 1 ID 2 security code 3 MESSAGE MODE 4 LCD CONTRAST 5 PRINTER ADJUST MENU PANEL UTILITY PANEL Type 3 Type K Helpful hint 2 Following procedure allows you to make a direct select...

Страница 27: ...s shown on panel 3 1 Number of the starting parameter on the panel before the last Number of the starting parameter on the previous panel 3 3 3 4 c Call the self check panel Press F2 DIAG on a paramet...

Страница 28: ...Current TABC 101 EJ aH01 If you have set a security code you must enter the security code See section 4 SETUP PANEL 1 Select the parameter to change with or and press ENT F0417 2 EPS E J a F3 NO F2 PO...

Страница 29: ...t a security code you must enter the security code See section 4 SETUP PANEL 1 Select the parameter to change with or and press ENT 2 Select the setup data with or and press ENT twice to complete the...

Страница 30: ...ded until you switch off the BT200 F0419 EPS PARAM C10 TAG NO TABC 101 C20 PRESS UNIT mmH2O C21 LRV 0 mmH2O DATA DIAG PRNT ESC SECURITY ID BT200 SECURITY CODE _ CLR ESC SET C10 TAG NO TABC 101 TABC 10...

Страница 31: ...individual instrument and reduces the chances of improper settings This function does not apply to certain instruments such as signal conditioner cards 1 COPY TO THE BT200 IN A BATCH UPLOAD First it...

Страница 32: ...yed while the transfer is in progress 4 5 5 The transfer is complete when panel appears 4 5 Because the data is written to the BT200 s nonvolatile memory it is preserved intact even when the terminal...

Страница 33: ...to execute a download DNLOAD communi MODEL EJ110 DM DOWNLOADING please wait DNLOAD MODEL EJ110 DM DOWNLOAD complete F3 print data PRNT ESC 4 A download is executed and a transfer starts Panel is displ...

Страница 34: ...a list of self check information such as error information designated by the DIAG key Uploaded data list prints out data after it has been uploaded Downloaded data list prints out data after it has be...

Страница 35: ...PY LIST ESC Sample printout 1 3 PRINTING ALL PARAMETERS FROM A MENU CHOICE PARAM A10 OUTPUT 100 0 A11 ENGR OUTPUT 1000 mmH2O A20 AMP TEMP 23 deg C DATA DIAG PRNT ESC F0506 1 EPS PARAM A10 OUTPUT 100 0...

Страница 36: ...ME SET ADJ ESC F0507 1 EPS 1 Connect the BT200 to the other instrument and make it ready for communication Press F4 ESC on the menu panel to call panel 1 2 F0507 2 EPS FUNC 1 MENU 2 UPLOAD TO HHT 3 DO...

Страница 37: ...OAD UPLOAD data printing please wait F4 STOP printing STOP 3 The message UPLOAD data printing please wait is displayed while the printing is in progress Press F4 STOP to cancel printing The message PR...

Страница 38: ...el 2 Press F3 PRNT to start printing 1 2 DIAG C60 SELF CHECK ERROR ERROR OUT OF RANGE OVER SENS TEMP OVER OUTPUT FEED PRNT ESC 1 F1 FEED F3 PRNT F4 ESC Paper feed Print out self check information Retu...

Страница 39: ...t new ID _ CODE CAPS CLR ESC F0511 EPS 1 Select 1 ID from the utility panel to call panel Type the new ID and press ENT twice 1 1 2 LANGUAGE SELECTION BETWEEN ENGLISH AND JAPANESE a English to Japanes...

Страница 40: ...el in Japanese 1 2 3 4 3 2 Select and press ENT to go to panel 3 Select and press ENT to go to panel for confirmation 2 F0515 2 EPS F3 NO F4 OK Return to panel Go to panel 4 UTILITY 1 ID 2 SECURITY CO...

Страница 41: ...the utility panel and press ENT to select the LCD contrast control panel Use or to control the LCD contrast When finished press ENT to set the BT200 to the specified LCD contrast level 4 PRINT DENSIT...

Страница 42: ...To replace the batteries follow these steps 1 Switch off the BT200 2 Using a Phillips screwdriver remove three screws on the back of the unit and detach the battery case Be careful not to lose the scr...

Страница 43: ...6 2 Toc Ind 6 MAINTENANCE IM 01C00A11 01E Manufacture Model Type Voltage DURACELL MN1500 Alkaline 1 5 V PC1500 manganese Figure 6 1 a Removing Screws...

Страница 44: ...ll paper into part A The roll paper has its face and back Insert the roll paper to face as shown in Figure 6 2 4 Push in the roll paper until its end comes out of part B When the roll paper comes out...

Страница 45: ...m 4 Details of the problem 5 Checks made and the results 6 Other related information NO MODEL F0701 EPS Figure 7 1 The Nameplate 1 PRESSING THE KEY PRODUCES NO DISPLAY 1 Did you press the key positive...

Страница 46: ...rrent output circuit of the connected instrument If you are using our distributor to power the connected instrument a reception resistor is built in it 4 Does the wiring distance of the current output...

Страница 47: ...Toc Ind 7 TROUBLESHOOTING 7 3 IM 01C00A11 01E Figure 7 2 Connector pin numbers Figure 7 3 Wiring...

Страница 48: ...A SETTING A SECURITY CODE To register a security code in the BT200 as shipped follow these steps SECURITY new SECURITY CODE _ CODE clear mode CLR ESC F0A01 EPS SECURITY new SECURITY CODE re enter new...

Страница 49: ...press ENT to complete the procedure If you type a different code the message incorrect CODE set CODE again is displayed Retry from Step 2 downward 1 2 3 UTILITY 1 ID 2 SECURITY CODE 3 LANGUAGE SELECT...

Страница 50: ...SECURITY CODE _ CLR ESC F0A04 EPS SECURITY new SECURITY CODE _ CLR ESC SECURITY new SECURITY CODE re enter new CODE _ CLR ESC 1 Call security panel and type RSET 2 Type a new security code and press...

Страница 51: ...rature 15 to 55 C Electrical Parameters BT200 Intrinsically Safe Apparatus Parameters The Maximum Input Voltage Vmax in 30V The Maximum Input Current Imax in 165mA The Maximum Input Power Pmax in 0 9W...

Страница 52: ...ertified by CSA Associated apparatus manufacturer s installation drawing must be followed when installing these intrinsically safe apparatuses Not a warning label worded SUBSTITUTION OF COMPONENTS MAY...

Страница 53: ...1 2 5 EMC CONFORMITY STANDARDS Add optional code CS1 Subsection 2 2 Error correction FUNCTION COMMAND LIST Add CAUTION FOR INTRINSICALLY SAFE TYPE Subsection 6 1 Add Appendix B Installation of CSA In...

Отзывы: