ML-x17 DATA LOGGER MANUAL
Manufacturers of low power instruments
page 62
4.20.2.1
Send interval
The send interval on which the data is send to the radio. This can be another send interval than the
internal modem has. More on send interval see:
Send Interval
Note:
only parameters which are configured to output data to Radio will be included in a radio message.
4.20.2.2
Send delay
When the user likes an time offset in respect to the send interval he can set this offset here. This is
practical, using multiple radio’s they must NOT be sending simultaneously. The send interval can be the
same for each data logger, but each data logger must have a different send delay, in order to avoid the
radios to transmit simultaneously.
4.20.2.3
Power down delay
The logger is often faster than the connected radio device. When the logger has send its data string to the
radio, the radio needs some time to send it over the air. This time is defined here (default 5 seconds).
Radio
settings
[0] Exit
[1] Name >> Radio
[2] Port settings >> RS232 8N1; 4800 Baud
[3] Module power switch >> Enabled; Warm up 00:00:01
[4] Send interval >> 00:00:10
[5] Send delay >> Not used
[6] Power down delay >>
00:00:05
[R] Remove
>