Pg. 9
Controller Settings
When charged with controller, and the controller output is used to connect load:
It is recommended that the controller is set to the following parameters to avoid failure of the battery
to recover when the BMS cut off the battery for protection after a continuous small current
discharge.
Max charge voltage: 14.6V
Overcharge protection voltage: 14.8V
Overcharge recovery voltage: 14.2V
Discharge cut-off voltage: 11.2V
Over-discharge recovery voltage: 11.6V
The above settings ensure that the controller triggers its protection before the BMS does, thereby
prolonging the service life of the battery.
If solar charging is used, please set the regulator to LiFePO4 charging mode.
LCD Screen
1.
Press the function key once and the screen will light up to display the battery voltage.
2.
Press the function button again to display the State of Charge (SOC).
3.
On the third press, the display screen will turn off.