![yellow jacket AccuProbe UV Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/yellow-jacket/accuprobe-uv/accuprobe-uv_instruction-and-operation-manual_3292109007.webp)
7
PROBLEM
CHECK
REPAIR OR REPLACE
No power
Check for weak or reversed
batteries
Replace batteries
Stays in "warm up"
mode
Sensor not plugged into socket
correctly
Sensor open/defective
Make sure sensor is pushed all the
way down into socket
Replace sensor
No detection
Check sensor with leak standard
bottle
Check if the filter is dirty or sensor
opening is plugged
Replace sensor
Replace filter or clean out opening
Slow recovery after
detection
Check if filter is dirty or sensor
opening is plugged
Replace filter or clean out opening
No beeping
Nothing
Press mute button (if equipped)
to turn speaker back on
Troubleshooting Guide
Replacement Parts
AccuProbe UV
and
AccuProbe II
Parts kit (sensor, filters and leak standard bottle)
69383
Sensor and filter
69384
Sensor filters (package of 5)
69385
Leak standard bottle
69386
A/C Adapter Input: 115V 60Hz
UL
listed
69380
A/C Adapter
—
EU/UK Plug Input: 230V 50Hz
CE
&
T
Ü
V
Approved
69381
A/C Adapter
—
AU/NZ Plug Input: 230V 50Hz
CE
&
T
Ü
V
Approved
69378
Battery cover and screw
69388
Carrying case - blow molded with inserts
69387
AccuProbe II
Carrying pouch
69361
AccuProbe UV
Certified to the European Standard EN 14624 (Section 13)
Minimum sensitivity R-134a fixed position
1 gram/year
Maximum sensitivity R-134a fixed position
>50 gram/year
Minimum sensitivity R-134a in motion
3 gram/year
Maximum sensitivity R-134a in motion
>50 gram/year
Minimum time for detection 1 gram/yr R-134a
1 second
Zeroing time for 50 grams/yr exposure
Approximately 12 seconds
Minimum sensitivity in polluted ambience
1 gram/year fixed; 3 grams/year moving
Calibration frequency
Check annually with calibrated leak source