<5. Functions>
79
IM 01E21A02-03EN
5.3.2 Connection of Contact Point Output to DI Function
The contact point outputs at STB and DTB are output to specific channels, respectively. By
selecting the channel to use in the DI function block, it is connected to the contact point.
The relation of the channel for each contact point output and the channel which can be selected
from each DI function block is shown in the figure below.
DTB
STB
Velocity1 Hi/Lo Limit
Velocity2 Hi/Lo Limit
Volume1 Hi/Lo Limit
Adhesion1 Hi/Lo Limit
ElectrodeA2 Hi/Lo Limit
Flow Noise1 Hi/Lo Limit *
Adhesion Warning Status
Adhesion Alarm Status
Flow Noise Warning Status *
Channel 21
Channel 22
Channel 23
Channel 30
Channel 34
Channel 38
Channel 39
Channel 40
DI1
DI2
DI3
Volume2 Hi/Lo Limit
Channel 24
Mass1 Hi/Lo Limit
Channel 25
Mass2 Hi/Lo Limit
Channel 26
Calorie1 Hi/Lo Limit *
Channel 27
Calorie2 Hi/Lo Limit *
Channel 28
Adhesion2 Hi/Lo Limit
ElectrodeA1 Hi/Lo Limit
Channel 31
ElectrodeB2 Hi/Lo Limit
Channel 33
ElectrodeB1 Hi/Lo Limit
Channel 32
Flow Noise2 Hi/Lo Limit *
Channel 35
Conductivity1 Hi/Lo Limit *
Channel 36
Conductivity2 Hi/Lo Limit *
Channel 37
Flow Noise Alarm Status *
Low Conductivity Warning Status *
Channel 41
Channel 43
Channel 29
Channel 42
F0446.ai
* for AXG
Figure 5.3.2 Relation of Process Value of STB and DTB and DI Function Block
The information of the figure above can be organized below.
Table 5.3.1 List of Relation of Contact Point Output and DI Function Block
CHANNEL
number
Channel Selection
Model
Display
F
OUNDATION
Fieldbus
21
Velocity1 Hi/Lo Limit
Velo.1
AXG / AXW
22
Velocity2 Hi/Lo Limit
Velo.2
AXG / AXW
23
Volume1 Hi/Lo Limit
VolFlw.1
AXG / AXW
24
Volume2 Hi/Lo Limit
VolFlw.2
AXG / AXW