2

IM 77M02D01-01EN

3rd Edition 

Apr. 01, 2022-00

1.3 Terminal 

Arrangement

 

Protect-side 
terminal

Surge-side 
terminal

A
B

C

1
2
3

+

í

Not Connected

+

í

Not Connected

Grounding

terminal

A

C

B

1

2

3

1.4 Wiring

 NOTE

Use of arresters ignoring the speci

fi

 cations may cause 

electric shock, overheating or damage.
1.  Input signal value applied to the arrester should 

meet the required speci

fi

 cations.

2.  The external wiring to the terminals and wiring to 

ground are as speci

fi

 cations.

Flexible twisted wire and durable round crimp-on terminal (JIS C 
2805) are recommended to use.
(1) Signal cable
 

Nominal cross-sectional area of conductor: 0.5 to 0.75 mm

2

.

 

Example of suitable cable:  Vinyl code (VJF) (JIS C 3306) for 

electronic instrument.

(2) Grounding cables
 

Nominal cross-sectional area of conductor: 2.0 mm

2

 or more 

for grounding.

 

Example of suitable cable:  600V vinyl insulated cable (IV) 

(JIS C 3307), Vinyl insulated cable 
(KIV) (JIS C 3316) for electronic 
instrument

1.5 Grounding

 

 

 

 

 

 

 

 

 

 

 

 NOTE

Wire tightening torque for arrester should not be 1.2 
N•m or more.

   

(1) Interconnect Grounding (2) Interconnect Grounding

 

(when using shield line)

Arrester

Instrument

Arrester

Instrument

Apply the grounding system which is 
defined by the rules and standards 
of the country or the region.

Short bar
(for grounding terminal connection)

Grounding for serial installation of 
arresters is to connect grounding 
terminals of neighboring arresters to 
each other and touch ground at one 
point from last arrester according.

Make sure to earth ground the ground terminal through minimum resistance.

2.  

CONNECTION OF ARRESTERS WITH 

INSTRUMENTS TO BE PROTECTED

   

Convertor

RTD

AR-RT

AR-RT

A

C

1

3

1

B

2
3

A

2

B

C

GND

Ground Terminal

Ground Terminal

A

B

B

Lightning

Surge

Protect side

Protect side

Surge side

Potentiometer

100%

0%

3. ENVIRONMENTAL 

CONDITIONS

Ambient temperature: 

10 to +60°C

Relative humidity:

5 to 90% RH (No condensation)

Altitude at installation site: Max. 2000 m above sea level
Installation category based on IEC/EN61010-1: II, pollution 
degree: 2 (see Note.)

 NOTE

The “Installation Category” implies the regulation for
impulse withstand voltage. It is also called the 
“Overvoltage category”.“ II ” applies to electrical 
equipment.“Pollution level” describes the degree 
to which a solid, liquid or gas which deteriorates 
dielectric strength is adhering.“2” applies to a normal 
indoor atmosphere.

4. MANTENABCE

4.1 Arrester 

Checking

The arrester main body and terminal base are connected by plug-
in. Circuit between surge side and protect side would not be open 
even if the main body is removed from the socket on terminal 
base by loosing main unit-

fi

 xing screw. To check the arrester 

performance, remove the main body from the socket and check 
it by using the AR2-CK (arrester checker: option). If the arrester 
cannot be used because the main body is deteriorated or broken, 
be sure to replace both the main body and the terminal block. 
The terminal block may be damaged by receiving surges. The 
replacement of only the main body may fail to meet its protection 
performance level.

4.2  Arrester check period

To protect the instrument from damage by induced lightning, the 
arrester should be checked periodically at least once a year. In 
areas where lightning occurs frequently, check should be done 
more often particularly after thunderstorms.

5. HARDWARE 

SPECIFICATION

Use

RTD/Potentiometer

*

Maximum continuous 
operating voltage (Uc)

Between lines

8 V DC

Between ground 40 V DC

Permissible current 
leakage

Between lines

μ

A or less (at 8 V DC)

Between ground 2 

μ

A or less (at 40 V DC)

Instrument side voltage 
limit (10 kV, 1.2/50 

μ

A)

Between lines

30 V or less

Between ground 250 V or less

*

Voltage protection 
level (Up)

Between lines

150 V or less

Between ground 350 V or less

*

Impulse durability
(8/20 

μ

A)

Category C1

500 A

Category C2

5000 A

Discharge starting 
voltage

Between lines

20 V DC or more

Between ground 74 V DC or more

*

Rated current

2 A DC

JIS compliant

JIS C 5381-21 (Category: C1, C2)

*: Description compliant with JIS C 5381-21.