INSTALLATION OF REFRIGERANT PIPES

DIMENSIONS 

OF CONNECTING PIPES

Items

Gas Pipe (inch)

Liquid Pipe(inch)

 9000, 12000

3/8

1/4

18000

1/2

1/4

Capacity of indoor unit(Btu/h)

21000, 24000

5/8

Connecting to Indoor unit (I.D)

5/8

1/4

BU module

Connecting to Outdoor unit (I.D)

3/4

3/8

Outdoor unit

Between outdoor unit and the 1st branch

The pipe L1

Between the 1st and the 2nd branch

The pipe L2

WMMS-80CH-V2B(59)2 

WMMS-90CH-V2B(59)2 

CONNECTION OF BRANCH PIPES

If two or three BU modules used, Y-type branch pipe of  

 will be chosen

(59)2S-00-BranchY

(59)2S-00-BranchY-L1

(59)2S-00-BranchY-G1

Y-type branch pipe is equipped with auxiliary tubes to adjust the diameter of different pipes. If the dimension 
of the pipe selected is different from the dimension of branch pipe joint, Cut the copper tube in the middle 
with tube cutter and clear up burrs. Please do that as following figure.

Length (Ft.)

180

262

295

49

131

98

98

49

49

16

as possible as short

H1

H2

H3

H4

L1

L1+L2+L3+L4+L5

1A+1B+1C+2A+2B+2C+3A+3B

1A;1B;1C;2A;2B;2C;3A;3B

L4+1B;L2+L5+2A; L2+L3+3B

L3;L4;L5

The pipes

Between BU and the branch

Between outdoor and the 1st branch

Between indoor and indoor units

Between BU and BU modules

Between outdoor units and BU

Between outdoor and indoor units

Between indoor unit and the 1st branch

Between indoor unit and BU module

Between 

unit and BU

indoor 

WMMS-80CH-V2B(59)2 

WMMS-90CH-V2B(59)  

2

Between outdoor unit and BU

Items

Maximum allowable length

Maximum allowable length

Minimum allowable length

3/8

3/8

3/8

3/8

3/8

5/8

5/8

3/4

5/8

INST

ALLER'S 

INSTRUCTION

Inlet

Outlet

Cut the middle

Cut the middle

Inlet

Outlet

Cut the middle

Cut the middle

Cut the middle

P14 OF 32

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

INSTALLATION OF REFRIGERANT PIPES

Y-type branch pipe must be installed in vertical or horizontal direction. In the inlet of the branch pipe, keep 
at least 19.69inch straight pipe.

1) Pipe connections should be follow the following 
    rules:
* Outdoor unit shall be installed close to the indoor 
  unit, hence to minimize the length and bends of 
  connection pipes.
* The gap of outdoor unit and indoor units should be 
  as small as possible.
* The bending diameter of the pipeline is better as 
  large as possible.

PRECAUTION FOR CONNECTION

2) The brazing operation must be strictly in 
    accordance with the process requirements. During 
    the installation, do not damage the pipeline and 
    the bending diameter must be greater than 200mm.
3) The connection pipe cannot often be bent or 
    straightened. Otherwise it will harden.

4) The elbow operation must use the elbow. 
    Otherwise, the pipe may be cracking.

5) The process of flaring
* Using the tube cutter cutting the connecting pipe in 
    the middle and remove the burrs.
* Install the nut before the flaring operation.
* Check the flared portion, whether there is fractured 
    or not.
6) The following table for the torque required to 
    tighten the nuts.

Pipe diameter(inch) Wall thickness(inch) Tightening torque(N.m)

0.25

0.02

15~30

0.375

0.03

30~40

0.5

0.04

45~50

0.625

0.04

60~65

0.75

0.04

70~75

7) Align the flared end of copper tube with the center 
    of pipe joint. Tighten the nuts with hands.

8) Tighten the flaring nuts with torque wrench until 
    you hear a "click".

9) After all the refrigerant installation has been done, 
    use nitrogen to carry out gas leak check.

* During the connection of the indoor unit or BU 
   module to the refrigerant pipe, never pull any joints 
  of the indoor unit or the BU module by force; 
  otherwise the capillary pipe or other pipe may crack, 
  which then would result in leakage.
* The refrigerant pipe should be supported by 
  brackets, that is, don't let the unit withstand the 
  weight of it.
* For the Super Free Match system, each pipe should 
  be labeled to tell which system it belongs to avoid 
  mistaken inaccurate piping.

INST

ALLER'S 

INSTRUCTION

Within ±

 

30

Within ±

 

30

Содержание SYMPHONY CHOIR 80CH

Страница 1: ... Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City or Local Codes and related manuals from us Otherwise damage to equipment or property even injury to people may occur Installer Currently licensed HVAC installer only Read this manual before installation Sign on the warranty registration card User Keep this ma...

Страница 2: ...ORTANT NOTE YMGI HOLDS FINAL EXPLANATION The quality of the installation plays a key role in whether the units will work well and for an extended period of time The information we provide in our manuals is for the sole purpose of reminding you and your installer It is our ultimate goal to help insure that your YMGI units are installed properly and correctly from the very beginning to the very end ...

Страница 3: ...re humidity ranges installation operation maintenance service warranty parts and so on 4 Properly select correct most suitable YMGI product models of units and accessories for your HVAC applications jobs and list them in your proposal quote in writing on your company s quote form or letter head basing upon the information you get from 1 2 and 3 above 5 List your currently valid HVAC license and EP...

Страница 4: ... the installation 5 Supply electrical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC circuit breaker fuse or disconnect switch to the outdoor unit 11 What is the refrigerant pipe length between each indoor unit and the outdoor unit Unit A Unit B Unit C U...

Страница 5: ... the tools to do these calculations correctly and get your approval before purchasing the air conditioner or heat pump equipment Any problems due to improper installing of the air conditioner heat pump system Installation should be conducted by currently licensed HVAC technician following manufacturer installation instructions all governing safety codes with care and professionalism Any problems d...

Страница 6: ...the appointed service center A place which is full of machine oil A region with saline sodic soil near the sea A place where the sulphide fog exists such as the sulphur spring A place where the high frequency facilities exist such as radio equipment electric welder and medical equipment An environment with special conditions 1 When the place of the installation is exposed to strong wind When stron...

Страница 7: ...is strength and level so that the unit will not cause any operating vibration or noise after installation 2 In accordance with the foundation drawing in the Fig 6 please drill 4 holes in the installation location A Discharge air side B Bottom view inches C Drain holes 3 Fix the unit securely with the foundation bolts You can get the M10 or M8 foundation bolts nuts and washers from the market 4 Rub...

Страница 8: ...RANT PIPES Y type branch pipe must be installed in vertical or horizontal direction In the inlet of the branch pipe keep at least 19 69inch straight pipe 1 Pipe connections should be follow the following rules Outdoor unit shall be installed close to the indoor unit hence to minimize the length and bends of connection pipes The gap of outdoor unit and indoor units should be as small as possible Th...

Страница 9: ...e operation 2 As shown in the following figure expel the gas from the refrigerant pipes by the vacuum pump 3 Open the pump and turn on the knobs to evacuate the gas in the liquid and gas pipes 4 When the pressure of the system is less than 0 1Mpa 1bar keep the system for more than one hour under the condition 5 Then turn off the knobs and the pump and if the pressure of the pressure vacuum gauge d...

Страница 10: ...sure vacuum gauge 6 7 8 9 Hi knob Lo knob R410A tank Scale When the liquid and gas stop valves have not been opened the system is under the vacuum 1 Refer to the left of the Fig 20 connect the R410A tank to the system 2 Turn on the R410A tank and the Hi knob charge the R410A refrigerant into the system from the liquid side stop valve The Lo knob should be closed completely 3 Turn off the R410A tan...

Страница 11: ...ground terminal should be provided and the ground wire cannot be connected to any of the following places a Water pipe b Coal gas pipe c Sewage pipe d Lightning rod e Telephone line f Other unreliable places considered by a professional ELECTRICAL WIRING WORK The ground connection should be reliable and the ground wire should be connected to the dedicated device of the building by the professional...

Страница 12: ... or outdoor unit is blocked Remove the obstacles Air inlet or outlet of indoor unit or outdoor unit is blocked Remove the obstacles Temperature setting is improper Adjust the setting of remote controller or wire controller Air speed is set too low Adjust the setting of remote controller or wire controller Improper airflow direction Adjust the setting of remote controller or wire controller Door or...

Страница 13: ... board of the outdoor unit Check for more details about the meaning of each error Conditions Causes When restart the unit soon after it is stopped The overload protection switch of the unit let the startup delayed for three minutes As soon as power supply is on The unit will stand by for approximate one minute When the cooling operation starts The hi humidity air indoor is cooled quickly The unit ...

Страница 14: ...ing to include a 1 year installation service warranty at no extra charge Check with them to see if that is available If available include that in the contract 14 Verify and confirm the installation is done completely and all the unit functions have been checked and are working properly all the items in the checklist have been checked and marked well in the warranty registration card form prior to ...

Страница 15: ...e exceptions Most have resulted in equipment failure due to lack of knowledge and experience A few of the problems result from DIY s lack of knowledge in the following areas Sizing and selecting correct type size and model of cooling and or heating equipment Sizing and installing correct electric circuit breakers and wires Wiring the units correctly and properly Taping the ends connecting to indoo...

Страница 16: ...different from what are typical in traditional split type air conditioning and heat pump systems and similar systems made by other manufacturers These are not defects Take some time to learn the functions of your unit We will be happy to assist you with any questions you may have concerning the functions of your new unit 1 Part repair or replacement after trouble shooting This is the most common a...

Страница 17: ...ND INSTALLATION SERVICE MAINTENANCE NOTES Notes Asked for Your Technician for Help Did You Ask YMGI Tech for Help INSTALLATION NOTES Original Installation Company Name Technician Name Phone HVAC License Job Not Performed by Technician Technician Checklist Completed Fully SERVICE MAINTENANCE NOTES No Date Contents of Service Maintenance Technician s Company Name Technician Name Phone HVAC License P...

Отзывы: